12.2. Electrical function test
WARNING
Danger of fatal injury as a result of faults in installation and functional check.
Ì
Before carrying out the functional check, make sure that there are no persons in the danger zone.
Ì
Observe the valid accident prevention regulations.
After installation and any fault, the safety function must be fully checked. Proceed as follows:
1. Switch on operating voltage.
¨
The machine must not start automatically.
¨
The safety switch carries out a self-test. The green STATE LED flashes for 5 s at 5 Hz. The green STATE LED then flashes
at regular intervals.
2. Close all guards.
¨
The machine must not start automatically.
¨
The green STATE LED illuminates continuously.
3. Enable operation in the control system.
4. Open the guard.
Ì
The machine must switch off and it must not be possible to start it as long as the guard is open.
Ì
The green STATE LED flashes at regular intervals.
Repeat steps 2 - 4 for each guard.
13. Factory reset
A factory reset deletes the parametrization and restores the device’s factory settings.
To perform a factory reset, connect the two outputs FO1A and FO1B to 0 V when switching on or send the command Ox1E
via IO-Link communication (see chapter
11.3.2. Acyclical data (device data and events) on page 21)
.