MANUAL 

ESC system error codes 

Table 1: Luminaires’ errors  

ERROR 

REMARK 

ERROR 

CODE 

Battery disconnected 

Not to be noted in central battery use. 

E01 

Short circuit in battery 

Not to be noted in central battery use. 

E02 

Led disconnected 

 

E03 

Short circuit in LED 

 

E04 

Battery condition fail 

Not to be noted in central battery use. 

E05 

Battery failed during test. 

Not to be noted in central battery use. 

E08 

Battery disconnected 

Not to be noted in central battery use. 

E01 

Table 2: Central panel errors 

ERROR 

REMARK 

ERROR 

CODE 

Communication error 

Error in the communication between 

luminaire and panel. 

E14 

Blackout 

Not an actual error. Doesn’t need to be set 

off. Is noted in the error log. 

E15 

Low control voltage 

Control voltage drops, but doesn’t cause a 

blackout. 

E16 

Loop 1 dead 

Control voltage too low or fuse is broken. 

E17 

Loop 2 dead 

See above. 

E18 

Earth leakage in loop 1 

 

E19 

Earth leakage in loop 2 

 

E20 

Excess current in loop 1 

Overload in loop 1 

E21 

Excess current in loop 2 

Overload in loop 2 

E22 

Inverter or battery fail 

Inverter fail during test 

E23 

Inverter or battery fail 

Battery fail during test 

E24 

 

Summary of Contents for ESC-200P

Page 1: ...Hermiankatu 6 8 33720 Tampere 358 10 773 5400 info exilight com MANUAL Addressable Combination System ESC 200P...

Page 2: ...lights 4 Connect the small NiMH battery to panel printed circuit board and 12 V backup batteries to panels battery cables Backup batteries of panels have a voltage of 12 V 5 Connect power to central p...

Page 3: ...ntered with SET button and panel will be moved to next parameter New time will be set if all parameters are configured If one leaves the view with RIGHT button before all parameters are set new time i...

Page 4: ...trol loop 1 dry contact Battery connector Swith K3 Filter ON OFF default ON If panel is to be connected to earlier generation of ESC 200P set filter OFF Jumpers X317 and X318 Do not change By default...

Page 5: ...rmal status a Everything Ok b An Error code when something is wrong 2 Browse error 3 Annual test time 4 LED test time 5 Monthly test time 6 Demo mode 7 Start monthly test 8 Start annual test 9 Annual...

Page 6: ...rs that have been detected in the past The errors will be shown chronologically so that the latest error will be the first to show up on the display You can browse the errors by pushing UP or DOWN The...

Page 7: ...lly these communication errors are stopped The center checks if there is some communication errors with appliance IDs 16 Browse appliances Here you can check all the appliances connected to the center...

Page 8: ...the center finds all the appliances connected to the system Center ask before new installation delete memory you can choose no or yes If you choose yes centter will delete luminaire addresses what is...

Page 9: ...Hermiankatu 6 8 33720 Tampere 358 10 773 5400 info exilight com MANUAL Picture 1 Picture 2...

Page 10: ...ome back to the display within few minutes You can set off the Error Code by pushing the RIGHT button two 2 times inthe display shown in pictures 4 and 5 demonstrated in pictures 6 and 7 If the Error...

Page 11: ...Hermiankatu 6 8 33720 Tampere 358 10 773 5400 info exilight com MANUAL Picture 5 You can see what the Error Code actually means by pushing LEFT button Picture 6 Set off the Error Code by pushing RIGHT...

Page 12: ...ling the Emergency lights is operated with NC contact If there is no remote controlling the lights there is a loop in the terminals as shown in Picture 8 If there is a blackout or the remote control i...

Page 13: ...ations to the panel With import button you can bring file which include the addresses The file must be written in the following way every lane has Loop information address information location informa...

Page 14: ...Hermiankatu 6 8 33720 Tampere 358 10 773 5400 info exilight com MANUAL Picture 9 Luminaire location setting PC software...

Page 15: ...reduce failures coming from other networks o There are no external signs about the Center checking the operating status How long does it take to Error Code to show up on Centers display depends on ho...

Page 16: ...of 100 luminaires per line Place the luminaires to lines with as even spacing as possible If long spans are needed prepare own line for it and do not include any other luminaires on the way Cable cri...

Page 17: ...Hermiankatu 6 8 33720 Tampere 358 10 773 5400 info exilight com MANUAL Example cabling TVK is same as Control Panel ESC 200P Cabling FRHF AV is same as AMU...

Page 18: ...y person with professional and knowledgeable person Constant maintenance is needed in order to ensure the proper function of the system Warranty Warranty terms under the supplier s standard terms In c...

Page 19: ...ot to be noted in central battery use E01 Table 2 Central panel errors ERROR REMARK ERROR CODE Communication error Error in the communication between luminaire and panel E14 Blackout Not an actual err...

Page 20: ...Hermiankatu 6 8 33720 Tampere 358 10 773 5400 info exilight com MANUAL This page is intentionally left blank...

Page 21: ...EXILIGHT OY Tampere Hermiankatu 6 8 A FI 33720 Tampere Finland 358 10 773 5400 Espoo Tekniikantie 12 FI 02150 Espoo Finland 358 10 773 5404 www exilight com info exilight com...

Reviews: