Managing cables
The minimum radius that a 50 micron cable can be bent under full tensile load is 5.1 cm (2 in.). For a cable under no tensile load, that
minimum is 3.0 cm (1.2 in.). Cables can be organized and managed in a variety of ways, for example, using cable channels on the sides
of the rack or patch panels to minimize cable management. Following is a list of additonal recommendations:
•
Plan for rack space required for cable management before installing the device.
•
Leave at least 1 m (3.28 ft) of slack for each port cable. This provides room to remove and replace the device, allows for
inadvertent movement of the rack, and helps prevent the cables from being bent to less than the minimum bend radius.
•
For easier maintenance, label the fiber-optic cables and record the devices to which they are connected.
•
Keep LEDs visible by routing port cables and other cables away from the LEDs.
•
Do not route the cables in front of air vents.
•
Use Velcro
®
type straps to secure and organize fiber-optic cables.
•
Route the cables away from LEDs to keep them visible.
•
Use the cable management comb that attaches to the chassis for simple cable management. The comb can be installed without
service disruption.
CAUTION
Before plugging a cable into any port, be sure to discharge the voltage stored on the cable by touching the electrical
contacts to ground surface.
NOTE
Do not use tie wraps with optical cables because they are easily overtightened and can damage the optic
fibers.
Installing an SFP+ transceiver
While non-Extreme optics are supported, Extreme-qualified transceivers are recommended. The port might not become operational
using unqualified transceivers.
To insert an SFP+ transceiver, complete the following steps.
NOTE
Route cables to the side so that the line cards can be removed without disturbing the cables to the other line cards.
Installing an SFP+ transceiver
ExtremeRouting SLX 9850-4 Hardware Installation Guide
9035474-02 Rev AA
127
Summary of Contents for ExtremeRouting SLX 9850-4
Page 10: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 10 9035474 02 Rev AA...
Page 22: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 22 9035474 02 Rev AA...
Page 30: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 30 9035474 02 Rev AA...
Page 56: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 56 9035474 02 Rev AA...
Page 94: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 94 9035474 02 Rev AA...
Page 102: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 102 9035474 02 Rev AA...
Page 114: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 114 9035474 02 Rev AA...
Page 118: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 118 9035474 02 Rev AA...
Page 136: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 136 9035474 02 Rev AA...
Page 146: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 146 9035474 02 Rev AA...
Page 150: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 150 9035474 02 Rev AA...