background image

ML434_ES | v11

Page

6

Expo Technologies UK

T: +44 (0) 20 8398 8011
E: [email protected]

Expo Technologies US

T: +1 (440) 247 5314
E:[email protected]

Expo Technologies China

T: +86 532 8906 9858
E: [email protected]

Section 4: Description and Principle of Operation

The MiniPurge

®

 system is pneumatic in operation, with electrical interfaces.

Purge and pressurization is a method of protection used in Zone 1 (21) and/or Zone 2 (22) hazardous locations 
to ensure that the interior of an enclosure is free of flammable gas. Addition of a MiniPurge

®

 system allows 

the electrical equipment within the enclosure to be used safely in a hazardous location.

The principle of purge and pressurization is as follows:

• Clean compressed air or inert gas is drawn from a non-hazardous location.

• The interior of the pressurized enclosure is flushed to remove any hazardous gas or dust.

• This is introduced into the pressurized enclosure to keep the internal pressure at least 0.5 mbarg above the

external pressure.

• Whilst pressurized, flammable gas cannot enter the enclosure from the environment.

Prior to switching on the power to the electrical equipment, the enclosure must be purged to remove any 
flammable gas that might have entered the enclosure before pressurization. Purging is the process of removal 
contaminated air and replacement with air (or inert gas) known to be free from flammable gas. The duration 
of this purge process is normally ascertained by performing a purge test.

At the end of the purge cycle the system automatically switches to leakage compensation mode. The Purge 
Outlet Valve is closed and the airflow is reduced but remains high enough to compensate for the leakage of 
air from the enclosure whilst maintaining the minimum over pressure state.

In the event of pressure failure within the pressurized enclosure the system will raise an alarm in the form of 
visual indicators and a volt free contact depending on the specification of the system. The default action on 
loss of pressurization is alarm and automatic disconnect of power (A&T - Alarm and Trip). This can be changed 
by the customer to Alarm Only (/AO), please refer to section titled Main Components.

The MiniPurge

®

 system incorporates a Closed Loop Automatic Pressurization System (CLAPS). This allows the 

system to detect a rise or fall of the enclosure’s internal pressure and adjust the leakage compensation rate 
accordingly. Pressure variations are more likely during sudden start up of large rotating electrical machines but 
can also be caused by changes in running temperature. This system has been specifically designed to maintain 
a stable internal pressure within the enclosure.

Pressure characteristics during purge and pressurization of a pressurized enclosure using a MiniPurge

®

 system 

that incorporates a CLAPS system:

Intermediate Pressure

Sensor Pressure

Power Interlock switch

Alarm &Trip

Purge Time

Machinery Start

Normal Operation

CLAPS Regulator

Pressure

Intermediate switch contacts

open. Intermediate sensor

sends falling pressure signal

Fault Condition - loss of pressure

outside of CLAPS regulation

Minimum Pressure

Sensor Pressure

Purging Pressure

Minimum pressure switch contacts

open. Minimum pressure sensor sends

a low pressure signal.
Alarm indicator shows red (alarm only)

Alarm indicator shows red and power

is disconnected (Alarm and Trip)

Minimum

pressure switch

Intermediate

pressure switch

Power Interlock switch

Alarm Only

Contacts

Active

Inactive

Summary of Contents for MiniPurge D758-ES

Page 1: ...w these instructions Please refer to the standard for principles and definition These instructions apply only to the pressurizing system it is the responsibility of the manufacturer of the pressurized...

Page 2: ...S Regulator 9 Relief Valve Unit 9 PA Terminal Box 10 Section 6 Installation of the System 10 Relief Valve Unit 10 Air Supply Quality 10 Pipe Work 11 Multiple Enclosures 11 Provision and Installation o...

Page 3: ...Ex rules Directive 2014 34 EU or UKCA Regulations as applicable For further details refer to the applicable certificates 5 X LC ss ES OV PA PC Size 5 MiniPurge Purge flow rate 6000 NI min Approval Cer...

Page 4: ...5 mm 1 ID tube inlet sized appropriately for flow rate Reference points signals 1 8 NPT female minimum 6 mm pipe to be used Visual Indicators Alarm Red Pressurized Green System Purging 4 LEDs that fla...

Page 5: ...10 mbarg Tolerance 0 10 Note there must be a 2 5 mbarg difference between the intermediate and CLAPS sensor calibration point For example Minimum pressure 5 mbarg intermediate pressure 6 5 mbarg CLAP...

Page 6: ...in air supply pressure during the purge process Operation of the System Once the system is installed correctly turn on the air supply Refer to Commissioning section The purge system commences the purg...

Page 7: ...ay be used in IECEx and ATEX Zone 1 and or Zone 2 Categories 2 and 3 respectively MiniPurge systems may be used for hazards of any gas group Apparatus associated with the MiniPurge system such as intr...

Page 8: ...educed but remains high enough to compensate for the leakage of air from the enclosure whilst maintaining the minimum over pressure state In the event of pressure failure within the pressurized enclos...

Page 9: ...o reset and the Alarm Pressurized indicator turns Red The sensor is factory calibrated and set to operate in falling pressure at or above the minimum specified pressure Purge Flow Sensor The Purge Flo...

Page 10: ...e sent to the purge complete valve Alarm Only Circuit AO If the pressure in the pressurized enclosure is too low the system will normally cut off electrical power to it In certain circumstances where...

Page 11: ...nimum required flow rate The Purge Flow Restrictor must be readjusted during commissioning CLAPS Sensor This sensor monitors the pressure within the pressurized enclosure and sends a control signal to...

Page 12: ...points where air enters and exits the pressurized enclosure should normally be at opposite ends of the enclosure The RLV unit must be mounted vertically and there should be a minimum clearance of 300...

Page 13: ...ppropriate to the environment into which the system is installed No valve may be fitted in any signal pipe connecting the Control Unit to the pressurized enclosure This pipe work must be fitted in acc...

Page 14: ...must be replaced after any short circuit that occurs within the main circuit the switch is a piece of encapsulated equipment and as such it is not possible to check the state of the contacts Technical...

Page 15: ...ll disable all of the pressure sensors Using a 4 mm nylon tube connect a manometer to the bulkhead fitting from which the minimum pressure sensing pipe was removed Open the Purge Flow Restrictor Valve...

Page 16: ...operation of Minimum Pressure Sensor check readings on manometer as system will automatically re purge when it reaches minimum pressure 21 While the system re purges return the CLAPS Regulator to the...

Page 17: ...us is suitable for use in the hazardous location There are no unauthorised modifications The air supply is uncontaminated The interlocks and alarms function correctly Approval labels are legible and u...

Page 18: ...thread sealant If the thread has seized up remove to a safe area and heat slightly to soften prior to making any adjustment This prevents potential damage to the brass of the nozzle Disconnect pipe w...

Page 19: ...s been designed for ease of fault finding and many of the components fitted are plug in or chassis mounted Check components by substitution only after establishing that such action is necessary Before...

Page 20: ...uring purge Check air supply pressure at the inlet to the control unit Ensure that the supply pipe bore is suitable for the flow rate Pressurized Enclosure Excessive leakage from the pressurized enclo...

Page 21: ...06 Purge flow sensor factory set to 6 4 mbarg S0030 016 Minimum Pressure sensor must be factory set to the value as stated on the Customer Test and Inspection Sheet HSI 0160 000 Intermediate pressure...

Page 22: ...ystem Status Indication TP 518 058 WD 2 Component Certificate Number Purge System EU Declaration of Conformity SC004 UKCA Declaration of Conformity SC004 UK ATEX Certificate SIRA 01ATEX1295X IECEx Cer...

Page 23: ...2 67 1 66 67 8 77 1 6 67 1 66 67 5 1 352 7 21 7KH FRQWHQWV RI WKLV GUDZLQJ GRFXPHQW DUH RS ULJKW SR 7HFKQRORJLHV LPLWHG 7KH DUH WR EH WUHDWHG DV FRQILGHQWLDO DQG DUH UHWXUQDEOH XSRQ UHTXHVW 7KH DUH Q...

Page 24: ...85 7 0 5 752 31 80 7 32 5 6833 336 1 725 50 35 6685 1 725 6 67 0 385 1 0 1 385 28 1 725 7 50 1 5 7 50 1 6 203 17 3 7 50 1 2 67 1 66 67 28 9 6 1 3527 725 5 1 352 7 21 7KH FRQWHQWV RI WKLV GUDZLQJ GRFXP...

Page 25: ...to be treated as confidential and are returnable upon request They are not to be copied or communicated in part or in whole without written consent from Expo Technologies Limited neither are they to b...

Page 26: ...6mm I D 1 8 NPT TEST POINT NORMALLY PLUGGED 1 8 NPT PRIMARY ENCLOSURE PRESSURE 1 4 6mm I D B C D E F 8 5 7 6 4 3 1 2 3RD ANGLE PROJECTION The contents of this drawing document are Copyright Expo Techn...

Page 27: ...e they to be used in any way against our interests DIMENSIONS IN mm DENOTES IMPERIAL WEIGHT Kg TITLE DO NOT SCALE IF IN DOUBT ASK FINISH MATERIAL A3 SCALE DRAWING STATUS A TOLERANCES UNLESS OTHERWISE...

Page 28: ...55 C 250V 4A AC 15 SYSTEM PURGING CONTACTS GREY BLACK BROWN 1 2 3 4 B C D E F 8 5 7 6 4 3 1 2 3RD ANGLE PROJECTION The contents of this drawing document are Copyright Expo Technologies Limited They ar...

Page 29: ...IF IN DOUBT ASK FINISH MATERIAL A3 SCALE DRAWING STATUS A TOLERANCES UNLESS OTHERWISE STATED FLATNESS TO BE LESS THAN 0 4 OVER ANY 100mm LENGTH ANGLE STD 1 MOD REVISION DRAWN CHECKED APPROVED DATE DR...

Page 30: ...76 72 68 7 0 02817 1 7 6 5 1 352 7 21 7KH FRQWHQWV RI WKLV GUDZLQJ GRFXPHQW DUH RS ULJKW SR 7HFKQRORJLHV LPLWHG 7KH DUH WR EH WUHDWHG DV FRQILGHQWLDO DQG DUH UHWXUQDEOH XSRQ UHTXHVW 7KH DUH QRW WR EH...

Page 31: ...ORZ 2 ODFN 3XUJH IORZ WRR ORZ 3XUJH ORZ 6HQVRU WXUQV RQ HV 1R 3XUJH 2XWOHW IORZ DERYH WKH PLQLPXP 5HOLHI 9DOYH RSHQV 3XUJH IORZ VWDUWV 3UHVVXUL HG VLJQDO WR UHPRWH DODUP VZLWFK 35 6685 1 725 UHHQ 3UHV...

Page 32: ...QRORJLHV LPLWHG 7KH DUH WR EH WUHDWHG DV FRQILGHQWLDO DQG DUH UHWXUQDEOH XSRQ UHTXHVW 7KH DUH QRW WR EH FRSLHG RU FRPPXQLFDWHG LQ SDUW RU LQ ZKROH ZLWKRXW ZULWWHQ FRQVHQW IURP SR 7HFKQRORJLHV LPLWHG Q...

Page 33: ...o further guidance for the selection of cable and cable glands or conductors in conduit When the MIU e application requires the hazardous area marking code Ex eb IIC T4 Gb Tamb 20 C to 60 C the user s...

Page 34: ......

Page 35: ......

Page 36: ...19ATEX0542X...

Page 37: ......

Page 38: ......

Page 39: ...chnologies UK Expo Technologies Ltd Unit 2 The Summit Hanworth Road Sunbury On Thames TW16 5DB UK T 44 20 8398 8011 F 44 20 8398 8014 E sales expoworldwide com Expo Technologies China Qingdao Expo M E...

Reviews: