Specifications of communication & I/Os Interfaces

5.13.Digital output

Specification 

Value

Type of output 

Open drain (MOSFET) 

Max current (external source)

 

200mA @ 30 VDC 

Isolation 

3,5 kV 

Pin-out connector 

See Input/Outputs

  

This digital output is activated by an open drain MOSFET transistor driven by an optocoupler. The 
maximum current flow into this transistor has a characteristic above the value specified in the eWON, 
in order to cope with the switching power losses. The transistor used is in an open drain type with pre 
drive. This means the relay power supply has to be supplied from an external source to the pre drive 
electronics.

The diagram below shows the external wiring needed for correct operation of the digital 
output. A relay has been chosen for this sample application but any load within the 
specifications can be used instead.

WARNING

 -

Note that this is a sink only output to ground (the transistor acts like a switch to ground).

Page 22 / 36

eWON 2005CD | IG 001

Summary of Contents for 2005CD

Page 1: ...support ewon biz eWON 2005CD This installation guide describes the hardware of the eWON 2005CD and explains how to get started with it Installation Guide IG 001 Rev 1 9...

Page 2: ...tions 11 3 4 Equipment information versions 11 3 5 Mechanical Outline 12 3 6 Mounting environmental conditions 13 3 7 Preparing the installation 13 3 8 Specification for external Power Supply selectio...

Page 3: ...26 A 2 2 Ethernet WAN 27 A 3 Direct connection 28 A 4 Connection over Hub Switch Router 29 A 5 RJ 45 Connector 29 A 6 Inputs Outputs 30 A 7 Serial Port 31 A 8 MPI Port 32 A 9 PSTN ISDN Phone line conn...

Page 4: ...ll the benefits of an universally recognized standard network It also allows you to use popular software tools like Internet Explorer FTP client SNMP Manager Mail Recipient and so to reduce significan...

Page 5: ...3 3 Remote Access Server functions Remote Access Server RAS and TCP IP Server PAP CHAP Authentication Login password Remote network access User access control Security NAT IP filtering Conventional a...

Page 6: ...wer Supply 2 Low voltage 12 24DC z Serial Port type 0 RS232 RS422 RS485 6 MPI m Modem 1 No modem Ethernet only 3 ISDN EU modem 4 PSTN 56k modem 7 GPRS EDGE Quad band A HSUPA Tri band modem B UMTS Glob...

Page 7: ...ype 2 Reference Guides Software Exhaustive reference guides to use all advanced functions of the eWON General Reference Guide RG 001 Programming Guide RG 002 Web reference guide RG 003 3 Application U...

Page 8: ...3 Housing markings 3 Housing markings 3 1 Housing interfaces For HSUPA modem with part number EW2620A only the SIM card drawer is located on eWON top side See Embedded HSUPA modem Page 8 36 eWON 2005C...

Page 9: ...rial Number SN is an important traceability tool both for the user and for the manufacturer Therefore next to the product label each eWON has its serial number stored in the flash memory This SN is al...

Page 10: ...3 EU Applies to eWONs with embedded wireless modem 3 3 3 Applicable Safety Standards The eWON2005CD range including optional modems is in conformity with the following safety standards IEC EN 60950 1...

Page 11: ...ollocated or operating in conjunction with any other transmitter or antenna To comply with regulations limiting both maximum RF output power and human exposure to RF radiation the maximum antenna gain...

Page 12: ...lace insert the upper slider into the upper part of the rail with the eWON tiled around 20 Then push and rotate the eWON downward to put the unit right The eWON2005CD is now safely fastened For HSUPA...

Page 13: ...s only if the following environmental conditions are respected Environment Conditions Ambient temperature range 20 C to 70 C for eWON with GPRS EDGE HSUPA modem 0 C to 50 C for eWON with PSTN or ISDN...

Page 14: ...ter Common mode filter1 Power absorbed 10 Watts Input Protection Protected against polarity inversion Equipment Supplied by Class 2 or Level 3 Power Supply 3 8 1 Auto fuse An auto fuse placed just aft...

Page 15: ...Chapter 4 Front panel control LED s 4 Front panel control LED s Front panel LED s description Page 15 36 eWON 2005CD IG 001...

Page 16: ...in out RJ45 connector See RJ45 connector Please refer to the appendix Direct connection and Connection over Hub Switch Router for information on the different Ethernet connection modes straight and cr...

Page 17: ...5 5 Embedded GPRS EDGE Quad band Modem optional Specification GPRS QB Bands Quad band EGSM 850 900 1800 1900 MHz Class GPRS Class 10 Max baud rate 40 kbps theoretical Compliant to standards R TTE CE F...

Page 18: ...1900 2100 MHz Class GPRS Multi slot Class 12 EDGE Multi slot class 12 Max baud rate 921 kbps theoretical Compliant to standards R TTE CE FCC Certificate number Antenna connector Type SMA F Tightening...

Page 19: ...installation Sim card installation is common to GPRS EDGE Modem GPRS quad band Modem UMTS Modem UMTS HSUPA Modem with part number EW2620B For HSUPA modem with part number EW26206B only the SIM card d...

Page 20: ...1 is the right one Position Mode RS232 RS422 RS485 WITHOUT polarization and termination resistor RS422 RS485 WITH polarization and termination resistor Note The 3 switch configurations shown here abov...

Page 21: ...alue Input voltage range 0 to 24 VDC Input voltage absolute max varistor protection 33 VDC Zero state max input voltage OFF 5 VDC One state voltage range ON 10 to 30 VDC One state currents ON 3 8mA 12...

Page 22: ...bove the value specified in the eWON in order to cope with the switching power losses The transistor used is in an open drain type with pre drive This means the relay power supply has to be supplied f...

Page 23: ...heir serial number The utility allows also to edit the IP parameters IP parameters always have to be defined in full agreement with network policies applicable within your organization ask your networ...

Page 24: ...nication parameters 6 1 2 Factory Reset This second level reset is used only exceptionally because it formats all non volatile memories and make the eWON returning to its factory defaults This operati...

Page 25: ...it unstable In such a case you have to redo the full reset procedure from scratch and wait until it is totally completed When performing a full reset the eWON does NOT restart in normal mode by itself...

Page 26: ...Positive A 2 Ethernet By default only the LAN Ethernet interface of the eWON2005CDTM can be used to access the internal Web Site A 2 1 Ethernet LAN The Ethernet LAN is a four ports auto sense Etherne...

Page 27: ...oth ends The type of cable straight or crossed depends on the equipment the eWON will be connected to The most current cases are the direct connection with a PC crossed and the connection through a hu...

Page 28: ...use a crossover Ethernet cable to make a direct WAN connection When cabling over long distance you have to take care of the twisted pairs This means that along with the above cabling conventions the...

Page 29: ...evice with a straight cable Again the wiring is as shown on the following picture and care should be taken to keep the RX and TX signals on twisted pairs A 5 RJ 45 Connector The RJ45 connector has got...

Page 30: ...osition REF Description 1 DO GND Output digital signal 0V ground connected to the emitter of the transistor 2 DO Output digital signal connected to the drain of the MOSFET transistor 3 DO VDC Common o...

Page 31: ...ial Port Mating female connector not included Type Female DB9 with 4 40 blocking screws Pin out Serial port according to mode PIN RS232 RS485 RS422 1 2 RXD RX 3 TXD A TX 4 5 GND GND GND 6 7 RTS RX 8 C...

Page 32: ...ix A Pin outs connections A 8 MPI Port Mating male connector not included Type Male DB9 with 4 40 blocking screws MPI port pin out DB9 female PIN MPI 1 2 3 B 4 5 GND 6 7 8 A 9 Page 32 36 eWON 2005CD I...

Page 33: ...ed Type RJ11 type 6P2C without shield PIN out PSTN PIN out ISDN PIN Description PIN Description 1 1 2 2 TX 3 TIP 3 RX 4 RING 4 RX 5 5 TX 6 6 The ISDN modem in the appliance shall be connected to the t...

Page 34: ...850 900 1800 1900 MHz Impedance 50 Ohms Devices conformity has been assessed with the reference antenna Kinsun 6602G01081 eWON reference for the antenna is EW40923 or EW40922 for the antenna with a 2...

Page 35: ...dem the conformity assessment has been performed with the reference antenna Taoglas TG 09 0113 eWON reference for the antenna is FAC90501_0000 or FAC90501_0100 for the antenna with a 2 meters length e...

Page 36: ...or implicit is made concerning the quality the accuracy and the correctness of the information contained in this document In no case the manufacturer s responsibility could be called for direct indire...

Reviews: