EvoHeat CS-i Commercial Inverter Series Heat Pump 

6.1 Error Codes 

Electronic Control Fault Table 

Protect/fault 

Fault 

display 

Reason 

Elimination methods 

Inlet Temp. Sensor Fault 

P01 

The temp. Sensor is broken or short circuit  Check or change the temp. Sensor 

Outlet Temp. Sensor Fault 

P02 

The temp. Sensor is broken or short circuit  Check or change the temp. Sensor 

Ambient Temp. Sensor Fault 

P04 

The temp. Sensor is broken or short circuit  Check or change the temp. Sensor 

Coil 1 Temp. Sensor Fault 

P05 

The temp. Sensor is broken or short circuit  Check or change the temp. Sensor 

Coil 2 Temp. Sensor Fault 

P15 

The temp. Sensor is broken or short circuit  Check or change the temp. Sensor 

Suction Temp. Sensor Fault 

P07 

The temp. Sensor is broken or short circuit  Check or change the temp. Sensor 

Discharge Temp. Sensor Fault 

P081  The temp. Sensor is broken or short circuit  Check or change the temp. Sensor 

Exhaust Air over Temp Prot. 

P082  The compressor is overload 

Check whether the system of the 

compressor running normally 

Antifreeze Temp. Sensor Fault 

P09 

Antifreeze temp sensor is broken or short 

circuited 

check and replace this temp sensor 

Pressure sensor Fault 

PP 

The pressure Sensor is broken 

Check or change the pressure Sensor 

or pressure 

High Pressure Prot. 

E01 

The high-pressure switch is broken 

Check the pressure switch and cold 

circuit 

Low Pressure Prot. 

E02 

Low pressure1 protection 

Check the pressure switch and cold 

circuit 

Flow Switch Prot. 

E03 

No water/little water in water system 

Check the pipe water flow and water 

pump 

Waterway Anti-freezing Prot. 

E05 

Water temp. or ambient temp. is too low 

 

Inlet and outlet temp. too big 

E06 

Water flow is not enough and low 

differential pressure 

Check the pipe water flow and 

whether water system is jammed or 

not 

Anti-freezing Prot. 

E07 

Water flow is not enough 

Check the pipe water flow and 

whether water system is jammed or 

not 

Primary Anti-freezing Prot. 

E19 

The ambient temp. Is low 

 

Secondary Anti-freezing Prot. 

E29 

The ambient temp. Is low 

 

Comp. Overcurrent Prot. 

E051  The compressor is overload 

Check whether the system of the 

compressor running normally 

Communication Fault 

E08 

Communication failure between wire 

controller and mainboard 

Check the wire connection between 

remote wire controller and main 

board 

Communication Fault (speed 

control module) 

E081  Speed control module and main board 

communication fail 

Check the communication 

connection 

Low AT Protection 

TP 

Ambient temp is too low 

 

EC fan feedback Fault 

F051  There is something wrong with fan motor 

and fan motor stops running 

Check whether fan motor is broken 

or locked or not 

Fan Motor1 Fault 

F031 

1. Motor is in locked-rotor state 

2. The wire connection between DC-fan 

motor module and fan motor is in bad 

contact 

1. Change a new fan motor 

2. Check the wire connection and 

make sure they are in good contact 

 

 

Fan Motor2 Fault 

 

 

F032 

1. Motor is in locked-rotor state 

2. The wire connection between DC-fan 

motor module and fan motor is in bad 

contact 

1. Change a new fan motor 

2. Check the wire connection and 

make sure they are in good contact 

 

 

 

 

 

Summary of Contents for CS-i Series

Page 1: ......

Page 2: ...Start up Shut Down ___________________________________________________________________ 9 5 2 2 Switching Modes Setting the Target Temperature ___________________________________________ 9 5 2 3 Clock...

Page 3: ...130 Heat output at 27 C air 26 C water kW 65 130 Heat output at 15 C air 26 C water kW 50 100 Cooling output at 55 C air 35 C water kW 15 54 Cooling output at 45 C air 26 C water kW 30 73 C O P AT 27...

Page 4: ...oHeat CS i Commercial Inverter Series Heat Pump 2 Unit Dimensions Evo CS i 65 unit mm Evo CS i 130 A L B W C H Water inlet outlet CS i 65 1750mm 830mm 1750mm 50 CS i 130 2260mm 1160mm 2127mm 100mm fla...

Page 5: ...oad protection system After a previous stoppage the unit will not start for at least 3 minutes For unit cleaning or maintenance switch off and disconnect the power of the unit Do not install the unit...

Page 6: ...on the front panel of the unit The gauge should be showing a pressure of approx 10 20 on the outside red band any less than this figure means there may be a leak in the refrigerant system and you shou...

Page 7: ...nstalled a maximum of 5m below the water level of the pool spa If further than 5M please discuss with your EvoHeat specialist for the best advice Make sure the heat pump is not located where large amo...

Page 8: ...in the air condenses on the fins of the evaporator During times of high humidity the condensate may be several litres per hour This may give the impression that the heater is leaking however this is a...

Page 9: ...he unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger After installation is completed follow the steps below 1 Turn on your filter pump Check fo...

Page 10: ...perature interface 7 Temperature Curve Click to view the temperature and power curve 8 Water Inlet Temperature Press to enter mode setting and the target temperature interface 9 LOCK Click to lock the...

Page 11: ...nction 1 Timing Start Button Start Green End Grey Click this button to start or end the timing start setting function 2 Timing On Setting Click to set the start time of the timer 3 Timing End Button O...

Page 12: ...check the failure record the main interface will display a static The failure record is in reverse order according to the time of occurrence Press the clean key to delete all fault records 5 2 6 Colou...

Page 13: ...eaners to ensure proper water flow Is the current pool spa water temperature higher than the set temperature on the controller If so the unit will not operate until the pool spa water temperature fall...

Page 14: ...If the water has chlorine it is a water leak and you need to contact EvoHeat tech support on 1300 859 933 Or Turn the heater off and run the water pump continuously for a period of 2 4 hours If the wa...

Page 15: ...rcuit Flow Switch Prot E03 No water little water in water system Check the pipe water flow and water pump Waterway Anti freezing Prot E05 Water temp or ambient temp is too low Inlet and outlet temp to...

Page 16: ...eck the input voltage measurement Inv Sampling Volt F11 The input voltage sampling fault Check and adjust the current measurement Comm Err DSP PFC F12 DSP and PFC connect fault Check the communication...

Page 17: ...101 123A 2 x 35mm2 35mm2 160A 30mA less than 0 1 sec 123 148A 2 x 50mm2 50mm2 225A 30mA less than 0 1 sec 148 186A 2 x 70mm2 70mm2 250A 30mA less than 0 1 sec 186 224A 2 x 95mm2 95mm2 280A 30mA less t...

Page 18: ...17 EvoHeat CS i Commercial Inverter Series Heat Pump 7 3 Wiring Diagrams 7 3 1 CS i 65...

Page 19: ...18 EvoHeat CS i Commercial Inverter Series Heat Pump 7 3 2 CS i 130...

Page 20: ...rature input 13 AI DI06 Water input temperature input 14 AI DI07 Water output temperature input 15 AI DI08 System fan coil temperature input 16 AI DI09 Ambient temperature input 17 AI DI10 Mode switch...

Page 21: ...time 8 1 Energy Saving Tips If your pool water is allowed to cool significantly it may take several days to return to the desired swimming temperature For weekend use it is more economical to maintai...

Page 22: ...y handling freighting or damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b prov...

Reviews: