5.4
System shut down
Caution!
Risk of uncontrolled dosing of chlorine or pH-correction
medium! Shut down dosing system, close positioner!
If the installation site of the flow block assembly is not frost-free,
the system must be shut down in due time!
1
Switch off the power supply.
2
Drain the sample water supply line and drainage line (hold
container underneath)
3
Empty cell bodies and remove cleaning sand (see Page 223).
4
Dismantle the filter housing and the check valve housing.
5
When the remaining water has drained from the flow control
valve, refit the filter housing and the check valve housing.
6
Remove the sensors from the cell body cover and disconnect
from the cable.
7
Apply a KCI solution to the protection caps of the pH and
Redox electrodes and fit onto the electrodes.
Please note
A "KCI tank to store the sensors" may be used instead of the
protection cap for pH and Redox electrodes (see 8. “Complete
Units, Retrofit Kits and Spare Parts”).
The fluoride electrodes can be stored wet in the short term in a
100 mg/l fluoride solution at pH 7. Fill the electrodes in the
tank with 100 mg/l fluoride solution and mount on the
electrodes. However, the electrodes should be kept in a dry
condition if they are to be stored for several months. In this
case, drain the fill solution from the electrode chamber and
wash the membrane and chamber with distilled water.
Picture 13 Senor components
8
Store the sensors in a frost-free place.
Please note
The water must be drained if frost occurs.
Insert electrode in a beaker with water and store in a frost-free
place.
9
Procedure for membrane sensors, see
4.2.6 “Membrane sensors”.
A
B
C
D
E
A Sensor
B Sealing cap
C O-ring
D Tank
E Stand
Summary of Contents for WALLACE & TIERNAN SFC
Page 1: ...WALLACE TIERNAN MEASURING AND CONTROL SYSTEM SFC from version V 3 08 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 590 000 DE IM 0719 SFC Please note Original instruction manual...
Page 40: ...40 WT 050 590 000 DE IM 0719 Description SFC 3...
Page 118: ...118 WT 050 590 000 DE IM 0719 Functions SFC 4...
Page 121: ...SFC Installation 5 121 Top hat rail assembly...
Page 122: ...122 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 123: ...SFC Installation 5 123 Top hat rail assembly...
Page 124: ...124 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 125: ...SFC Installation 5 125 Control cabinet installation assembly...
Page 126: ...126 WT 050 590 000 DE IM 0719 Installation SFC 5 Control cabinet installation assembly...
Page 127: ...SFC Installation 5 127 Installation of the front panel on the control cabinet...
Page 156: ...156 WT 050 590 000 DE IM 0719 Installation SFC 5...
Page 218: ...218 WT 050 590 000 DE IM 0719 Operation SFC 6...
Page 232: ...232 WT 050 590 000 DE IM 0719 Maintenance SFC 7...
Page 266: ...266 WT 050 590 000 DE IM 0719 Complete Units Retrofit Kits and Spare Parts SFC 8...
Page 274: ...274 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 275: ...SFC Declarations and certificates 10 275 10 2 Certificate of Compliance...
Page 276: ...276 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 284: ...284 WT 050 590 000 DE IM 0719 Settings Table SFC 11...