E2610-CO 

Rev 28.10.2020 

Connections 

1. Detach the base of the enclosure by gently pulling along four guiding pins. 

2. Attach the base to the wall with two screws. (see drawings below). 

 

3. Use rounded cutouts on the side of the base to let in the cables from the power supply

 

 

 

 

 

 

   

 

   

   

 

 

 

 

 

 

and of the external devices as shown below. 

 

 

Summary of Contents for E2610-CO

Page 1: ...Carbon Monoxide Detector E2610 CO User Manual...

Page 2: ...3 Specifications 4 Product description 5 Safety requirements 5 Operating conditions 5 Installation guidelines 6 Connections 7 Operation 9 Maintenance 9 Calibration 9 Delivery set 10 Order code for E2...

Page 3: ...eight 28 Relative gas density to air 0 97 Conversion 1 ppm 1 15 mg m 3 Boiling point 191 5 C Low explosive limit LEL vol in air 12 5 Upper explosive limit UEL vol in air 74 Odor odorless Hazards Highl...

Page 4: ...Relay outputs 2 SPDT max 5 A 30 VDC 250 VAC Alarm Buzzer 85 dB Enclosure ABS plastic with ventilation slots wall mount protection class IP20 Dimensions H85 W85 D37 mm CE marking According to 2014 30 E...

Page 5: ...electronic components directly as they are sensitive to static electricity Connection diagrams can be found in the connections section The device might not perform correctly or be damaged if the wron...

Page 6: ...nce and repair The aforementioned conditions above will affect the coverage area of the device however the coverage area for a detector is usually between 2 5 to 5 meters radius For early leakage dete...

Page 7: ...the enclosure by gently pulling along four guiding pins 2 Attach the base to the wall with two screws see drawings below 3 Use rounded cutouts on the side of the base to let in the cables from the po...

Page 8: ...2610 series devices are suitable for a wide range of wires with cross section 0 2 1 5 mm 2 We recommend to strip the wire end by 5 6 mm and tin it or to use the wire end sleeves To connect the wire lo...

Page 9: ...ow 80 of the LOW alarm setpoint If the gas level exceeds the HIGH alarm setpoint the bottom red LED starts flashing and the buzzer starts beeping at a rate of 2 Hz and also the relay RE2 switches over...

Page 10: ...ide Detector E2610 CO Mounting accessories 2 screws and 2 plastic dowel plugs Order code for E2610 CO options 10 E2610 options Order code Integrated 90 265 V mains power supply module E2610 CO 230 Int...

Page 11: ...anufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manuf...