TOROIDAL CURRENT TRANSFORMERS /  Manual instruction 

                     Toroidalne przekładniki pr

ą

dowe / Instrukcja obsługi

 

 

GENERALITY/ INFORMACJE OGÓLNE 

The toroidal current transformer CTE line allow the remark of homopolar differential 

current disperse in the earth direction. The toroidal current transformer CTE are designed to be 
combined with relays of maximum differential current LRE line. 
The current transformer must be installed at the beginning of line or load to protect or to supervise, 
all the active conductor (phase and neutral) of the single phase and three phase line. The current 
transformer read the vectorial sum of the current in the way to transmit at the secondary coil the earth 
leakage current. 
For other applications of current transformer CTE it’s necessary to see specific documentation (for 
example the reading of the earth homopolar current on supplying transformer). 
 

Toroidalne przekładniki pr

ą

dowe CTE.. umo

ż

liwiaj

ą

 wykrycie homopolarnych

 

pr

ą

dów 

ż

nicowych spływaj

ą

cych w kierunku ziemi. Przekładniki s

ą

 zaprojektowane do współpracy z 

przeka

ź

nikami ró

ż

nicowopr

ą

dowymi serii LRE… 

Przekładnik pr

ą

dowy musi by

ć

 zainstalowany na pocz

ą

tku linii lub  obci

ąż

enia dla ochrony lub 

nadzoru wszystkich czynnych przewodów (fazowych i neutralnego) w sieci jedno- lub trójfazowej. 
Przekładnik odczytuje wektorow

ą

 sum

ę

 pr

ą

dów w celu przeniesienia na uzwojenie wtórne cewki 

sygnału odpowiadaj

ą

cego pr

ą

dowi upływu. 

Dla prawidłowego zastosowania przekładnika CTE… nale

ż

y zapozna

ć

 si

ę

 ze specyfik

ą

 zjawisk 

obejmuj

ą

cych wykrywanie pr

ą

dów ró

ż

nicowych. 

 

INTRODUCTION/ WST

Ę

The current transformer CTE are built with a core of sheet iron of excellent magnetic 

quality that allows to read fault currents a lot of low. On the core are wrapped two coils, one to read 
the fault signal, the other to make a test of functionality. 
Using specific models of relays it’s possible to do the test that use this second coil, the differential relay give a signal at the test coil, this signal creates a flow like that of a 
failure, that the first coil notice and it send at the relay that tripped. 
The choice of the toroidal current transformer depends by the dimensions of the conductors or the bar that must pass inside. It’s possible to install a current transformer without 
to disconnect the cable of wiring, using the models with the core that can be opened./ 

Przekładniki pr

ą

dowe CTE… s

ą

 zbudowane na rdzeniu z blach stalowych o dobrej przenikalno

ś

ci magnetycznej umo

ż

liwiaj

ą

cej odczyt pr

ą

dów o bardzo małej 

warto

ś

ci. Na rdzeniu nawini

ę

te sa dwa uzwojenia, jedno dla odczytu sygnału pochodz

ą

cego od pr

ą

du ró

ż

nicowego za

ś

 drugie umo

ż

liwiaj

ą

ce test funkcjonalny. 

Wykorzystuj

ą

c specyficzne modele przeka

ź

ników ró

ż

nicowopr

ą

dowych mo

ż

liwe jest wykonanie testu, wykorzystuj

ą

cego drugie uzwojenie, poprzez które przeka

ź

nik ró

ż

nicowy 

podaje sygnał na uzwojenie testowe, który to sygnał tworzy przepływ pr

ą

du podobnego do tego jaki powstaje przy wykryciu rzeczywistego upływu w sieci. Sygnał ten zostaje 

wykryty przez uzwojenie pomiarowe i powoduje zadziałanie przeka

ź

nika.  

Wybór przekładnika toroidalnego zale

ż

y od rozmiarów przewodu lub szyn które musz

ą

 przechodzi

ć

 przez jego otwór. Mo

ż

liwe jest zainstalowanie przekładnika pr

ą

dowego bez 

potrzeby rozł

ą

czania kabla głównego, z wykorzystaniem wykona

ń

 z dzielonym rdzeniem. 

 

TYPES/ TYPY 

Toroidal currant transformer/ Toroidalny przekładnik pr

ą

dowy  

Type/typ 

code No/ nr kod. 

Description/opis 

weight [g] 

packing [pcs] 

CTE-35 

004671609 

Current transformer/

przekładnik pr

ą

dowy

 

200 

CTE-60 

004671610 

Current transformer/

przekładnik pr

ą

dowy

 

260 

CTE-80 

004671611 

Current transformer/

przekładnik pr

ą

dowy

 

400 

CTE-110 

004671612 

Current transformer/

przekładnik pr

ą

dowy

 

450 

CTE-160 

004671613 

Current transformer/

przekładnik pr

ą

dowy

 

980 

CTE-210 

004671614 

Current transformer/

przekładnik pr

ą

dowy

 

1200 

 

INSTALATION/ INSTALACJA 

The toroidal current transformers must be installed in the way that all the conductors of the line (phase and neutral if distribute) pass inside. The earth conductors, 

instead, must not pass inside. The direction of the passage must be the same for all the conductors and in the application where the current transformer in parallel are not used, 
it’s not necessary to respect the sense of the introduction (P1). From the 1 (S1) and 2 (S2) terminals must be taken the signal of output to connect ad the differential relay for 
the measure, the 3-4 terminals must be connected at the output test of the relay that have this option; at contrary they must be disconnected.  

It’s better to use conductor twisted or shielded for this connection, and possibly far from cable of power. The minimum section of the wire of the connection should 
have a maximum resistance of 3 

; approximately it’s possible to take a section of 0,5 mm

2

 max 20 meters and of 2,5 mm

2

 max 100 meters. 

The fixing of the current transformer can be done on the bottom of the electric panel, on section or on cable. For the current transformer  tha can be opened it’s necessary to 
verify that the contact surface of the two half-core is cleaned, the correct closing of the bolts and the connection of the cable that join the two parts. If present, the shield, must 
be connected at earth after toroidal current transformer or if the shield pass inside, the connection at earth of the shield must pass another time in opposite sense inside the 
toroidal current transformer (see the figure). In presence of specific over current, at the starting of big motor, the transformer are turned on, that can cause the tripping untimely 
of differential relays, it’s necessary to observe the following indications: 

to install a current transformer on a stretch rectilinear cable, to centre the positioning of the 

cable inside the toroidal current transformer, to use current transformer bigger than the necessary (also 2 time of diameter of cables)./ 

Przekładniki toroidalne musz

ą

 by

ć

 instalowane w taki sposób aby obejmowały wszystkie przewody linii (fazowe   i neutralny – je

ś

li wyst

ę

puje). Przewody uziemiaj

ą

ce 

z kolei nie mog

ą

 przechodzi

ć

 przez otwór przekładnika. Kierunek przej

ś

cia musi by

ć

 zgodny dla wszystkich przewodów za

ś

 w aplikacjach gdzie nie wyst

ę

puj

ą

 równolegle 

podł

ą

czone przekładniki pr

ą

dowe, nie jest konieczne zachowanie kierunku wprowadzenia (P1). 

Z zacisków 1 (S1) i 2 (S2) musi by

ć

 pobrany sygnał wyj

ś

ciowy do podł

ą

czenia na wej

ś

cie pomiarowe przeka

ź

nika ró

ż

nicowopr

ą

dowego, natomiast zaciski 3-4 musz

ą

 by

ć

 

podł

ą

czone na wyj

ś

cie testowe przeka

ź

nika, o ile jest on wyposa

ż

ony w tak

ą

 opcj

ę

. W przeciwnym wypadku zaciski te nale

ż

y pozostawi

ć

 niepodł

ą

czone.   

Zaleca si

ę

 stosowanie skr

ę

tki przewodowej lub przewodu ekranowanego oraz prowadzenie go z dala od przewodów silnopr

ą

dowych. Minimalny przekrój powinien 

zapewnia

ć

 rezystancje przewodu nie wi

ę

ksz

ą

 ni

ż

 3 

; co przy przekroju 0,5 mm

2

 daje max 20 metrów za

ś

 przy przekroju  2,5 mm

2

 max 100 metrów. 

Je

ś

li wyst

ę

puje ekran, musi on by

ć

 poł

ą

czony z przewodem uziemiaj

ą

cym za przekładnikiem  a je

ś

li przechodzi on przez otwór przekładnika, poł

ą

czenie uziemiaj

ą

ce musi 

przej

ść

 powrotnie przez otwór (patrz rysunek). W niektórych sytuacjach du

ż

ych przeci

ąż

e

ń

, np. przy rozruchu du

ż

ych silników, zał

ą

czaniu transformatorów itp. co mo

ż

spowodowa

ć

 przedwczesne zadziałanie przeka

ź

nika ró

ż

nicowego, nale

ż

y przestrzega

ć

 nast

ę

puj

ą

cych wskazówek: 

zainstalowa

ć

 przekładnik pr

ą

dowy na prostoliniowym odcinku kabla i wycentrowa

ć

 kabel wewn

ą

trz przekładnika pr

ą

dowego lub zastosowa

ć

 przekładnik wi

ę

kszy 

ni

ż

 jest to konieczne (nawet 2 razy wi

ę

kszy od 

ś

rednicy kabla). 