background image

Page

1

ML548 | v11

Expo Technologies UK

T: +44 (0) 20 8398 8011

E: [email protected]

Expo Technologies US

T: +1 (440) 247 5314

E:[email protected]

Expo Technologies China

T: +86 532 8906 9858

E: [email protected]

Section 1: System Specification

                                         

Conditions of Safe Operation

The D760 design permits system operation in external ambient temperatures down to -60°C. Installation & 
safe use requires the internal heater to be connected to maintain both the internal ambient temperature and 
the temperature of the logic air supply above -20°C. Temperature sensors are provided for user connection, and 
it is the users responsibility to not initiate purge unless these temperature conditions are met.

Temperature sensors (PT100 RTDs) are provided for user monitoring of internal ambient temperature and logic 
air supply temperature. The individual sensors are each 4-wire devices with all 4 wires brought to terminals in 
the system junction box. The RTDs are to be treated as 'simple apparatus' intrinsically safe components - see 
EXPO 20MDOC1403X as attached. Users may decide to connect RTD monitoring circuits as 2-, 3- or 4-wire 
circuits as preferred. The temperature monitoring circuits themselves are provided by others.

If the logic air supply temperature falls below -10°C, this should be investigated and rectified. If the logic air 
supply falls below -20°C, the purge system will be operating outside of its certification parameters and should 
be stopped. The purge system can only be re-initiated when the logic air supply is above -20°C.

If the internal ambient temperature falls below -20°C, this should be investigated and rectified.

5    X     LC  /  ss  /  ET  /  OV  /  PA  /  PC / LT

Size 

5 = MiniPurge

®

Purge flow rate:
2000 - 6000 NI/min

Approval / Certification

Sira 01ATEX1295X 

 2813 

 II 2(2) G 

Ex [pxb] db e ia IIC T4 Gb
T

amb

 -60ºC to +55ºC

IECEx SIR07.0027X
Ex [pxb] db e ia IIC T4 Gb
T

amb

 -60ºC to +55ºC

PC

 = Pressurized Control. Automatic 

leakage compensation (CLAPS)

OV

 = Purge Outlet Valve is pneumatically 

operated

Timing Method
ET

 = Electronic Timer

MiniPurge

®

 Housing

ss

 = Stainless Steel 316L

Pressurization Method
LC

 = Leakage Compensation

ATEX Certificate:

IECEx Certificate:

PA

 = Power and Alarm Switches. 

Integral /PA Terminal Box

LT

 = Low Temperature

2020312304000830
Ex [px] d e ia IIC T4 Gb
T

amb

 -60ºC to +55ºC

CCC Certificate:

EAC Certificate:

ЕАЭС RU С-GB.АЖ58.В.00906/20

1Ex [px] d e mb ia IIC T4 Gb
(-60°C ≤ T

amb

 ≤ +55°C)

CSAE 21UKEX1067X 

 2813 

 II 2(2) G 

Ex [pxb] db e ia IIC T4 Gb
T

amb

 -60ºC to +55ºC

UKEX Certificate:

Summary of Contents for D760-ET MiniPurge

Page 1: ...hese instructions Please refer to the standard for principles and definition These instructions apply only to the pressurizing system it is the responsibility of the manufacturer of the pressurized en...

Page 2: ...CLAPS Sensor 10 CLAPS Regulator 10 Relief Valve Unit 10 PA Terminal Box 10 Thermostat and Heater 10 Section 6 Installation of the System 11 Relief Valve Unit 11 Air Supply Quality 11 Pipe Work 12 Mult...

Page 3: ...ML548 v10 ii Section 11 Glossary 19 Section 12 Drawings and Diagrams 19 Section 13 Certifications 20...

Page 4: ...circuits as preferred The temperature monitoring circuits themselves are provided by others If the logic air supply temperature falls below 10 C this should be investigated and rectified If the logic...

Page 5: ...to 2 5 barg 36 psi Process Connections Purge supply and outlet to pressurized enclosure 1 NPT female Minimum supply line 25 mm 1 ID tube inlet sized appropriately for flow rate Reference points signa...

Page 6: ...arg Tolerance 0 10 Note there must be a 2 5 mbarg difference between the intermediate and CLAPS sensor calibration point For example Minimum pressure 5 mbarg intermediate pressure 6 5 mbarg CLAPS sens...

Page 7: ...n air supply pressure during the purge process Operation of the System Once the system is installed correctly turn on the air supply Refer to Commissioning section The purge system commences the purge...

Page 8: ...y be used in IECEx and ATEX Zone 1 and or Zone 2 Categories 2 and 3 respectively MiniPurge systems may be used for hazards of any gas group Apparatus associated with the MiniPurge system such as intri...

Page 9: ...e enclosure before pressurization Purging is the process of removal contaminated air and replacement with air or inert gas known to be free from flammable gas The duration of this purge process is nor...

Page 10: ...he Alarm Pressurized indicator turns Red The sensor is factory calibrated and set to operate in falling pressure at or above the minimum specified pressure Purge Flow Sensor The Purge Flow Sensor moni...

Page 11: ...ical supply to the pressurized enclosure and to reduce the high purge flow rate to leakage compensation mode It also provides a hold on signal that maintains the leakage compensation mode with the pow...

Page 12: ...from the switch is terminated in the PA terminal box Intermediate Switch This is a flameproof switch which is activated by the signal from the Intermediate Sensor The cable from the switch is termina...

Page 13: ...tlet Valve is closed and the enclosure sealed The Relief Valve Unit has an in built relief valve This is sized to ensure that if the air supply pressure rises up from the specified maximum the interna...

Page 14: ...might affect the calibration of the device In particular the exterior of the spark arrestor should not be painted or blocked in any way Air Supply Quality The MiniPurge system should be connected to...

Page 15: ...minal boxes Provision and Installation of Alarm Devices When the pressure inside the pressurized enclosure is above the minimum the Minimum Pressure Sensor re turns a positive pressurized signal causi...

Page 16: ...nuity meter Gauge manometer 0 to 200 mbarg Differential manometer 2 off 4mm plugs If after commissioning the system does not perform as expected refer to the Fault Finding Section Follow the steps as...

Page 17: ...be changed by removing the large cover plate from over the outlet valve assembly and screws Warning When opening the Purge Flow Regulator ensure the over pressure within the enclosure does not exceed...

Page 18: ...nual should be supplemented with any additional requirements set out in appropriate local codes of practice The following checks should be carried out every 6 36 months dependent on environment accord...

Page 19: ...tment screw in position using the hex key loosen the retaining nut Adjust the hex key clockwise to increase or anti clockwise to reduce the lift off pressure Before testing retighten the locking nut w...

Page 20: ...been designed for ease of fault finding and many of the components fitted are plug in or chassis mounted Check components by substitution only after establishing that such action is necessary Before c...

Page 21: ...n the supply pipe Static pressure of 4 barg must be maintained during purge Check air supply pressure at the inlet to the control unit Ensure that the supply pipe bore is suitable for the flow rate Pr...

Page 22: ...must be factory set to the value as stated on the Customer Test and Inspection Sheet S0015 018 Pressure gauge Air Supply Pressure 0 10 barg S0015 135 Miniature gauge Logic Pressure 0 4 barg ETM IS31 0...

Page 23: ...ficate IECEx SIR07 0027X UKCA Certificate CSAE 21UKEX1067X CCC Certificate 2020312304000830 EAC Certificate RU GB 58 00906 20 Ex e Terminal Box ATEX Certificate BASEEFA 06ATEX0117X IECEx Certificate I...

Page 24: ...THERWISE STATED MOD No REVISION DRAWN CHECKED APPROVED DATE DRAWN DATE SURREY TW16 5DB UNITED KINGDOM Expo Technologies Limited DRAWING No REVISION RELEASED 14 04 2014 FLATNESS TO BE LESS THAN 0 4 OVE...

Page 25: ...X XXX 0 05 06 DQN 12429 30 06 2020 AR CE AR AR RJ CE 17 06 2020 DQN 12436 05 PB 21 11 2018 DQN 12414 04 SHEET No 2 OF 4 XBR 7TD0 106 DIMENSIONS IN mm DENOTES IMPERIAL DO NOT SCALE IF IN DOUBT ASK NOT...

Page 26: ...ALLY SEATED UNION 6 Ex e ELECTRICAL JUNCTION BOX 7 ELECTRONIC PURGE TIMER WITH LED INDICATOR 8 SYSTEM PURGING INDICATOR QUAD AMBER LEDS 9 LOW PRESSURE ALARM TRIP INDICATOR RED GREEN 10 ALARM PRESSURIZ...

Page 27: ...VISION RELEASED 14 04 2014 06 DECIMALS X 0 5 X X 0 2 X XX 0 1 X XXX 0 05 06 DQN 12429 30 06 2020 AR CE AR AR RJ CE 17 06 2020 DQN 12436 05 PB 21 11 2018 DQN 12414 04 SHEET No 4 OF 4 XBR 7TD0 106 DIMEN...

Page 28: ...interests DIMENSIONS IN mm DENOTES IMPERIAL WEIGHT Kg TITLE DO NOT SCALE IF IN DOUBT ASK FINISH MATERIAL A3 SCALE DRAWING STATUS A TOLERANCES UNLESS OTHERWISE STATED FLATNESS TO BE LESS THAN 0 4 OVER...

Page 29: ...NIMUM SIZE FOR PURGE AIR DISTRIBUTION PIPEWORK ELECTRICAL SIGNAL VIA EEx e JUNCTION BOX B C D E F 8 5 7 6 4 3 1 2 3RD ANGLE PROJECTION The contents of this drawing document are Copyright Expo Technolo...

Page 30: ...d IIC T6 OPTIONAL AC 15 4A 250V Ex d IIC T6 COMPLETE CONTACTS ALARM CONTACTS LOW PRESSURE HIGH PRESSURE INTERMEDIATE LOW PRESSURE SYSTEM PURGING PURGE PURGE INLET PRESSURE ENCLOSURE MOTOR ENCLOSURE PR...

Page 31: ...PPLY SUPPLY PT100 RTD SENSOR PT100 RTD SENSOR TYPICAL TYPICAL 4 WIRE BARRIER CONNECTION 4 WIRE BARRIER CONNECTION 1 SH SH B C D E F 8 5 7 6 4 3 1 2 3RD ANGLE PROJECTION The contents of this drawing do...

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ......

Page 41: ......

Page 42: ......

Page 43: ...2...

Page 44: ...2...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ......

Page 49: ......

Page 50: ......

Page 51: ...E info expoworldwide com Expo Technologies Ltd Registered in England No2854600 www expoworldwide com Expo Technologies purge pressurization systems may incorporate temperature sensors based on platin...

Page 52: ...chnologies UK Expo Technologies Ltd Unit 2 The Summit Hanworth Road Sunbury On Thames TW16 5DB UK T 44 20 8398 8011 F 44 20 8398 8014 E sales expoworldwide com Expo Technologies China Qingdao Expo M E...

Reviews: