EVER POWERLINE DARK 33 10 - 40 kVA UPS Operating Manual
39
Technical Assistance, phone: +48 61 6500 400
2019-06-10 14:36 Type 01
- in NC configuration, to pins J4-1 and J4-2
- in NO configuration, to pins J4-3 and J4-4
If the UPS is not connected to an external circuit, a jumper must be placed on pins
J4-1 and J4-2. Pins J4-3 and J4-4 should remain disconnected (standard
configuration).
Powering from a Generator
The J5 input terminal is used for communication with the generator (information
about the UPS receiving power from a generator). The method of connection is
presented in Fig. 31.
J5
GEN
+24V
AUX-N.O.
AUX-N.O.
Generator
Fig. 31: Connections for J5 terminal
Battery switch
Terminals J6 and J7 are used when an optional battery switch system is used. Fig.
32 presents the manner of making the connection. Table 7 presents the pinout and
the relevant description.
B
C
B
_
D
R
V
B
C
B
_
C
O
N
T
J6
J7
B
C
B
_
O
N
L
+24V
+24V
+24V
Fig. 32: Connections for J6 and J7 terminals