8. Electrical connection
1 AS-Int
3 AS-Interface -
4 Not used
View of plug connector
Safety switch
1
4
3
Figure 1:
Terminal assignment, AS-Interface M8 plug connector
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì
Power devices which are a powerful source of interference must be installed in a separate location
away from the input and output circuits for signal processing. The cable routing for safety circuits
should be as far away as possible from the cables of the power circuits.
Ì
To avoid EMC interference, the physical environmental and operating conditions at the in-
stallation site of the device must comply with the requirements according to the standard
EN 60204-1:2006, section 4.4.2 (EMC).
Ì
Pay attention to any interference fields from devices such as frequency converters or induction
heating systems. Observe the EMC instructions in the manuals from the respective manufacturer.
Ì
To ensure the degree of protection IP67 is achieved, the mating connector must be tightened with
0.3 Nm. This value must not be exceeded, however.
Important!
If the device does not appear to function when operating voltage is applied (e.g. green STATE LED
does not flash), the safety switch must be returned unopened to the manufacturer.
8.1. Notes about
Important!
Ì
This device is intended to be used with a
Class 2
power source in accordance with UL1310.
As an alternative an LV/C (Limited Voltage/Current) power source with the following properties can
be used:
- This device shall be used with a suitable isolating source in conjunction with a fuse in accordance
with UL248. The fuse shall be rated max. 3.3 A and be installed in the max. 30 V DC power supply
to the device in order to limit the available current to comply with the
requirements. Please note
possibly lower connection ratings for your device (refer to the technical data).
Ì
For use and applications as per the requirements of
1)
, a connecting cable listed under the UL
category code CYJV2 or CYJV must be used.
1) Notice on the scope of the UL approval: only for applications as per NFPA 79 (Industrial Machinery). The devices have been tested as per the requirements of
UL508 and CSA/ C22.2 no. 14 (protection against electric shock and fire).