Page 4 | 26
Rev: 01/18/2021
SPECIFICATIONS
Filter Media
Perlite
Media Regeneration Method
PowerBump™
Filtration Area
212 ft
2
(19.7 m
2
)
Minimum Flow Rate
107 gpm (24 m
3
/hr)
Maximum Flow Rate
300 gpm (68 m
3
/hr)
Maximum Allowable Water Pressure
50 psi (3.45 Bar)
Required Air Pressure
90-110 psi (6.2
– 7.6 Bar)
Maximum Water Temperature
104°F (40°C)
Maximum Ambient Temperature
110°F (43°C)
Minimum Ambient Temperature
0°F (-17°C) (Above 36°F when full of water)
Controller Power
110/230 VAC 15/10A 50-60Hz
Drain Line
100 gpm (23 m
3
/hr) Surge Flow (atmospheric)
Installation Location
Indoor/Outdoor
SAFETY
The Defender FP-Series RMF is a system designed to run 24/7 with limited supervision. Ensure that all precautions are
taken to maintain the safety of operators or service technicians and restrict access to unauthorized personel.
Inhalation hazard may be present when loadng Perlite media. Minimize dust exposure through
proper handling and wear respiratory PPE if necessary.
The potential of skin burn injury exists when handling or servicing the pnuematic actuators and
pump when on or shortly after stopping the system. Use caution around the system and avoid
the heated areas during operation. Use personal protective equipment to prevent burns if
necessary.
A potential hearing hazard exists when pumps and compressors are in operation. Repair
malfunctioning equipment immediately and install sound absorbing protective measures if
necessary.
Potential electrical hazards exist when servicing the local control panel and pumps. Always
isolate electrical power supplies before servicing powered equipment and devices. After isolating,
ensure power has dissipated from circuit components before accessing panels and equipment.
Exercise caution around pools of water that may have become electrified.
Potential slip hazards exist over the lifetime of operating equipment. Wear slip resistant shoes
and repair leaking connections or piping immediately.
A potential moving parts hazard exists when servicing or inspecting centrifugal pumps or
actuated valves. Turn off control to pumps and valves before servicing. Do not operate without
guards in place.