70
WT.090.370.000.DE.IM.0715
Operation
Barrier M
5.
5.9
Flow rate monitoring
If the flow rate monitoring function is activated, the following dis-
plays appear in the operator menu
If values are below or above of the maximum and minimum limit
values set at the factory (see setting data, page 2 of the operating
manual), the red LED for the "FLOW RATE" alarm lights up (see
5.12 Errors). At the same time, the „pump on“ signal contact closes
and the lamps are switched off (time delay option) and a voltage-
free contact is activated. The green LED "UV
" disappears.
5.10
Temperature monitoring
Please note
Please bear in mind that the value shown on the display for the wa-
ter temperature can be influenced by lamp heat and cable re-
sistance!
Please note
Risk of damage to the UV disinfection unit!
The water temperature must not exceed 45° C! Temperatures in
excess of 60° C will damage the unit!
Warning!
Risk of burns!
Hot surface of treatment disinfection chamber (UV reactor)! The
alarm value for the maximum water temperature is programmed at
the factory to 45° C. Higher temperatures causes burns when con-
tacting the treatement disinfection chamber. To avoid this, for tem-
peratures in excess of 45° C safety measures must be taken by the
client (e. g. fix a safety guard)!
Display
Q meas.:
xxxm³/h (flow rate value)
Summary of Contents for WALLACE & TIERNAN Barrier M 1200
Page 1: ...WALLACE TIERNAN UV DISINFECTION UNIT BARRIER M OPERATING MANUAL...
Page 2: ...2 WT 090 370 000 DE IM 0715 Barrier M Please note Original manual...
Page 96: ...96 WT 090 370 000 DE IM 0715 Spare parts maintenance schedule Barrier M 6...
Page 100: ...100 WT 090 370 000 DE IM 0715 Table of UV alarm levels Barrier M 7...
Page 102: ...102 WT 090 370 000 DE IM 0715 Certificates declarations and statements Barrier M 8...
Page 103: ...Barrier M Certificates declarations and statements 8 103 8 2 QPS certificate...
Page 104: ...104 WT 090 370 000 DE IM 0715 Certificates declarations and statements Barrier M 8...
Page 105: ...Barrier M Certificates declarations and statements 8 105 8 3 NSF certficate...
Page 106: ...106 WT 090 370 000 DE IM 0715 Certificates declarations and statements Barrier M 8...
Page 109: ...Barrier M 109...