10. Connection of several devices in a switch chain (series connection)
Important!
Ì
A BR switch chain may contain a maximum of 20 safety switches.
Ì
The following connection examples show only excerpts that are relevant for the connection
of the CES system. They do not represent complete system planning. The user is responsi-
ble for safe integration into the overall system. Detailed application examples can be found at
www.euchner.com. Simply enter the order number of your switch in the search box. You will find all
available connection examples for the device in
Downloads
.
Ì
When using Y-distributors, make sure to use the correct Y-distributor version. See chapter
Connector assignment of Y-distributor for series connection without IO-Link communication on
page 16 and 10.2.4. Connector assignment of Y-distributor for series connection with IO-Link
10.1. Series connection with wiring in the control cabinet
The series connection can be realized via additional terminals in a control cabinet.
The safety outputs are permanently assigned to the respective safety inputs of the downstream switch. FO1A must be rout-
ed to FI1A and FO1B to FI1B. If the connections are interchanged (e.g. FO1A to FI1B), the device will enter the fault state.