Evikon PluraSens E2418DP User Manual Download Page 3

E2418DP

Rev 27.05.2021

Specifications

Version

E2418DP-1K

E2418DP-10K

Detection range options

-1...+1 kPa

-10...+10 kPa

Resolution

1 Pa (0,01 mbar)

10 Pa (0,1 mbar)

Max. overpressure

10 kPa

80 kPa

Accuracy

±20 Pa

±200 Pa

Zero point drift

<5 Pa/year

<50 Pa/year

Temperature effect

Compensated within -5...+65 °C range

Analog outputs

2 × 4-20 mA or 0-10 V, user settable

Standard output scales

E2418DP-1K

E2418DP-10K

0-250 Pa,
0-500 Pa,

0-1,0 kPa

-250 - +250 Pa
-500 - +500 Pa

-1,0 - +1,0 kPa

0-2,5 kPa,

0-5 kPa,

0-10 kPa

-2,5 - +2,5 kPa

-5 - +5 kPa

-10 - +10 kPa

Digital interface

RS485, Modbus RTU protocol

Load resistance

RL < (Us - 3 V) / 22 mA for 4-20 mA

RL > 100 kOhm for 0-10 V mode

Operating conditions

-20...+70 °C, <99 %RH non+condensing,

Without dust, aggressive gases, mist or oil;

Residential or business spaces

Power supply options

11...30 VDC or 24 VAC

Power consumption

< 1 W

Electromagnetic
compatibility

According to 2014/30/EU:

EN 61000-6-3:2020, EN 61326-1:2013(EMC, emissions)

EN 61000-6-1:2019, EN 61000-6-2:2019(EMC, Immunity)

Enclosure

Light-grey ABS 82 × 80 × 55 mm, IP65

3

Summary of Contents for PluraSens E2418DP

Page 1: ...PluraSens Low differential pressure transmitter E2418DP User Manual...

Page 2: ...rements 4 Operating conditions 5 Installation and connections 5 Delivery set 8 Order code for E2418DP options 8 Configuring 8 Return to default settings 9 Emergency mode 9 Modbus RTU Communication 10...

Page 3: ...0 Pa 0 1 0 kPa 250 250 Pa 500 500 Pa 1 0 1 0 kPa 0 2 5 kPa 0 5 kPa 0 10 kPa 2 5 2 5 kPa 5 5 kPa 10 10 kPa Digital interface RS485 Modbus RTU protocol Load resistance RL Us 3 V 22 mA for 4 20 mA RL 100...

Page 4: ...uration of the transmitter and its integration into various automation systems through the Fieldbus network If the symbol is marked on the equipment consult the documentation for further information S...

Page 5: ...in the range of 20 70 C relative humidity in the range of 0 99 without condensation atmospheric pressure in the range of 84 106 7 kPa Installation and connections Before proceeding with the installat...

Page 6: ...ternal devices Attach the power cable to the device without turning it on Using the connection diagram below connect the analog outputs and digital interface terminals to the relevant devices accordin...

Page 7: ...ers J1 OUT1 and J2 OUT2 By closing pins on a specific jumper the related output is 0 10 V with an open jumper the output is 4 20 mA Power restart is required after changing the position of the jumpers...

Page 8: ...esolution 5 Pa E2418DP 10K Differential pressure transmitter regulator 25 25 kPa resolution 12 5 Pa E2418DP 25K Integrated 90 265 V mains power supply module E2418DP 230 Configuring Differential press...

Page 9: ...mA high current Bites Functions Notes Default bit 0 0 1 sensor present absent Read only bit 1 0 1 analog outputs activated deactivated 1 bit 2 0 1 in case of sensor absence turn signalling off on OUT...

Page 10: ...mit 168 RW Integrating filter time constant for pressure data s 1 32000 s 0 no filter 201 RW Parameter assigned to OUT1 0 none 1 temperature 2 pressure 9 forced Modbus control value set in 203 202 RW...

Page 11: ...rameters Parameter Permitted values Default Supported baud rates 1200 2400 4800 9600 19200 38400 57600 9600 Data bits 8 8 Parity none odd even none Stop bits 1 2 1 Protocol Modbus RTU Modbus functions...

Page 12: ...anufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manuf...

Reviews: