evoheat Evo Control 17 Installation & Operation Manual Download Page 11

 

 

10 

Evo Control 17 & 25 Manual 

5.2.3 Switching Modes 

At the main interface, you can switch between the modes of cooling, economic heating, heating & rapid heating by 
pressing 

 . Example: Switch from Cooling mode to Economic Heating 

 

Note: The operation of mode is invalid if the unit you purchase is heating only or cooling only. 

5.2.4 System State Checking 

At any interface you can enter the system working state by pressing   TWICE, then using the UP and Down arrow 
keys to highlight the required parameter, then press 

 to enter. To exit, press the ON/OFF button 

 

5.2.5 Changing Temperature 

At the main interface, press the UP or DOWN key to adjust the temperature setting as desired. Once complete, press 
the 

 button to save the settings and exit. Press the ON/OFF button to exit without saving settings. Refer to the 

Parameter Table to set relevant temperature. 

 

5.2.6 Clock Setting 

At the main interface press   to enter the clock setting interface. Select the parameter you wish to change and 
press   to make the parameter begin flashing which indicates it can be changed. Press the UP or DOWN keys to 
change the parameter value, then press   to save. Press the ON/OFF button to return to the main menu. 

 

Note: If there is no operation after 10 seconds, it will return to the main menu and changes will automatically be saved.  

To change the date, the same process is followed. 

Summary of Contents for Evo Control 17

Page 1: ......

Page 2: ...HELP Button __________________________________________________________________9 5 2 2 Starting Shutting Down ________________________________________________________________9 5 2 3 Switching Modes____...

Page 3: ...with these recommendations will invalidate the warranty This manual and all others are available for download on our website The Evo Control Series air to water heat pump is designed for multiple use...

Page 4: ...3 Evo Control 17 25 Manual 2 2 Dimensions Evo Control 17 Evo Control 25...

Page 5: ...Quantity 2 Fan Power Input W 120x2 200x2 Fan Rotate Speed RPM 850 750 Noise dB A 56 59 Hot water volume L h 57 Water Pump Input kW 0 2 0 75 Water Head m 13 5 24 Water Connection Inch 1 1 5 Water Flow...

Page 6: ...off before any work is started on the unit Do not work on the electrical components if water or high humidity is present on site When the unit is being connected ensure that no impurities are introduc...

Page 7: ...6 Evo Control 17 25 Manual 4 Installation 4 1 Application for Air Con 4 2 Application for Air Con and Super Heater for Hot Water...

Page 8: ...leakage test must be carried out to ensure that there is no water leaking before the installation can be made The pipe must be tested by pressure separately DO NOT test it together with the unit There...

Page 9: ...nts and that they are in good order When powering the unit on review the indicator on the controller to see if there is any indication of failure The gas gauge can be connected to the check valve to s...

Page 10: ...clock or turn the timer on off UP Press this key to select the upwards option or increase the parameter value DOWN Press this key to select the downwards option or decrease the parameter value 5 2 Fun...

Page 11: ...re At the main interface press the UP or DOWN key to adjust the temperature setting as desired Once complete press the button to save the settings and exit Press the ON OFF button to exit without savi...

Page 12: ...ss to enter the timer setting interface The process is much the same as adjusting the Clock settings To cancel and return to the previous menu press the ON OFF button 5 2 7 1 Timer Each timer has an O...

Page 13: ...ere 8am 10am Timer 3 were 1pm 5pm the unit would operate or stop accordingly 5 2 8 Keyboard Lock To lock the controller after adjusting settings at the main interface hold the ON OFF button for 5 seco...

Page 14: ...oken Check the pressure switch and cold circuit Low pressure 2 protection E22 12 on 1 off The low pressure switch is broken Check the pressure switch and cold circuit Heat source side water flow failu...

Page 15: ...the temp sensor System 1 2 3 4 high Pressure protection E11 system1 E21 system2 E31 system3 E41 system4 The high pressure switch is broken Check the pressure switch and cold circuit System 1 2 3 4 lo...

Page 16: ...recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor does not run Power supply failure Chec...

Page 17: ...illed water Installation Requests 1 The Factory only offers main unit in the legend the other modules which are indispensable fittings are to be provided by the user or installation company 2 The unit...

Page 18: ...ndle A can return close when the system is full of water 5 Automatic filled water valve needs cleaning in a periodic time and then you must close the tap unscrew the plug D and remove the inside filte...

Page 19: ...o the electronic boiler or warm net pipe for city accordingly 1 Water chiller and heat pump assistant gas fired boiler 2 Water chiller and heat pump assistant electronic boiler 7 5 Unit Parameters Mea...

Page 20: ...e input 10 RO 08 Spray valve output 220VAC 31 AI 05 Ambient temperature input 11 RO 09 Alarm system output 220VAC 32 AI 06 System 1 antifreeze temperature input 12 DI DO 1 Mode indicator output 33 AI...

Page 21: ...put 12 RO 10 Spray valve output 220VAC 38 AI 11 System 4 antifreeze temperature input 13 RO 11 Alarm system output 220VAC 39 AI 12 System 1 suction temperature input 14 DI DO 1 Emergency switch output...

Page 22: ...23 148A 2 x 50mm2 50mm2 225A 148 186A 2 x 70mm2 70mm2 250A 186 224A 2 x 95mm2 95mm2 280A Three Phase Unit Nameplate maximum current Phase Line Earth Line MCB Creepage Protector Signal Line No more tha...

Page 23: ...it is restarted Please drain out the water in the super heater of the heat pump unit in winter when the super heater is not used The water loop of the heat pump MUST be protected from freezing in wint...

Page 24: ...or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your re...

Reviews: