7. Troubleshooting
7.1 Parameters Explained
No.
Meaning
Range
Default
value
Details
Hardware parameters
/01
The usage of the O05 port
0/2
0
0-Low speed / 2-Solar
water pump
/02
High temperature disinfection target temperature
0/2/3
0
0-No output / 2-Solar
water pump / 3- Solar drain
valve
Defrost parameters
D01
Heating enter defrosting coil temp value
-30~0
-3
D02
Heating exit defrosting coil temp value
0~30
13
D03
Heating defrost cycle
30~90min
45min
D04
Heating the maximum defrosting time
1~20min
8min
D05
Heating the minimum defrosting time
0~D04
3min
D06
Heating the minimum defrosting time
0~2
0
0-Standard / 1-Economic /
2-Intelligent
D07
Intelligent defrost temperature conversion point
-10~20
4
High temperature disinfection parameters
G01
High temperature disinfection target temp
30~70
60
G02
High temperature disinfection running time
0~90min
0min
When G02= 0, no high
temperature disinfection
function
G03
High temperature disinfection startup time
0~23H
0h
G04
High temperature disinfection cycle
7~99Days
7
EEV parameters
E01
EEV adjustment mode
0/1
1
0- Manual / 1- Auto
E02
EEV target overheat temp
- 20~20
5
E03
EEV initial steps
0~500
240
E04
EEV minimum steps
0~500
80
E05
Defrosting EEV steps
0~500
480
System parameters
H01
Whether enable the power down memory
function
0/1
1
0-No / 1-Yes
H03
Heat source mode
0
0
H07
Fahrenheit / Celsius
0/1
0
0-Celsius / 1-Fahrenheit
H30
Unit address
4(1~255)
0
H31
Remote control mode
0/1
0
0-Centralized control / 1-
DTU&WIFI
H32
Status parameter feedback to cloud cycle
1~255min
0
H98
Type of unit parameter
2/3
0
2-0*08 / 3-0*18
H99
Main display temp showing adjustment
0/1
0
0-No / 1-Yes
Solar water pump parameters
N01
Which temp sensor used for controlling the solar
water pump
0/1
0
0-Water tank bottom temp
sensor 1-Water tank top
temp sensor
N02
The maximum running time of the solar water
pump
1~30min
15min
N03
The solar water pump startup return difference
0~20
5
N04
Whether enable the night cooling mode
0/1
0
0-No / 1-Yes
N05
Cooling function startup time
0~23h
0h
N06
Cooling function shutdown time
0~23h
6h
N07
Night cooling startup temp
40~90
70
N08
Night cooling shutdown temp
1~40
10
N09
Solar drain valve temp setting value
50~90
68
N10
Solar water pump shutdown temp setting value
50~90
N11
Whether enable the independent solar control
function
0 / 1
0
0-Disable / 1-Enable