background image

 

 

Safety Instructions 

 

1).Avoid electric shock 

Danger!!

 

 

Please do not touch any part of the battery or the frame, electrolyte, cooling water of 
the battery by hand when the equipment charging up the battery. Operator shall wear 
insulative waterproof rubber shoes and gloves to operate the battery, or may result in 
electric shock injury accident. 

 

Please  do  not  operate  the  equipment  when  opening  the  door  of  equipment,  or  may 
touch the high voltage terminal and result in electric shock accident. 

 

Keep the equipment off-position when connecting the battery, or may result in electric 
shock or injury. 

 

Please  do  not  open  the  equipment  when  powering  on  or  operating,  or  would  get  an 
electric shock.   

 

Please do not approach nearby ground when the equipment is on-position because in 
the  process  of  charging, the  output  positive  and  negative  side  would  in  high pressure 
and the ground would have leakage current from the frame. The ground nearby would 
in high pressure. 

 

Please do not touch the DC output end in high pressure state, or may result in electric 
shock. 

 

When  Wiring  or  examining,  power  shall  be  disconnected  and  10  minutes  later, 
detecting  the  residual  voltage  disappearing  by  multimeter,  or  may  result  in  electric 
shock accident. 

 

Please  do  not  maintain  the  equipment  when  the  DC  output  end  still  connecting  the 
battery  even  though  the  power  is  at  a  off-position  state.  Please  maintain  without 
connecting the battery, or may result in electric shock accident for the battery voltage 
attaches  to  the  equipment  through  output  cable  and  the  equipment  still  in  high 
pressure. 

 

The equipment shall use third-level or above grounding method. 

 

Please do not change the fuse when charging with electricity, or may result in electric 
shock. 

 

Please  do  not  change  the  fuse  when  the  equipment  outputting  and  connecting  the 
battery. 

 

Please do not operate the switch by wet hand to avoid electric shock. 

 

The  operation  including  wiring  and  examination  shall  be  conducted  by  professional 
technician.   

 

Please  do  not  damage,  stress,  clamp or make  the  input  and  putout  cable carry  heavy 
objects, or may result in electric shock.   

 

The battery rack or frame shall use third-level or above grounding method. 

 
 

Summary of Contents for uXcel Series

Page 1: ...uXcel series charger user manual Everexceed Corporation...

Page 2: ...logy without prior notice Please keep this manual to the end operator and maintenance personnel Safety Precautions Please do not install operate maintain or examine the equipment before reading the us...

Page 3: ...utput end in high pressure state or may result in electric shock When Wiring or examining power shall be disconnected and 10 minutes later detecting the residual voltage disappearing by multimeter or...

Page 4: ...he same performance Using the fuse of different model or different performance may result in fire 3 Avoid Injury Caution The voltage of each terminal shall be the regulated voltage to avoid bursting a...

Page 5: ...left and right vent of the equipment not blocking by objects Please keep the screw the debris of cable or other conductive body or oil combustible out off the equipment Please use in the following con...

Page 6: ...abnormal charge and damage the battery Please trial run after maintaining the equipment The equipment unused for a long time shall keep away from dampness and keep in seal It must be checked and trial...

Page 7: ...operating principle 9 3 2 Circuit schematic diagram 9 4 Installation 10 4 1 Safety precautions 10 4 2 Installation instructions 10 5 Operating instructions 10 5 1 Panel display and description 10 5 2...

Page 8: ...grade The power component adopts aluminum profile and high power SCR component of cake shape The product has superior performance and stable operation In addition it has long distance centralized cont...

Page 9: ...current charging constant current and limiting voltage discharging cycling etc Protection Reserving data when there is over current over voltage current cutting and power off It could automatically re...

Page 10: ...r would output the charging mode current and voltage required Measuring the present current and voltage uninterruptedly when the touch panel is working and comparing with the current and voltage requi...

Page 11: ...rder form and the cabinet has no apparent damage Removing the fixed screw and holder to check whether each component and wire loose or short out or not The equipment shall be installed vertically The...

Page 12: ...ion When the charging machine stops or fails the indicator will go out Failure indicator light of charger The charging machine state indicates that the charging machine is normally extinguished under...

Page 13: ...when it out of order displaying by screen and judging whether the equipment misfunctions or not b Real time operating and controlling the equipment The operations to charging power mainly are operatin...

Page 14: ...he charging voltage and current that changed by time It could save st most charging curve of 7 days As showed in the figure 5 4 Figure 5 4 4 Charging setting screen Operator could click the top button...

Page 15: ...ge or current reaches this adjustment it would leap and leap to the step of setting next step Minus means leaping if it is less than the value No symbol means leaping if it is more than the value Limi...

Page 16: ...Step 2 Setting charging state as boost and the charging mode as constant voltage with 56 4V Time could be set as 0min 0 means the leaping condition would not affect by time Setting next step as 3 and...

Page 17: ...ton could download the charging step to changing setting screen For example the charging setting of the 48V200AH battery bank mentioned above has three steps For convenience it could save the whole ch...

Page 18: ...screen could set the parameters of over under voltage protection overload protection phase break protection and three phase imbalance as showed in the figure 5 11 Figure 5 11 8 System set Language se...

Page 19: ...ction password and system password as showed in the figure 5 13 Figure 5 13 network setting setting the parameters of IP address and remote control for the charger please find the specific entering wa...

Page 20: ...y reset resetting the charger and the factory reset value shall be the present value saved Charger panel factory reset when the charger panel out of order or system halted its function is to restore t...

Page 21: ...charging voltage of the first step as 10 50 100 rated voltage in turn and it begins charging Checking whether the virtual voltage is in line with the setting voltage or not If it matches then go to t...

Page 22: ...ting in cutout 1 Checking the contactor and wiring 2 Checking the fuse 3 Checking the air switch 4 Checking the inside wiring situation and fastening 5 Changing the malfunction components Control pane...

Page 23: ...pection Charger is a stationary machine mainly formed by semiconductor In order to avoid the influences of using condition such as acid mist temperature humidity dust dirt and vibration and other fact...

Page 24: ...place as follows the company will provide warranty service 1 Warranty scope refers only to the charging machine body 2 During the product warranty period the manufacturer shall be responsible for the...

Page 25: ...ection Don not connect if do not use 8 9 CT3 current transformer connecting terminal It is corresponding to W phase current display and has overcurrent protection and the recognition function of open...

Page 26: ...rminal Another terminal is corresponding to 17 COM connection When in malfunction connecting 17and 25could reset the system 26 SCR overheating input terminal Another terminal is corresponding to 17 CO...

Reviews: