Operating Instructions
Non-Contact Safety Switch CES-AH-C03-AE-LS
8
(Translation of the original operating instructions) 2105267-10-08/20
7. Mounting
CAUTION
Risk of damage to equipment as a result of incorrect installation. Safety switches must not be used
as a mechanical end stop.
Ì
Fit an additional end stop for the movable part of the guard.
Important!
Ì
From the assured release distance S
ar
, the safety outputs are safely shut down.
Ì
When mounting several safety switches, observe the stipulated minimum distance to avoid mutual
interference.
min. 80mm
Ì
If the actuator is installed flush, the operating distances change as a function of the installation
depth and the guard material.
Operating
distance
Actuator
Operating
distance
Actuator
Flush mounting
Surface mounting
Note the following points:
Ì
Actuator and safety switch must be easily accessible for inspection and replacement.
Ì
Actuator and safety switch must be fitted so that
-the front faces are at the minimum operating distance 0.8 x Sao or closer when the guard is closed (see section
Actu-
ating ranges
). For a side approach direction for the actuator a minimum distance must be maintained so that the actu-
ating range of the side lobes is not entered (see actuating range for the actuator).
-when the guard is open up to the distance Sar (assured release distance), a hazard is excluded.
-the actuator is positively mounted on the guard, e.g. by using the safety screws included.