114J500E4.01
·
EVJ 500
series
04/2021
|41|
9. PARAMETERS
Description of columns in the Table of Parameters
• Par
.:Listofconfigurabledeviceparameters;
• Description
: Indicates parameter operation and any possible selections;
• MU
: Measurement unit relating to the parameter;
• Range
: Describes the interval of values that the parameter can assume. This can be correlated with other instrument
parameters (indicated with the parameter code).
NOTE
:
if the actual value is outside the permitted limits for that parameter (for example, because other parameters
defining the aforementioned limits have been altered), the value of the violated limit is displayed instead of the actual
value;
• Default
:Indicatesthepre-setfactoryconfiguration;
• PW
: Indicates the access level for the parameter.
9.1 TABLE OF CONFIGURATION PARAMETERS
Par. Description
MU
Range
Default models
PW
506
526
536
ANALOGUE INPUTS Group
CA1
Pb1probeoffset.
°C/°F
-25.0...25.0
0.0
0.0
0.0
1
CA2
Pb2 probe offset.
°C/°F
-25.0...25.0
0.0
0.0
0.0
1
CA3
Pb3 probe offset.
°C/°F
-25.0...25.0
0.0
0.0
0.0
2
P0
Type of probe.
0
=PTC+EVHTP500;
1
=NTC+EVHTP500;
2
=PTC+EVHTP520;
3
=NTC+EVHTP520.
---
0/1
1
1
1
2
P1
Enable decimal point in °C.
0
= No;
1
= Yes.
---
0/1
1
1
1
2
P2
Temperaturemeasurementunit(ifthevalueischanged,thetemperature
parameter limits must be reset manually).
0
= °C;
1
=°F.
---
0/1
0
0
0
2
Pr3
Probe Pb3 configuration.
0
= Digital input ID3;
1
= Condenser probe;
2
= Needle probe (display only);
3
= External air probe (display only).
4
=Auxiliaryprobe;
5
= Defrost 2 probe.
---
0...5
5
5
5
2
P5
Largedisplay1value.
0
= No information displayed (display off);
1
=Analogueinput1;
2
=Analogueinput2;
3
=Analogueinput3;
4
=Setpoint1(Temperature);
5
= Setpoint 2 (Humidity).
---
0...5
1
1
1
2
P6
Small display 2 value. Same as
P5.
---
0...5
2
2
2
2
P8
Refreshtimedisplay1.
Increaseordecreaseby1digitforintervalselected.
s
0...250
5
5
5
2
P9
Refresh time display 2.
Increaseordecreaseby1digitforintervalselected.
s
0...250
5
5
5
2
P31
Enable setpoint change of programme in progress and times during active
cycle.
0
= No;
1
= Yes.
---
0/1
1
2
P32
If
P31
=1savechangestosetpointsintheprogrammetoo.Timer
variations are excluded.
0
= No;
1
= Yes.
---
0/1
0
2
TEMPERATURE REGULATION Group
r0
Cooling mode setpoint differential.
°C/°F 0.1...25.0
2.0
2.0
2.0
1
r1
Minimum setpoint.
°C/°F
-30.0...
r2
0.0
0.0
0.0
2
r2
Maximum setpoint.
°C/°F
r1
...99.0
50.0
50.0
50.0
2
r4
Setpoint offset in energy saving added to setpoint value.
°C/°F
0.0...99.0
0.0
0.0
0.0
2
r5
Disable humidity regulation in OverTemp function.
0
= No;
1
= Yes.
---
0/1
0
0
2
r6
ThresholdrelativetoSetpoint1temperatureinOverTempfunction.
°C/°F
-40.0...99.0
0.0
0.0
2