Extron electronics PVM 220 Installation Manual Download Page 4

 

4

PVM 220 • Installation Guide (Continued)

Step 5 — Run signal and control cables to the PVM 220.

Run the signal and control cables either into cable clamps or through 
conduit attached to the PVM 220 enclosure (see figure 7). 
To install a cable clamp on the enclosure:

a. 

Select a suitable sized cable clamp for the quantity and  
thickness of cable to be fed into the enclosure (see the 

Notes

 

on page 3, Step 4 for knockout sizes).

b. 

Identify the most suitable cable entry point and remove one 
or more knockouts as needed.

NOTE:

  Remove only the knockouts that are to be used for 

cabling. Leave intact the unused knockouts.

c. 

Remove the large nut from the back of the cable clamp and 
insert the clamp into the enclosure knockout from the inside.

d. 

Place the nut on the clamp and tighten to secure.

e. 

Pass the cables through the clamp into the enclosure. Leave  
enough cable slack at the PVM 220 to ensure cable connection 
to any device is maintained when the access door is open.

f. 

Tighten down the cable clamp until the cables are held firmly. 
Avoid damaging or bending cables at too sharp an angle.

NOTE:

  See the 

PoleVault System Installation Guide

 for full 

cable connection details. 

Step 6 — Install devices onto the device mounting plate.

NOTE:

  The maximum door load is 15 lbs (6.8 kg).

To mount the devices and accessories:

a. 

If mounting a PoleVault (PVS) switcher, carefully align the  
switcher with the appropriate holes in the marked location on  
the device mounting plate (the location is  indicated by a white  
device outline and 2 arrows, see figure 8).  
Non-PVS devices can be mounted anywhere within the enclosure. 

NOTE:

  The PVS switcher must be mounted in the 

designated area ONLY. This ensures that the switcher is 
positioned correctly for proper ventilation.

b. 

Secure the PVS switcher with the supplied #4-40, 

3/16 inch  

mounting screws, tightening each one until snug. Do not 
overtighten.

c. 

Align the power supply with the appropriate holes in the marked 
location on the device mounting plate (location is indicated  
by a white device outline and 3 arrows). Secure using the 
supplied screws.

NOTE:

  Replacement power supplies must be either the 

equivalent Extron power supply, or a UL Listed NEC 
Class 2 power supply.

d. 

Mount all other devices following the procedures in the  
supplied device guide.

PVS 4

05SA 

IP

POLE

VAU

LT SW

ITCH

ER

INPU

TS

AUD

IO LE

VEL A

DJU

ST

PAGIN

G

SENS

OR

SEN

SITIV

ITY

PEA

K

NOR

MAL

SIGN

AL

VOICE

LIFT

PEA

K

NOR

MAL

SIGN

AL

INPU

T

SELEC

T

CON

FIG

R

1
2

3
4

5

A

U

X

A

U

D

IO

E

Mount the PoleVault
switcher with the front 
panel facing outwards
in the marked location.

Mount other optional 
devices as desired.

Mount the PoleVault 
Switcher Power Supply
in the marked location. 

Device
Mounting Plate

ò

ô

õ

Figure 8. 

PVS Switcher and Power Supply Mounting 
Locations on Device Mounting Plate.

ì

 Push the cable clamp into the

   knockout from inside the enclosure.

í

 Attach the nut from the outside

    of the enclosure.

Figure 7. 

Install a cable clamp on the PVM 220 
enclosure (viewed from above).

POWER

SUPPLY

POLEVAULT SWITCHER

Figure 9. 

Install the devices onto the mounting plate.

Reviews: