Pos.
Part
Function
1
Outdoor air filter
Filters outdoor air
2
Bypass damper
For operation with heat recovery, the bypass damper is closed
so that the air passes through the crossflow heat exchanger.
For bypass operation, the damper is open, and the air bypass-
es the heat exchanger.
3
Condensation tray
Collects the condensate and drains it away from the crossflow
heat exchanger to the condensation outlet.
4
Condensation outlet
Channels condensate to the drain.
5
Extract air filter
Filters extract air
6
Spigot 1,1,B
Extract air spigot
7
Crossflow heat exchanger
Conducts heat from extract air to supply air
8
Electric heating coil
Heats supply air if heat recovery is insufficient.
9
Spigot 2,2,B
Supply air spigot The spigot can also be positioned on the top
of the unit (2,2,A).
10
Supply air fan
For outdoor air/supply air
11
Extract air fan
For exhaust/extract air.
12
Spigot 1,2,B
Extract air spigot The spigot can also be positioned on the top
of the unit (1,2,A).
13
Closing damper LS
Closing damper, exhaust air, LSA (accessory)
14
MPT1 (AFC)
Airflow control (accessory).
15
Isolation switch
Connects/disconnects current.
16
Connection box
Connection of accessories.
17
Terminal row
Connection of accessories to ventilation unit.
18
Bypass motor
Opens/closes bypass damper.
19
Sliding plate
Positioning of motor control components.
20
HMI panel
Control panel.
21
EXact2 control
Control system.
22
MPT3 (DEP)
Ice detection (accessory).
23
MPT2 (MPTF)
Filter monitor (accessory).
24
Closing damper LS
Closing damper, outdoor air, LSF (accessory)
25
Spigot 2,1,B
Outdoor air spigot The spigot can also be positioned at the bot-
tom of the unit (2,1,A)
1.4.2 Parts of the VEX unit
Cabinet
The inside and outside of the cabinet are made of Aluzinc® The cabinet has been
insulated with 50 mm mineral wool.
Fans
The unit contains two centrifugal fans with backward curved blades for extract air
and supply air.
Crossflow heat ex-
changer
The crossflow heat exchanger in the unit is mounted with a modulating bypass
damper. The crossflow heat exchanger can be removed for cleaning.
Filters
The unit includes integral panel filters for both extract air and supply air.
3004504-2019-08-29
Product information
11/32