2.2 #AA
Description:
Read Analog Input
Syntax:
#AA[CHK](cr)
# delimiter character
AA address of reading/response module(00 to FF)
Response:
Valid Command:
>(Data)
(Data) analog input value for its format while use #AA command
to EX9017F, the data is the combination for each channel
respectively.
Example :
Command :#01 Receive : >+02.635
Read address 01, get data successfully.
Command : #02 Receive : >4C53
Read address 02, get data in HEX format successfully.
Command : #04
Receive:>+05.123+04.153+07.234-02.356+10.000-05.133+02.34
5+08.234
The module address 04 is EX9017. Read address 04 for getting
data of all 8 channels.