NOTICE TO THE INSTALLER

This manual provides an overview and the installation instructions for the EVAX EVX-ATM Audio Transponder Module. All terminals are 

power limited and should be wired in accordance with the requirements of NFPA 70 (NEC), NFPA 101 (Life Safety Code) and NFPA 

72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as 

intended. For further information, refer to the control panel installation instructions.
The module shall only be installed with listed devices. Refer to the installation manuals for proper system operation.

Description

The EVX-ATM provides a method of interfacing audio either into the evac system or from the evac system into an external paging 

system. It has several methods of accomplishing this and is field selectable for itsmodes. It is capable of being activated by either 

contact closure or signal presence by use of a VOX, Voice Activation Circuit. Its input may be Balanced Line, 1 Vrms into 600 Ohms, 25 

Vrms or 70 Vrms.

The input and output signals are isolated so systems will not experience ground loop problems.

Mounting: EVX-ATM mounts into standard 3” snaptrack. The board also has mounting holes at the corners for stand-off mounts where 

required.

5403676 Rev A  1/18

Evax by Potter        •           Branford, CT             •           Phone: (800) 325-3936               •            www.evax.com

 

PAGE 1 OF 4

1
2
3
4
5

6
7
8

1

2

3

4

1

2

EVX-ATM

A B C D

J1

P Q - R

J2

J6

V -

J4 1V 25

V

70

V

J3

1 5 M

J5

X Y

TB1

TB2

TB3

VR1

P1

TB2:

Ter. 1 - 2  Audio input   

selectable

Bal. Line 1V-600 Ohm,

25/70 VRMS       

TB1:

Ter. 1 - 

signal)

Ter. 2 - V+ (24V DC 0.10A)

Ter. 3 - ALARM

Ter. 4 - AUX SIG

Ter. 5 - AUX PTT 

Ter. 6 - Signal

Ter. 7 - Aux. Audio / PreAmp

PTT (Push To Talk 

TB3:

Ter. 1& 2 - N.O. Dry Contact

Ter. 3 - 4 - Bal. Line output

JUMPERS:

J1 - PTT Function 

J2 - Audio Path

J3 - Gain

J4 - Audio Input 

Voltage

J5 - Dry Contact 

Function

J6 - Audio Input

SPECIFICATIONS:

Power: 24 VDC

            0.015A Standby

            0.035A  Active

Dimensions: 3 x 3”

  

mounting holes 0.160” dia.  0.25” centered @ corners

Summary of Contents for EVX-ATM

Page 1: ...t is capable of being activated by either contact closure or signal presence by use of a VOX Voice Activation Circuit Its input may be Balanced Line 1 Vrms into 600 Ohms 25 Vrms or 70 Vrms The input and output signals are isolated so systems will not experience ground loop problems Mounting EVX ATM mounts into standard 3 snaptrack The board also has mounting holes at the corners for stand off moun...

Page 2: ...VX 25 50 100 Field wiring connections 6 32 wire clamp screw 14 18AWG 8 32 wire clamp screw 12 18AWG Horizontal wire entry terminal 18 26 AWG Wire gauge determined by circuit load 1 2 3 4 5 6 7 8 1 2 3 4 1 2 EVX ATM A B C D J1 P Q R J2 J6 V J4 1V 25V 70V J3 1 5 M J5 X Y TB1 TB2 TB3 VR1 P1 Jumper Settings J1 P J2 C J3 1 J4 1V 25V 70V J5 X J6 V Connections to EVX 25 50 100 Audio Input 25V 70V is sele...

Page 3: ... driving VOX circuit provides activation on presence of audio signal External Audio System Audio Input 25V or 70V is selected at J4 600 ohm audio out 24 VDC Neg EVX ATM to be mounted within external system cabinet N O dry contact available if needed to activate input of external unit Field wiring connections 6 32 wire clamp screw 14 18AWG 8 32 wire clamp screw 12 18AWG Horizontal wire entry termin...

Page 4: ...nable Blue Enable Blue Audio White Audio White Ckt Neg Green Ckt Neg Green EVAX HMX External Audio into HMX MP 600 ohm balanced line 25VRMS or 70 VRMS input EVX ATM required if external audio source is other than 600 ohm 1VRMS balanced See Page 2 for jumper settings Field wiring connections 6 32 wire clamp screw 14 18 AWG 8 32 wire clamp screw 12 18 AWG Horizontal wire entry terminal 18 26 AWG Wir...