Combustible gases
E2638-LEL detector-transmitter is sensitive to light hydrocarbon gases (acetylene,
methane, propane, butane) and hydrogen.
See Annex 2 for more detailed information concerning the properties of the
detected gases.
NOTE Transmitter with catalytic type sensor is not suitable for acetylene detection.
Installation guidelines
(See Installation and connections section for general information.)
For  gases  lighter  than  air  install  the  sensor  higher  than  potential  leakage/generation
source or near the ceiling. Combustible gases lighter than air are hydrogen (0,07 of air
density), methane (0,55 of air density) and acetylene (0.90 of air density).
Propane and butane are heavier than air (1.55 and 2.0 of air density respectively) and
tend  to  sink.  It  is  recommended  to  place  the  sensor  lower  than  potential  leakage  or
generation source.
Calibration
E2638-LEL  devices  have  been  calibrated  by  Manufacturer  with  standard  gas
mixtures  before  delivery.  Provided  that  the  sensor  is  used  under  moderate
conditions,  the  recommended  recalibration  interval  for  metal  oxide  sensor  is  12
months. Catalytic sensors are more sensitive to the environment and require field
recalibration every 3...6 months. Please contact your dealer for more information.

E2638-LEL_UM_EN 

         Rev 25.05.2020

Specifications

Detected gases

acetylene, butane, hydrogen, methane, propane etc

Sampling method

diffusion

Sensor type

metal oxide semiconductor

catalytic (pellistor)

Typical detection range

0...100% LEL

0...100% LEL

Resolution / digital unit

0.1% LEL

1% LEL

Response time T90

ca. 60 s

8 s

Sensor lifetime

> 5 years

> 2 years

Calibration interval

12 months

3...6 months

Operating conditions

-30...+70 °C

-20 to +60°C

<95 % RH non-condensing, 0,9...1,1 atm 

explosion safe areas; normal ambient oxygen level

avoid exposure to corrosive gases or silicon containing

products

Signal update

every 1 second

Power supply options

11...30 VDC, 24 VAC

or 90...265 VAC (with mains power unit)

Power consumption

< 2 VA

Analog outputs

2 × 4-20 mA / 0-10 V, user settable

Outputs assignment

OUT1 2 gas; OUT2 2 gas

NOTE for LCD version only output 1 is available

Load resistance

R

L

 < (Us - 2 V) / 22 mA for 4-20 mA

R

L  

> 250 kOhm for 0-10 V mode

Digital interface

RS485, Modbus RTU protocol; no galvanic isolation

Enclosure

grey ABS, wall mount, protection class IP65

Dimensions

H90 × W145 × D55 mm

(overall dimensions H140 × W145 × D55 mm)

CE marking

according to 2014/30/EU and EN61326-1 requirements

Relay option

Output relays

2 × SPST relays (closing contact),

250 VAC / 30 VDC, 5 A max

Default alarm setpoints

RE1 (LOW): set 20% LEL; release 16% LEL

RE2 (HIGH): set 50% LEL; release 40% LEL

Signalling options
Visual

red and green LEDs

Acoustic alarm

buzzer 85 dB

LCD indicator option
Operating temperature

0...+50 °C

Display dimensions

72 × 36 mm

Number of digits

3.5 7-segment

Character height

14 mm

Other features

backlight

Other options

Remote probe

protection IP65, default cable length 3.0 m;

max height 80 mm, max diameter 65 mm

         Evikon MCI OÜ

                Teaduspargi 7/9, Tartu

[email protected]

         Tel. +372 733 6310 

  50411 Estonia

www.evikon.eu

PluraSens

®

Combustible Gases
Detector-Transmitter

E2638-LEL

User Manual