Overview

The Echo Contact and Demand Response Interfaces are DIN rail mounted
devices that are available in the following configurations:

Input Interface - accepts four momentary or maintained closures to
trigger control actions within an Echo control system.

Demand Response Interface - accepts four maintained closures to
trigger demand response within an Echo control system.

Output Interface - provides four normally open or normally closed
output relays controlled by actions in the Echo control system.

Contact Input

Demand Response

Contact Output

Custom Configuration

This document guides you through the installation and basic local
configuration settings of the interface devices. Information about custom
configuration options available using EchoAccess are available in the app
integrated help system.

Note:

To use the configuration settings applied using EchoAccess,

the unit must be placed in Custom configuration mode. See

Set

Configuration Mode on page 5

.

Accessory Kits

ETC offers a Low Voltage DIN rail Cover Kit (part number 7186A1218) that
allows installation of the Contact and Demand Response Interfaces to a
10.16 cm (4 in) junction box (provided by others). Contact ETC for ordering
details.

Summary of Contents for Echo Contact Input

Page 1: ...actions within an Echo control system Demand Response Interface accepts four maintained closures to trigger demand response within an Echo control system Output Interface provides four normally open...

Page 2: ...of wires data and data for both data and power ETC recommends using Belden 8471 or approved equal Class 2 wire The total combined length of an EchoConnect wire run using Belden 8471 or equal may not...

Page 3: ...O normally closed N C and common COM for connection of output relays Terminals accept 0 2 mm 2 4 mm 2 24 12 AWG wire Each output includes a corresponding on board LED to indicate the normally open sta...

Page 4: ...Wet Contact Input For a wet contact input into the Contact Input Interface you must terminate to both the In and the negative terminal of the 24 VDC auxiliary input The V out terminal will not be use...

Page 5: ...achine driven applications ETC recommends a minimum of 500 ms between any input changes to ensure transitions are reliably applied Demand Response Interface Activates Demand Response affecting up four...

Page 6: ...owing default behaviors until changed using the EchoAccess App Input Interface Inputs control Presets 1 4 respectively using maintained input mode where closing the contact activates the preset openin...

Page 7: ...spaces that will be controlled A value higher than 13 will result in control of only Spaces 14 15 and 16 2 Set the Address Zone For a Contact Input Interface set the Address 1 through 16 available whi...

Page 8: ...cycling power and restoring the device to normal operation Reset to Factory Defaults Using a ball point pen press the Reset button for ten seconds to reset the interface to factory defaults The power...

Reviews: