NB
Max. and Min. may never be set closer to each other than 1K.
If
the following will be adjusted....
Supply air temp. maximum is
set lower than the room
temp. maximum.
The room temp. maximum is automatically re-
duced to the same value as the supply air temp.
maximum.
The supply air temp. mini-
mum is set higher than the
room temp. minimum.
The room temp. minimum is automatically in-
creased to the same value as the supply air
temp. minimum.
Menu 3.1.1.1.x - Supply air regulation, absolute
Air setpoint >
Air setpoint,cool
Temp. setpoint >
Abs. / Rel. >
Cool rel. start >
Cool abs. start >
Heat rel. start >
Heat abs. start >
3.1.1.1.x xxxxxxx
60
80
21,0
Absolute
---
26,0
---
21,0
%
°c
°c
°c
Note
Temp. Setpoint can never be set closer to Heating abs. start or Cooling abs. start
than 0.5 K.
Heating abs. start and Cooling abs. start can never be set closer to each other
than 1 K.
If
the following will be adjusted....
Maximum supply air temp. is set to a
value lower than Cooling abs. start
Cooling abs. start will automatically reduce
to the same value as Maximum supply air
temp.
Cooling abs. start is set to a value
lower than (Temp. se 0.5 K)
Temp. setpoint will automatically reduce to
(Cooling abs. start - 0.5 K).
Minimum supply air temp. is set to a
value higher than Heating abs. start
Heating abs. start will automatically rise to
the same value as Minimum supply air
temp.
Heating abs. start is set to a value
higher than (Temp. setpoint - 0.5 K)
Temp. setpoint will automatically rise to
(Heating abs. start + 0.5 K).
3005167-2022-02-02
Starting up the unit for operation
30/108