2105360-10-07/19 (Translation of the original operating instructions)
Operating Instructions
Non-Contact Safety Switch CES-AP-C.2-…
EN
11. Technical data
NOTICE
If a data sheet is included with the product, the information on the data sheet applies.
11.1. Technical data of safety switch CES-AP-C.2-…
Parameter
Value
Unit
min.
typ.
max.
Housing material
PBT plastic
Dimensions
95 x 30 x 12
Weight (device without connecting cable)
0.04
kg
Degree of protection
IP67/IP69K
(IP67 for version with M12 plug connector)
Safety class
III
Degree of contamination
3
Installation orientation
Any
Connection
- Plug connector with snap-action, 6-pin, or
- Connecting cable PUR, 0.14 mm², with plug connector M12, 5-pin, or
- Connecting cable PVC with flying lead, 6 x 0.14 mm²
Ambient temperature at U
B
= DC 24 V
°C
- Plug connector with snap-action
- 30
-
+ 65
- Connection cable laid rigidly
- 40
-
+ 65
- Connection cable movable
0
-
+ 65
Storage temperature
- 40
-
+ 70
Operating voltage U
B
(regulated, residual ripple < 5%)
24 ± 15% (PELV)
V DC
Current consumption
30
mA
External fuse
(operating voltage)
0.25
-
8
A
Safety outputs OA/OB
Semiconductor outputs, p-switching, short circuit-proof
- Output voltage U(OA)/U(OB)
1)
HIGH
U(OA)
U
B
-1.5
-
U
B
V DC
HIGH
U(OB)
LOW
U(OA)/U(OB)
0
1
Switching current per safety output
1
-
150
mA
Utilization category acc. to EN IEC 60947-5-2
DC-13 24 V 150 mA
Caution: Outputs must be protected by a free-wheeling diode in the case of inductive loads.
Off-state current I
r
2)
≤ 0.25
mA
Monitoring output DIA
1)
p-switching, short circuit-proof
- Output voltage
0.8 x U
B
-
U
B
V DC
- Max. load
-
-
50
mA
Rated insulation voltage U
i
-
-
75
V
Rated impulse withstand voltage U
imp
-
-
1.5
kV
Conditional short-circuit current
100
A
Resilience to vibration
Acc. to EN IEC 60947-5-2
Switching frequency
-
-
1
Hz
Repeat accuracy R
acc. to EN IEC 60947-5-2
≤
10
%
EMC protection requirements
Acc. to EN IEC 60947-5-3
Ready delay
-
0.5
-
s
Risk time
-
-
260
ms
Switch-on time
-
-
300
ms
Discrepancy time
-
-
10
ms
Test-pulse duration
300
µs
Test-pulse interval
100
ms
Reliability values acc. to EN ISO 13849-1
Category
4
Performance Level
PL e
PFH
D
1.8 x 10
-9
/ h
Mission time
20
years
1) Values at a switching current of 50 mA without taking into account the cable length.
2) Maximum current at an output in switched-off state.