Wiring

Heat Pump HVAC System Wiring

• 

Check your system information to be sure and note the color of original thermostat wire and the terminal it was 

connected to.  No matter what the old stat connection was (O or B), connect the wire to the thermostats W2/O 

terminal.  The setting of the C/O Type will set the correct system operation.  For change over with cool systems 

(Orange wire, O terminal): set C/O type to w/cool (most common and default setting).  For change over with heat 

systems (Brown wire, B terminal): set C/O type to w/heat.

• 

2nd Stage Heat 

- Enable second stage heating outputs.  If you have a single stage heating system, leave this set to 

N

.  If you have a 2 stage heating system, set to 

Y

 to enable.

• 

Aux Heat (HP)

 - If you have auxiliary heat strips, set this to 

Y

 to enable.

• 

2nd Stage Cool 

- Enable second stage cooling outputs.  If you have a single stage cooling system, leave this set to 

N

.  If you have a two stage cooling system, set to 

Y

 to enable.

Thermostat Back

Heat Pump HVAC System 

Thermostat Connection

 

G   Fan  

W1 Aux Heat 

Y1 Compressor Stage 1 

R   24VAC  Return 

C   24VAC Common 

Y2 Compressor Stage 2 

O    Change Over Valve 

For Heat Pump systems, connect the 24R connection 

to either the 24RC or 24RH 

Y1 

 G

 

Y2 

RS2

 

RS2

 

RSC

 

HC

 

24RC 

W1 

24RH

 

W2/O 

RS1 

RS1

 

RSC

 

H1

 

24C 

Cooling 24V 

Fan 

Cooling stage 1 

Cooling stage 2 

Remote Sensor 2 

Remote Sensor 2 

Sensor shield 

Humidity Relay Com  

24VAC Com 

24V Heating 

Aux Heating 

Change Over Valve 

Remote Sensor 1 

Remote Sensor 1 

Sensor shield 

Humidity Relay  

Remote Outside Sensor 

Remote Indoor Sensor  

Shielded cable 

Shielded cable 

Humidifier/Dehumidifier 

Contact 
Closure 

Input 

Note!

If you get heating when you 
expected cooling, change the C/O 
type to the opposite setting.

Setup

To set the HVAC system type, go to the 

Thermostat Info screen and press 

Setup

 

button.

• 

Type

 - Set the HVAC System Type: set to 

Heat Pump

• 

Fan Type

 - Automatically set for heat 

pump systems.  Ignore this setting.

• 

C/O type

 -  Change Over (reversing) Valve 

Type.  Heat pumps change from heating to 

cooling by reversing operation.You must 

configure the thermostat’s changeover 

valve setting to work correctly with your 

HVAC system.

Summary of Contents for T-100-R

Page 1: ...T 100 R Installation Guide ...

Page 2: ...ents T 100 R Z Wave Thermostat 3 4 HVAC System Setup 6 Installer Settings Menu Items 7 9 Installer Settings Summary 10 11 Overview Installation Standard Gas Elec HVAC System Wiring 13 Heat Pump HVAC System Wiring 14 Wiring ...

Page 3: ...ting systems 1 stage heating and cooling 2 stage heating and cooling Heat Pump systems 1 stage heating and cooling 2 stage heating and cooling 2nd or 3rd stage Auxilary heating heat strips Do NOT use for line voltage controls 120 240VAC STOP Before removing your existing thermostat be sure to label the wires with the terminal markings on the old thermostat and record them below Overview ...

Page 4: ...have a terminal marked B with a brown wire attached to it that means you have a changeover C O with heating type heat pump system Be sure to set the change over type in the Installer Settings menu to C O Type w Heat Otherwise leave it set to w Cool Standard HVAC System Wiring Terminal Marking Meaning Typical Wire Color Record the old thermostat wire connections and terminal marking here C 24VAC Co...

Page 5: ...installation ...

Page 6: ...will need to know the following information to correctly configure the thermostat The HVAC setup is in the Mechanical Settings menu screen HVAC system type What type HVAC system do you have Standard or Heat pump For Standard systems Fan Type Do you have Gas heat or Electric heat For Heat Pump systems Change over valve or reversing valve type Does your system change over with cooling operation or w...

Page 7: ...ing N Test mode off Normal system delays CAUTION in test mode all system safety delays are shorten Do not operate the system compressor in test mode Disconnect Y1 or Y2 outputs if using test mode on a live system Range Y or N Default N System Settings Submenu Sets the HVAC operational settings below Mechanical Settings Submenu Sets the HVAC system type and configuration Type Range Gas Elec or Heat...

Page 8: ...etpoints Attempts to lower the cooling below the heating setpoint by this amount will PUSH the heating setpoint down to maintain this separation Same for setting the heating setpoint above the cooling setpoint it will PUSH the cooling setpoint up to maintain this separation Heating Delta Stage 1 ON Range 1 8 degrees Default 1 Sets the delta from setpoint that stage 1 heating starts Heating Delta S...

Page 9: ...alue Will not ramp or accept setpoints lower than this minimum Range 44F to 113F 6C 45C Default 60F 15C Minimum Run Time MRT Sets the minimum run time before a heating cooling cycle can turn off Sets heating cooling cycle time Prevents rapid cycling Range 1 9 minutes Default 3 Minimum Off Time MOT Sets the minimum off time before another heating cooling cycle can begin Provides compressor short cy...

Page 10: ...pe w Heat or w Cool w Cool 2nd Stage Heat Y or N N Aux Heat Y or N Y 2nd Stage Cool Y or N N H C Delta 3 15 deg 3 Heat Delta Stage 1 On 1 8 1 Heat Delta Stage 1 Off 0 8 0 Heat Delta Stage 2 On 1 8 2 Heat Delta Stage 2 Off 0 8 0 Heat Delta Stage 3 On 1 8 3 Heat Delta Stage 3 Off 0 8 0 Cool Delta Stage 1 On 1 8 1 Cool Delta Stage 1 Off 0 8 0 Cool Delta Stage 2 On 1 8 2 Cool Delta Stage 2 Off 0 8 0 M...

Page 11: ...enu Maint Interval Disabled 100 4000 hrs 3000 Screen Timeout to minimized screen 0 20 120 sec 0 0 off will not timeout F C Mode F or C F Sensor Calibration Submenu Internal 7 to 7 0 Backlite Display Submenu Backlight Timeout 0 20 120 0 0 backlite off Backlight On Brightness 0 100 100 Backlight Off Brightness 0 100 0 Contrast 0 20 14 ...

Page 12: ...wiring ...

Page 13: ...is set to N If you have a two stage cooling system set to Y to enable Setup Standard HVAC System G Fan W1 Heat Stage 1 Y1 Compressor Stage 1 R 24VAC Return C 24VAC Common Thermostat Connection Y2 Compressor Stage 2 W2 Heat Stage 2 Optional 24R Connection for single transformer HVAC Systems RC and RH are jumpered together on thermostat board Cut RC RH jumper JP1 for separate heating cooling transfo...

Page 14: ...Back Heat Pump HVAC System Thermostat Connection G Fan W1 Aux Heat Y1 Compressor Stage 1 R 24VAC Return C 24VAC Common Y2 Compressor Stage 2 O Change Over Valve For Heat Pump systems connect the 24R connection to either the 24RC or 24RH Y1 G Y2 RS2 RS2 RSC HC 24RC W1 24RH W2 O RS1 RS1 RSC H1 24C Cooling 24V Fan Cooling stage 1 Cooling stage 2 Remote Sensor 2 Remote Sensor 2 Sensor shield Humidity ...

Page 15: ...CORPORATE 16 South Maryland Ave Port Washington NY 11050 855 750 9090 info eguestcontrols com ...

Page 16: ...www evolvecontrols com ...

Reviews: