OVERVIEW
DOC_DEV_IPL_User Guide_C
Page 9
3
Specifications
General characteristics
Dimensions
IPL-X-100: 120 x 37 x 88 mm (h,w,d)
Other IPL: 135 x 47 x 115 mm (h,w,d)
Weight
Max 0.65 kg
Casing
Metallic
IPL- X-100: IP41
–
IEC60529
Other IPL: IP20
–
IEC60529
DIN rail mounting
Temperature
Non-operating: -40°/ + 85°C
Operating: -20°/ +70°C
Humidity
5 to 95 % relative (non-condensing)
Power supply
Protected against reverse polarity
IPL-X-100: Nominal: 12-24 VDC (min 10 VDC - max 30 VDC)
Other IPL: Nominal: 12-48 VDC (min 10 VDC - max 60 VDC)
2 points Phoenix connector
Consumption
IPL-E : 2W
IPL-A, IPL-C and IPL-EW : 5W
IPL-AW, IPL-CW, IPL-DAC : 8W
EMC
Immunity EN61000-6-2:
EN61000-4-2 : ESD : 4 kV contact
–
8kV air
EN61000-4-3 : RF - radiated: 10V/m < 2 GHz
EN61000-4-4 : Burst
EN61000-4-5 : Surge : 4KV line / earth
EN61000-4-6 : RF - conducted
EN61000-4-8 : Magnetic fields
Emission EN61000-6-4:
EN 55032: RF - conducted and radiated
FCC:
IPL-X-100 : FCC Part 15
Electrical safety
IEC/EN 62368-1
IPL-X-100 : CB FR_704843
Hazardous substances
2011/65/UE (RoHS)
REACH