background image

15 

 

2.4 $AA0

 

 

Description:

 

Perform Span Calibration

 

Syntax:

 

$AA0[CHK](cr) 

$    delimiter character 

AA    address of setting/response module (00 to FF) 

0    command for performing zero calibration 

Response: 

Valid Command:      

 

!AA

 

Invalid Command:     

?AA

 

 

Example : 

Command : $010                   Receive : !01 

Perform address 01 zero calibration on channel 0, return success. 

Command : $020                   Receive : ?02 

Perform address 02 zero calibration on channel 2 , return not 

enable calibration before perform calibration command. 

 

Warning: Pls don't calibrate before you really understand. 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for EX-9017F

Page 1: ...00 2400 4800 9600 19 2K 38 4K 15 2K Analog Input type 8 differential 6 differential 2 single ended Analog Channels Numbers 8 Analog Resolution 16 bits 12bits for 9017F series Unit Conversion 10V 5V 1V 500mV 150mV 20mA Sampling Rate 10 Samples Second Bandwidth 15 7 Hz Accuracy 0 1 Zero Drift 0 5µV C Span Drift 25ppm C CMR 50 60Hz 150dB NMR 50 60Hz 100dB Input Impedance 20M Ohms Current Measurement ...

Page 2: ...2 ...

Page 3: ...500mV 500mV 150mV 150mV Current Input 20mA 20mA with 125ohms resistor Sampling Rate 10 50Hz 10Hz 10 50Hz Bandwidth 15 7Hz Accuracy 0 1 Zero Drift 0 5µV C Span Drift 25ppm C CMR 50 60Hz 150dB NMR 50 60Hz 100dB Input Impedance 20M ohms Power supply 10V 30V Over voltage protection Not support 240Vrms Notes 1 Warm UP for 30 minutes is recommended before starting operation 2 EX 9017F EX 9017 w fast mod...

Page 4: ...re connection 1 2 1 Block Diagrams 1 2 2 Wiring diagram for the EX 9017 series EEPROM Single Controller RS485 Interface Power Supply 5V ADC Vin 6 Vin 0 EX9017 Data Data Vs GND Vin 7 Vin 6 Vin 0 Photo Isolation MUX Vin 1 Vin 1 Vin 7 mV V Vinx Vinx mA Vinx Vinx ...

Page 5: ...ile the jumper JP1 setting is 8 differential mode EX9017F Analog I P Channel 6 and 7 wire connection while the jumper JP1 setting is Init mode JP1 JP1 Vin6 Vin6 Vin7 INIT Vin7 JP1 Vin6 Vin6 Vin7 INIT Vin7 Vin6 Vin6 Vin7 INIT Vin7 Vin6 Vin6 Vin7 INIT Vin7 mA mA ...

Page 6: ...t Settings Default settings for the EX 9017 17F 17R 17FR modules are as follows Module Address 01 Analog Input Type type 05 Baud Rate 9600 bps Checksum disabled Engineering unit format Filter set at 60Hz rejection ...

Page 7: ...New EX9000 modules have the INIT switch located on the rear side of the module to allow easier access to the INIT mode For these modules INIT mode is accessed by sliding the INIT switch to the Init position as shown below To enable INIT mode please following these steps Step1 Power off the module Step2 Connect the INIT pin with the GND pin or sliding the INIT switch to the Init ON position Step3 P...

Page 8: ...nues and never halt The Host Watchdog is a software function to monitor the host s operating status Its purpose is to prevent the network from communication problem or host halt When the timeout interval expired the module will turn all outputs to predefined Safe Value This can prevent the controlled target from unexpected situation The EX9000 module with Dual Watchdog may let the control system m...

Page 9: ...20mA Calibration Sequence 1 Connect calibration voltage current to module s channel 0 2 Warm Up for 30 minutes 3 Set the input type of module which you wish to calibration 4 Enable Calibration P 24 5 Apply Zero Calibration Voltage 6 Preform Zero Calibration Command P 16 7 Apply Span Calibration Voltage 8 Perform Span Calibration Command P 15 9 Repeat step4 to step 8 three times Warning Please don ...

Page 10: ...t 5 0000 0 0000 5 0000 of F S R 100 00 000 00 100 00 09 5 5V 2 s complement 7FFF 0000 8000 Engineer unit 1 0000 0 0000 1 0000 of F S R 100 00 000 00 100 00 0A 1 1V 2 s complement 7FFF 0000 8000 Engineer unit 500 00 000 00 500 00 of F S R 100 00 000 00 100 00 0B 500 500mV 2 s complement 7FFF 0000 8000 Engineer unit 150 00 000 00 150 00 of F S R 100 00 000 00 100 00 0C 150 150mV 2 s complement 7FFF ...

Page 11: ...reserved DF Key Description DF Data format 00 Engineering unit 01 of FSR full scale range 10 2 s complement hexadecimal CS Checksum setting 0 Disabled 1 Enabled FS Filter setting 0 60Hz rejection 1 50Hz rejection Note The reserved bits should be zero ...

Page 12: ...change CC new baudrate for setting module FF new data format for setting module IF the configuration with new baudrate or new checksum setting before using this command the rear slide switch must be in the ON INIT position The new setting is saved in the EEPROM and will be effective after the next power on reset Response Valid Command AA Invalid Command AA Example Command 0203080602 Receive 02 Set...

Page 13: ...ile use AA command to EX9017F the data is the combination for each channel respectively Example Command 01 Receive 02 635 Read address 01 get data successfully Command 02 Receive 4C53 Read address 02 get data in HEX format successfully Command 04 Receive 05 123 04 153 07 234 02 356 10 000 05 133 02 34 5 08 234 The module address 04 is EX9017 Read address 04 for getting data of all 8 channels ...

Page 14: ... reading response module 00 to FF N channel to read from 0 to 7 Response Valid Command Data Invalid Command AA Data analog input value for its format Example Command 032 Receive 025 13 Read address 03 channel 2 get data successfully Command 029 Receive 02 Read address 02 channel 9 return error channel number ...

Page 15: ...ming zero calibration Response Valid Command AA Invalid Command AA Example Command 010 Receive 01 Perform address 01 zero calibration on channel 0 return success Command 020 Receive 02 Perform address 02 zero calibration on channel 2 return not enable calibration before perform calibration command Warning Pls don t calibrate before you really understand ...

Page 16: ...ming span calibration Response Valid Command AA Invalid Command AA Example Command 011 Receive 01 Perform address 01 span calibration on channel 0 return success Command 021 Receive 02 Perform address 02 span calibration on channel 2 return not enable calibration before perform calibration command Warning Pls don t calibrate before you really understand ...

Page 17: ...00 to FF 2 command for read configuration Response Valid Command AATTCCFF Invalid Command AA TT type code of module CC baudrate code of module FF data format of module Example Command 012 Receive 01080600 Read the configuration of module 01 input range of 10 10V baudrate 9600 no checksum Note check configuration Tables ...

Page 18: ... first word represents the status of channel 4 7 and the second word represents the status of channel 0 3 Value 0 means the channel is disabled value 1 means the channel is enabled Response Valid Command AA Invalid Command AA Example Command 0152A Receive 01 Set address 01 to enable channel 1 3 5 and disable channel 0 2 4 6 7 return success Command 016 Receive 012A Read address 01 channel status r...

Page 19: ...y the module as two binary words 4 bit The first word represents the status of channel 4 7 and the second word represents the status of channel 0 3 Value 0 means the channel is disabled value 1 means the channel is enabled Example Command 0152A Receive 01 Set address 01 to enable channel 1 3 5 and disable channel 0 2 4 6 7 return success Command 016 Receive 012A Reads Read address 01 channel statu...

Page 20: ...iter character AA address of reading response module 00 to FF F command for read firmware version Response Valid command AA Data Invalid command AA Data Firmware version of module Example Command 01F Receive 01M6 92 Read address 01 firmware version return version M6 92 ...

Page 21: ...CHK cr delimiter character AA address of reading response module 00 to FF M command for read module name Response Valid command AA Data Invalid command AA Data Name of module Example Command 01M Receive 019017 Read address 01 module name return name 9017 ...

Page 22: ...Disable calibration Response Valid Command AA Invalid Command AA Example Command 010 Receive 01 Perform address 01 span calibration return the command is invalid before enable calibration Command 01E1 Receive 01 Set address 01 to enable calibration return success Command 010 Receive 01 Preform address 01 span calibration return success Warning Pls don t calibrate before you really understand ...

Page 23: ...r delimiter character AA address of setting response module 00 to FF O command for set module name Data new name for module max 6 characters Response Valid command AA Invalid command AA Example Command 01O9017 Receive 01 Set address 01 module name 9017 return success ...

Page 24: ... 2 13 Description Host OK Host send this command to all modules for send the information Host OK Syntax CHK cr delimiter character command for all modules Response No response Example Command No response ...

Page 25: ... AA address of reading response module 00 to FF 0 command for read module status Response Valid command AASS Invalid command AA SS module status 00 host watchdog timeout status is clear 04 host watchdog timeout status is set The status will store into EEPROM and only may reset by the command AA1 ...

Page 26: ...1 Description Reset Module Host Watchdog Status Syntax AA1 CHK cr delimiter character AA address of setting response module 00 to FF 1 command for reset module status Response Valid command AA Invalid command AA ...

Page 27: ...aracter AA address of reading response module 00 to FF 2 command for read host watchdog timeout value Response Valid command AAEVV Invalid command AA E host watchdog enable status 1 Enable 0 Disable VV timeout value in HEX format each count is 0 1 second 01 0 1 second and FF 25 5 seconds ...

Page 28: ...ead address 01 modules status return host watchdog timeout status is clear Command 013164 Receive 01 Set address 01 host watchdog timeout value 10 0 seconds and enable host watchdog return success Command 012 Receive 01164 Read address 01 host watchdog timeout value return that host watchdog is enabled and time interval is 10 0 seconds Command No response Reset the host watchdog timer Wait for abo...

Page 29: ...ost watchdog timeout value return that host watchdog is disabled and time interval is 10 0 seconds Command 011 Receive 01 Reset address 01 host watchdog timeout status return success And the LED of this module stop flash Command 010 Receive 0100 Read address 01 module status return host watchdog timeout status is clear ...