Design and function
Basic configuration using plug-in jumpers
12
099-000769-EW501
29.06.2015
5.2
Basic configuration using plug-in jumpers
The RINT X12 has a series of jumpers to configure various basic settings that cannot be changed during
operation.
These settings must be made before switching on the power source!
5.2.1
Select the welding-system
The welding system to be used must be selected by means of jumper 16. Operation is not possible if the
pre-set value is incorrect. The states of all the relays will change constantly and simultaneously to
indicate this once the system starts. In this case, the system must be switched off and the jumper setting
corrected.
JP 16 Input logic
X
Phoenix / alpha Q welding system
expected
-
Tetrix / forceTig welding system expected
5.2.2
Selecting the input logic
Jumpers 4 and 5 are used to modify the physical logic of the input signals to the automation control. The
RINT X12 supports both a positive and a negative actuation logic. With the positive logic, switching on
actuates active signals at +24 V. With the negative logic, an active signal is taken to earth and a positive
input level (above pull-up) is interpreted as a "low" signal.
JP 4
JP 5
Input logic
1-2
1-2
Positive input logic (factory setting)
2-3
2-3
Negative input logic
Combinations not given in the table will have undesirable consequences!