7. Troubleshooting 

7.1 Parameters Explained 

No. 

Meaning 

Range 

Default 

value 

Details 

Hardware parameters 

/01 

The usage of the O05 port 

0/2 

0-Low speed / 2-Solar 

water pump 

/02 

High temperature disinfection target temperature 

0/2/3 

0-No  output / 2-Solar 

water pump / 3- Solar drain 

valve 

Defrost parameters 

D01 

Heating enter defrosting coil temp value 

-30~0 

-3 

 

D02 

Heating exit defrosting coil temp value 

0~30 

13 

 

D03 

Heating defrost cycle 

30~90min 

45min 

 

D04 

Heating the maximum defrosting time 

1~20min 

8min 

 

D05 

Heating the minimum defrosting time 

0~D04 

3min 

 

D06 

Heating the minimum defrosting time 

0~2 

0-Standard / 1-Economic / 

2-Intelligent 

D07 

Intelligent defrost temperature conversion point 

-10~20 

 

High temperature disinfection parameters 

G01 

High temperature disinfection target temp 

30~70 

60 

 

G02 

High temperature disinfection running time 

0~90min 

0min 

When G02= 0, no high 

temperature disinfection 

function 

G03 

High temperature disinfection startup time 

0~23H 

0h 

 

G04 

High temperature disinfection cycle 

7~99Days 

 

EEV parameters 

E01 

EEV adjustment mode 

0/1 

0- Manual / 1- Auto 

E02 

EEV target overheat temp 

- 20~20 

 

E03 

EEV initial steps 

0~500 

240 

 

E04 

EEV minimum steps 

0~500 

80 

 

E05 

Defrosting EEV steps 

0~500 

480 

 

System parameters 

H01 

Whether enable the power down memory 

function 

0/1 

0-No / 1-Yes 

H03 

Heat source mode 

 

H07 

Fahrenheit / Celsius 

0/1 

0-Celsius / 1-Fahrenheit 

H30 

Unit address 

4(1~255) 

 

H31 

Remote control mode 

0/1 

0-Centralized control / 1-

DTU&WIFI 

H32 

Status parameter feedback to cloud cycle 

1~255min 

 

H98 

Type of unit parameter 

2/3 

2-0*08 / 3-0*18 

H99 

Main display temp showing adjustment 

0/1 

0-No / 1-Yes 

Solar water pump parameters 

N01 

Which temp sensor used for controlling the solar 

water pump 

0/1 

0-Water tank bottom temp 

sensor 1-Water tank top 

temp sensor 

N02 

The maximum running time of the solar water 

pump 

1~30min 

15min 

 

N03 

The solar water pump startup return difference 

0~20 

 

N04 

Whether enable the night cooling mode 

0/1 

0-No / 1-Yes 

N05 

Cooling function startup time 

0~23h 

0h 

 

N06 

Cooling function shutdown time 

0~23h 

6h 

 

N07 

Night cooling startup temp 

40~90 

70 

 

N08 

Night cooling shutdown temp 

1~40 

10 

 

N09 

Solar drain valve temp setting value 

50~90 

68 

 

N10 

Solar water pump shutdown temp setting value 

50~90 

 

 

N11 

Whether enable the independent solar control 

function 

0 / 1 

0-Disable / 1-Enable 

Summary of Contents for Evo315-C

Page 1: ......

Page 2: ...ller 7 6 2 Operating Functions 8 6 2 1 Startup Shutdown 8 6 2 2 Switching Modes 8 6 2 3 Locking the Controller 8 6 2 4 Setting Checking the Target Temperature 9 6 2 5 Hydroboost Setting 9 6 2 6 Force...

Page 3: ...dvanced energy efficiency technologies and built in smart features to ensure you re provided with clean safe and economical hot water all year round Conforms to AS 3498 2009 Australia and New Zealand...

Page 4: ...year d Press at any stage to cancel 3 Press until is displayed This will activate Eco Heating Heat Pump only mode and will provide the most efficient heating 4 During periods of unusually high hot wa...

Page 5: ...you restart the unit or turn it on manually the unit will not start to run again for approximately 3 minutes This is a protection feature to safeguard the compressor The handle of the P T safety valv...

Page 6: ...eat resistant and durable Piping for the P T Valve The spec of the valve connecting thread is BSP3 4 internal thread After installation confirm that the drainpipe outlet is exposed in the air When the...

Page 7: ...nces to allow airflow to circulate through the unit it is advised to keep a minimum gap between walls fences etc of 1000mm on the air inlet outlet sides 300mm rear clearance 600mm overhead clearance W...

Page 8: ...water temperature and target temperature The electric heater always will be off INTELLIGENT MODE The unit will automatically judge the operation mode according to the ambient temperature HIGH REQUIRE...

Page 9: ...for 0 5 seconds in the running screen of the controller to turn the unit off The main display will now show OFF The unit will dim the screen and display the standby screen when the controller has not...

Page 10: ...5 Hydroboost Setting Also known as the Electric heater the Hydroboost setting allows higher levels of hot water to be produced When there are high hot water usage requirements such as guests staying t...

Page 11: ...ameter value as shown in the below table and press the key to open that value Change the value using the up down arrow keys and press the key to save changes Press to exit the menu Description Paramet...

Page 12: ...t up time A and end time B Press to save the setting and exit back to the main interface Press and hold for 2 seconds the timer display will flash When the timer display flashes choose the start up ti...

Page 13: ...sh when it is selected use the arrow keys to select your desired start day then press to save all changes and exit back to the main interface Note Format is mm dd Example The unit will start up on Sep...

Page 14: ...rs E01 EEV adjustment mode 0 1 1 0 Manual 1 Auto E02 EEV target overheat temp 20 20 5 E03 EEV initial steps 0 500 240 E04 EEV minimum steps 0 500 80 E05 Defrosting EEV steps 0 500 480 System parameter...

Page 15: ...sor shutdown ambient temp 1 30 90 65 R20 The compressor shutdown ambient temp 2 30 90 55 Timing parameters L01 Whether enable the vacation mode 0 1 0 0 Disable 1 Enable L02 The vacation mode Year 0 99...

Page 16: ...p setting needs to be reduced if it is too high 4 Check the high pressure switch If the switch is open when the connection is closed replace it Low pressure protection E02 1 Check if the system is lea...

Page 17: ...BRN BLU Y G 3G2 5mm L N L N N N N N N 1 3 2 4 5 6 7 8 01 N 4 WHT N 4V 1 2 3 4 MTS RESET 1 3 4 2 OUT1 OUT2 OUT3 OUT4 OUT5 AC N 3 4 3 4 CN5 OUT6 CN6 CN1 CN2 12V NET GND 485 A 485 B DI01 DI03 GND DI04 GN...

Page 18: ...80900421 KP cover 640 22 ABS Black Gloss 9005 Plastic Absorption 14 80708081 KP Top Cover Galvanized sheet 0 8 gray white matte 9006 15 80704839 Fan top cover Galvanized sheet 1 0 Black finish 9005 16...

Page 19: ...th the water heater 8 4 Using the Overheating Protector The overheating protector is used to turn the power off in an emergency or with power supply issues preventing the water from being heated too h...

Page 20: ...clean of the unit with a damp cloth MAJOR FIVE YEAR SERVICE It is recommended a major five 5 year service be conducted on the Evo315 C Warning Servicing of a water heater must only be carried out by...

Page 21: ...ed within the i Costs associated with delivery handling freighting or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 o...

Reviews: