154
WT.050.590.000.DE.IM.0719
Installation
SFC
5.
5.3.12
Positioner calibration with SFC (application 3) or
single feed forward (application 2)
In these applications the linearization of the control output is
possible, such as for example with a gas feeder which has
positioner feedback. Here, for example, 30 % control (opening)
does not equal 30 % dosing capacity. Calibration of the positioner
feedback allows up to eleven dosing capacity points to be aligned,
in order to obtain dosing that is as linear as possible.
For this purpose, the number of support points to be calibrated can
be selected in the menu „Control“ => „Actuator“ => „Ym
Calib.Points“. It is possible to calibrate 2, 3, 6 or 11 support points.
The more support points are selected, the more accurate is the
dosing.
• Starting from the basic display, select the „Control“ =>
„Actuator“ menu.
• In the „Ym Calib.Points“ menu, select the number of
calibration support points.
• Select the „Ym Calibration.Man“ menu and confirm with the
Enter key.
• The dosing outputs to be calibrated are shown on the display
(max. 11).
• The calibration points can be selected using the up/down
arrow keys. Press Enter to calibrate the support points, and
use the up/down arrow keys to open/close the positioner until
the actual dosing shown on the dosing capacity indicator (e.g.
gas feed inspection glass) agrees with the calibration point
(e.g. 20%). Save the value by pressing the Enter key.
• Select the next calibration point and align the actuator position
as described.
Please note
All calibration points must be aligned or checked in order to obtain
linear dosing output.
000%
0.0
(calibration point 0 % dosing)
020%
20.0
(calibration point 20 % dosing)
040%
40.0
(calibration point 40 % dosing)
060%
60.0
(calibration point 60 % dosing)
080%
80.0
(calibration point 80 % dosing)
100%
100.0
(calibration point 100 % dosing)
Summary of Contents for WALLACE & TIERNAN SFC
Page 1: ...WALLACE TIERNAN MEASURING AND CONTROL SYSTEM SFC from version V 3 08 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 590 000 DE IM 0719 SFC Please note Original instruction manual...
Page 40: ...40 WT 050 590 000 DE IM 0719 Description SFC 3...
Page 118: ...118 WT 050 590 000 DE IM 0719 Functions SFC 4...
Page 121: ...SFC Installation 5 121 Top hat rail assembly...
Page 122: ...122 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 123: ...SFC Installation 5 123 Top hat rail assembly...
Page 124: ...124 WT 050 590 000 DE IM 0719 Installation SFC 5 Wall mounting assembly...
Page 125: ...SFC Installation 5 125 Control cabinet installation assembly...
Page 126: ...126 WT 050 590 000 DE IM 0719 Installation SFC 5 Control cabinet installation assembly...
Page 127: ...SFC Installation 5 127 Installation of the front panel on the control cabinet...
Page 156: ...156 WT 050 590 000 DE IM 0719 Installation SFC 5...
Page 218: ...218 WT 050 590 000 DE IM 0719 Operation SFC 6...
Page 232: ...232 WT 050 590 000 DE IM 0719 Maintenance SFC 7...
Page 266: ...266 WT 050 590 000 DE IM 0719 Complete Units Retrofit Kits and Spare Parts SFC 8...
Page 274: ...274 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 275: ...SFC Declarations and certificates 10 275 10 2 Certificate of Compliance...
Page 276: ...276 WT 050 590 000 DE IM 0719 Declarations and certificates SFC 10...
Page 284: ...284 WT 050 590 000 DE IM 0719 Settings Table SFC 11...