background image

E2615-H

2

S

Rev 24.08.2022

Hydrogen Sulfide

Colorless toxic, corrosive and flammable gas with a smell of rotten eggs. Occurs in natural
gas, volcanic gases, petroleum, and some sources of well water. It results from the
anaerobic decay of sulfur-containing proteins, e.g. in sewers.

Synonyms: Hydrosulfuric acid, Sewer gas, Sulfuretted hydrogen.

Chemical formula

H

2

S

Molar weight

34

Conversion

1 ppm = 1.40 mg/m

3

Relative gas density (to air)

1.17

Boiling point

−60 °C

Low explosive limit (LEL), % vol.
in air

4.0

Upper explosive limit (UEL), %
vol. in air

44.0

Odor

The characteristic smell of rotten eggs. Above 30 ppm, the odor is

described as sweet or sickeningly sweet.

Odor threshold

0.01-1.5 ppm

Note:

Sense of smell becomes rapidly fatigued and can NOT be

relied upon to warn of the continuous presence of H

2

S.

Hazards

Highly flammable, explosive gas.

Broad-spectrum poison, mostly affecting the nervous system. At

low concentrations causes eye irritation, a sore throat and cough,

nausea, shortness of breath, and pulmonary edema. Long-term,

low-level exposure results in fatigue, loss of appetite, headache,

poor memory, irritability, and dizziness. Exposure to high levels

can induce immediate collapse, with loss of breathing and a high

probability of death.

Exposure

limits

(Commission
Directive
2009/161/EU)

TWA

7 mg/mm

3

/ 5 ppm

STEL

14 mg/mm

3

/ 10 ppm

IDLH
(NIOSH)

140 mg/mm

3

/ 100 ppm

Conversion of ppm to mg/m

3

is calculated for 25°C and 1 atm.

3

Summary of Contents for E2615-H2S

Page 1: ...Hydrogen Sulfide Transmitter E2615 H2S User Manual...

Page 2: ...5 Product description 6 Safety requirements 6 Operating conditions 6 Installation guidelines 6 Mounting dimensions 8 Electrical connections 9 Operation 10 Maintenance 10 Calibration 10 Delivery set 1...

Page 3: ...described as sweet or sickeningly sweet Odor threshold 0 01 1 5 ppm Note Sense of smell becomes rapidly fatigued and can NOT be relied upon to warn of the continuous presence of H2S Hazards Highly fl...

Page 4: ...plastic wall mount protection class IP65 Indoor enclosure White ivory or black ABS plastic wall mount protection class IP20 Dimensions IP65 H70 W80 D36 mm IP20 H71 W71 D27 mm CE marking According to...

Page 5: ...voids the warranty Do not touch the electronic components directly as they are sensitive to static electricity Connection diagrams can be found in the electrical connections section The device might n...

Page 6: ...ance calibration The aforementioned conditions above will affect the coverage area of the device However the coverage area for a transmitter is usually between 2 5 to 5 meters radius For early leakage...

Page 7: ...th a hydrophobic microporous PTFE filter to protect the sensor from dust dirt and water drops NOTE Never stab or press the filter near its center where the sensor is located since this may damage the...

Page 8: ...f wires with a cross section of 0 2 1 5 mm2 We recommend to strip the wire end by 8 9 mm and use wire end sleeves To connect the wire loosen the screw insert the wire end into the terminal hole and ti...

Page 9: ...the screws The device is ready to use Maintenance Do not perform any maintenance operation with the power on Clean the device with a soft damp cloth Do not use any abrasive cleaning agents Do not imm...

Page 10: ...24 08 2022 Delivery set Transmitter E2615 Mounting accessories 2 screws with plastic dowels Order code for E2615 H2S options E2615 options Order code IP20 enclosure E2615 H2S IP20 IP65 enclosure E261...

Page 11: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Man...