ETC Unison Echo E-OCC Installation Manual Download Page 1

ETC Installation Guide

Unison Echo

®

 Occupancy Sensor

Echo Occupancy/Vacancy Sensor

 Page 1 of 12

Electronic Theatre Controls, Inc.

Corporate Headquarters

 

 Middleton, Wisconsin, USA 

 Tel +608 831 4116

 

 Service: (Americas) 

servi[email protected]

 

London, UK

 

 Tel +44 (0)20 8896 1000 

 Service: (UK)

 

se[email protected]

 

Rome, IT 

 Tel +39 (06) 32 111 683 



Service: (UK)

 

service@etceurope.com

 

Holzkirchen, DE

 

 Tel +49 (80 24) 47 00-0



Service: (DE)

 

tech[email protected]

 

Hong Kong 

 Tel +852 2799 1220 



Service: (Asia)

 

[email protected]

Web:

 

www.etcconnect.com

 

 Copyright © 2016 ETC. All Rights Reserved. 

Product information and specifications subject to change. 



ETC intends this document to be provided in its entirety.

7186M2180

 

 Rev C 



Released 2016-02 

Overview

The Echo Occupancy/Vacancy Sensor is a ceiling mounted sensor that utilizes 
passive infrared (PIR) technology, providing reliable vacancy and occupancy 
detection for lighting control. The sensor provides automatic configuration of 
vacancy (auto-off) or occupancy (auto-on/off) functionality based on other 
connected control stations. When manual control stations are present, the 
sensor will only perform vacancy actions.

Each sensor is available in white or black finish. Lens masks are provided to 
allow customized occupancy detection fields as required by each installation.

Custom Configuration

This document guides you through the installation and local configuration of 
the Echo Occupancy/Vacancy Sensor. For more detailed information about 
custom configuration options available for the Echo Occupancy/Vacancy 
Sensor using EchoAccess, reference the EchoAccess Mobile App integrated 
help system.

Note:

To use the configuration settings applied using EchoAccess, DIP switch 
2 must be enabled. Reference 

DIP Switch Settings

 on 

page 7

.

The Occupancy/Vacancy Sensor provides 360 
degree coverage of the installed location and is 
available in three models:

E-OCC-SR

- Occupancy/Vacancy Sensor with 

small room lens covers 450 sq. ft. at 
8 ft./ 800 sq. ft. at 10 ft.

E-OCC

 - Occupancy/Vacancy Sensor with 

standard room lens covers 1,800 sq. ft. at 
8 ft./ 3,000 sq. ft. at 10 ft.

E-OCC-HC

 - Occupancy/Vacancy Sensor 

with high ceiling lens covers 300 sq. ft. at 
10 ft./ 7,000 sq. ft. at 40 ft.

Summary of Contents for Unison Echo E-OCC

Page 1: ...off functionality based on other connected control stations When manual control stations are present the sensor will only perform vacancy actions Each sensor is available in white or black finish Len...

Page 2: ...nstall the sensor within eight feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways glass partitions or...

Page 3: ...box finished ceiling or soft ceiling tile Determine the installation method and follow the detailed instructions See Junction Box Installation on page 4 See Soft Ceiling Tile Installation on page 5 Se...

Page 4: ...the mounting plate Step 4 Secure the mounting plate to the junction box using the screws provided both short and long screws are provided for convenience Step 5 Strip each wire 5 16 8mm and terminate...

Page 5: ...ot provided to make the terminations If you are not continuing the data run proceed to Step 3 a Strip each wire to the appropriate length depending on the wire nut or other termination used wire nuts...

Page 6: ...terminal b Terminate the black incoming wire to the data terminal c Terminate the green yellow ground wire to the labeled ground terminal Sensor Configuration The Echo Occupancy Vacancy Sensor partic...

Page 7: ...ings are ignored Instead the settings made by the EchoAccess Mobile App for Vacancy Timeout Enable PIR LED and Occupancy actions are used DIP Switch 3 4 DIP switch 3 4 set the Vacancy Timeout to 5 15...

Page 8: ...hes MODE button and LED and the Auxiliary button See Preset below and Vacancy Timeout on page 9 for local configuration instructions Preset The MODE button and LED found on the rear panel of the senso...

Page 9: ...release the MODE button to save the current setting The Mode Sensor count LED turns off and the A button again blinks out the saved preset index Step 4 Attach the sensor to the mounting plate by align...

Page 10: ...curs during the grace period Lens Masking Lens masks are provided in the packaging for your convenience used to block a section of the lens from detecting occupancy PIR Detection The PIR detection aut...

Page 11: ...alk Test feature at the sensor A green LED will begin to flash indicating Walk Test is enabled and the vacancy no vacancy occupancy timer will be shortened to 10 seconds Step 3 Move throughout the spa...

Page 12: ...ft 6 1m 20ft 6 1m 20ft 9 1m 30ft 9 1m 30ft 12 2m 40ft 12 2m 40ft 0 12 2m 40ft 9 1m 30ft 6 1m 20ft Small Room side view 0 0 1 5m 5ft 1 5m 5ft 3 0m 10ft 3 0m 10ft 4 6m 15ft 4 6m 15ft 6 1m 20ft 6 1m 20ft...