
E2408DF
Rev 27.05.2021
Return to default settings
To reset the device’s Slave ID, baud rate and stop bit number to factory settings, proceed as
follows:
1. De-energize the device
2. Connect the X6 jumper
3. Turn on the device
4. De-energize the device
5. Disconnect the X6 jumper
6. Turn on the device
Emergency mode.
The current outputs of the detector may be programmed via Modbus commands (register
255) to signal if the connection with the sensor is lost. The signal may be set to 3,8 mA
(low current) or 21,5 mA (high current).
Bites
Functions
Notes
Default
bit[0]=0/1
sensor present/absent
Read-only
bit[1]=0/1
analog outputs activated/deactivated
1
bit[2]=0/1
in case of sensor absence, turn signalling
off/on (OUT 1)
1
bit[3]=0/1
In case of sensor absence turn on
signalling with low/high current on OUT 1
if bit [2]=0, this bit is ignored 0
bit[4]=0/1
in case of sensor absence, turn signalling
off/on (OUT 2)
1
bit[5]=0/1
In case of sensor absence turn on
signalling with low/high current on OUT 2
if bit [4]=0, this bit is ignored 0
bit[6]=0/1
Current/voltage output detected on OUT 1 Read-only
User defined
bit[7]=0/1
Current/voltage output detected on OUT 2 Read-only
User defined
bit[8]=0/1
LED deactivated/activated
Always 0 for 2408DF
0
bit[9]=0/1
Buzzer deactivated/activated
Always 0 for 2408DF
0
10