13.7. Changing device configuration (using DIP switches)
Tip!
You will find an animation on device configuration at www.euchner.com.
DIP switches
The device can be configured using the DIP switches. The following
settings are possible:
Ì
Changing system family (BR/BP switching)
Ì
Deactivating guard lock monitoring
Ì
Activating release monitoring (possible only with active guard lock
monitoring)
Position of the switches
Item
Description
1
DIP switch
2
Sticker with factory setting
Function of the switches
Switch
Function
1+4
on: device is operated as a BP system
off: device is operated as a BR system
2+5
on: guard lock monitoring is deactivated
off: guard lock monitoring is active (usually factory setting)
3
on: release monitoring is activated
off : release monitoring is deactivated (usually factory setting)
6
n.c.
7
on: factory reset on
off: factory reset off
8
on: configuration possible
off: configuration inhibited (factory setting)
13.7.1. Changing system family (BR/BP switching)
CAUTION
Malfunction due to incorrect configuration or incorrect connection.
Ì
Note that the terminal assignment also changes on changing the configuration (see chapter
13.10. Terminal assignment and contact description on page 38
1. Switch off power supply.
2. Set DIP switches 1, 4 and 8 as shown.
For change from BR => BP
For change from BP => BR
1
ON
3
4
6 7
8
2
5
1
ON
3
4
6 7
8
2
5
3. Switch on power supply for 5 s.
¨
The change is confirmed by positive acknowledgment.
4. Switch off power supply and set DIP switch 8 to OFF.
¨
The next time the device is started, it operates in the operating mode set.