Day
Checkmarks indicate which day are members of the set. From Sunday to Saturday.
Interval
There are 48 time interval one day. Each interval has 30 minutes.
•
Start - Select the start hour and minute.
•
End - Select the end hour and minute.
Action
•
Power On - Select the radio button to apply power on during the interval.
•
Power Off - Select the radio button to apply power off during the interval.
PoE Power Reset
The entry is used to control the power reset time on PoE port.
It is allowed to create at maximum five entries for each PoE port.
PoE Example 1
1. Parameter Setting:
•
Reserved Power determined: Class
•
Power Management Mode: Actual Consumption
•
Primary Power Supply: 6W
2. Test Port
•
Port 1: 802.3at with critical priority
•
Port 2: 802.3af with high priority
•
Port 3: 802.3af with low priority
3. PD Power Consumption
•
Port 1: 1.3 watt (PoE Splitter)
•
Port 2: 1.3 watt (PoE VoIP Phone)
•
Port 3: 3.8 watt (PoE WiFi AP)
4. Web Configuration
PoE Power Scheduling & Reset
ISW Application Guides
78
ISW Series Managed Industrial Ethernet Switch Hardware Installation & User Guide