Lifting precautions
DANGER
Use safe lifting practices when moving the product.
DANGER
A fully populated ExtremeRouting SLX 9850-4 weighs approximately 137.4 kg (303 lb) and requires a hydraulic or
assisted lift to install it.
Laser precautions
DANGER
All fiber-optic interfaces use Class 1 lasers.
DANGER
Laser Radiation. Do Not View Directly with Optical Instruments. Class 1M Laser Products.
DANGER
Use only optical transceivers that are qualified by Extreme Networks, Inc. and comply with the FDA Class 1 radiation
performance requirements defined in 21 CFR Subchapter I, and with IEC 60825 and EN60825. Optical products that do
not comply with these standards might emit light that is hazardous to the eyes.
Facility requirements
Before installing the device, be sure the following facility requirements are met.
TABLE 14
Facility requirements
Type
Requirements
Device specifications
Ensure that the facility can accommodate system, power, and environmental specifications for this device as
outlined in the
ExtremeRouting SLX 9850 Technical Specifications
on page 137 .
Electrical
Ensure that there are dedicated electrical branch circuits with the following characteristics:
•
Protected by a circuit breaker in accordance with local electrical codes
•
Supply circuit, line fusing, and wire size adequate to the electrical rating on the chassis nameplate
•
Location close to the chassis and easily accessible
•
Grounded outlets installed by a licensed electrician and compatible with the power cords
Thermal
Ensure that the air intake and exhaust vents have a minimum of 5.1 cm (2 in.) of airspace.
Ensure that the air temperature on the air intake side is less than 40°C (104°F) during operation.
Rack
Plan to install the device with the port side facing the air-intake aisle.
Ensure that the following amount of space is available in the rack:
•
SLX 9850-4: 10 rack unit (RU) height x 17.22 inches (43.7 cm) width x 30 inches (76.2 cm) depth.
Ensure that the rack meets these additional requirements:
•
All equipment in the rack is grounded through a reliable branch circuit connection.
•
Additional weight of chassis will not exceed the rack’s weight limits
•
The rack is secured to ensure stability in case of unexpected movement.
Facility requirements
ExtremeRouting SLX 9850-4 Hardware Installation Guide
24
9035474-02 Rev AA
Summary of Contents for ExtremeRouting SLX 9850-4
Page 10: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 10 9035474 02 Rev AA...
Page 22: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 22 9035474 02 Rev AA...
Page 30: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 30 9035474 02 Rev AA...
Page 56: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 56 9035474 02 Rev AA...
Page 94: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 94 9035474 02 Rev AA...
Page 102: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 102 9035474 02 Rev AA...
Page 114: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 114 9035474 02 Rev AA...
Page 118: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 118 9035474 02 Rev AA...
Page 136: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 136 9035474 02 Rev AA...
Page 146: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 146 9035474 02 Rev AA...
Page 150: ...ExtremeRouting SLX 9850 4 Hardware Installation Guide 150 9035474 02 Rev AA...