Supply air tempera-
ture limits
Setting
Go to menu
NB
Lowest permitted supply air tempera-
ture
3.1.8
Range: 10.0
℃
...
25.0°C
Highest permitted supply air tempera-
ture
Range: 30.0
℃
...
40.0°C
NB
The settings above must only be changed if special circumstances require
this. Otherwise, the factory settings can be used.
Room temperature limits
Function
Configuration of minimum and maximum room temperature limits. These are the
absolute minimum and maximum room temperature limits, i.e. all other menus
where room temperature can be changed will be limited by these settings.
Example
If a user selects maximum temperature in the user menu, the temperature will
never exceed the value set in this menu.
Room temperature
limits
Setting
Go to
menu
NB
Lowest permitted room tempera-
ture
3.1.8
Range: 10.0
℃
...34.0°C
Highest permitted room tempera-
ture
Range: 11.0
℃
...35.0°C
ΔT (difference between supply
air and extract air temperature)
Allows for prevention of con-
densation on supply air fixtures
and down draught. Range: ΔT:
2.0K...15.0K
NB
The settings above must only be changed if special circumstances require
this. Otherwise, the factory settings can be used.
Menu 5 - Time and weekly plan
Menu 5.1 - Date and time
This menu is used to set the current date, day and time.
3006401-2022-05-04
Starting up the unit for operation
35/72