(FIGURE 2-1) FIELD WIRING CONNECTIONS
A. Outdoor Sensor - outdoor air sensor, set point will adjust based on outdoor air temperature (not
needed if 0-10 VDC output is connected)
B. External sensor connection - system temperature sensor, senses water temp in a storage tank or
a heating loop.
C. Indirect Tank Sensor - Sensor for indirect DHW. An aquastat may also be connected here.
D. 0–10 VDC - connect a 0–10 VDC output here to vary set point temperature.
E. Additional Heat Source - dry contacts that will close a thermostat on an extra heater/boiler if the
cascade system is at 100% of capacity.
F. Lock Out Signal - alarm bell or light may be connected here to indicate that the boiler is a hard lockout.
G. Remote Thermostat - normally jumped. A room thermostat may be connected here to enable/
disable the heater/boiler.
H. Cascade Connection - communication cables get connected here and “daisy chained” to all heaters/
boilers in a cascade. This is polarity sensitive.
I. 3-Way Diverter Valve - Used in a boiler system with both Heating and Indirect Hot Water.
J. P2 - Pump for indirect. Used in a boiler system with both Heating and Indirect Hot Water.
K. P1 - Wire to primary pump for boilers.
L. P3 - Wire to primary pump for heaters or system pump for boilers.
M. Power Supply - connect 208–240 VAC single phase power supply here.