ETC DataTrack Planning And Installation Manual Download Page 1

Part Number: 7066M2100 Rev: D

Released: 2019-07

DataTrack and

DataTrack Backbone System

Planning and Installation Manual

Summary of Contents for DataTrack

Page 1: ...Part Number 7066M2100 Rev D Released 2019 07 DataTrack and DataTrack Backbone System Planning and Installation Manual ...

Page 2: ...rademarks and patents go to etcconnect com ip All other trademarks both marked and not marked are the property of their respective owners ETC intends this document whether printed or electronic to be provided in its entirety ...

Page 3: ...ad Capacity 8 DMX Data Path 10 Chapter 2 Installation 13 Cutting Track 13 Installation Methods 14 Surface Mounting DataTrack Only 14 Suspension Mounting DataTrack only 15 Threaded Rod Mounting DataTrack Backbone 15 End of Track 15 Installing End Feeds 16 Installing Mid Feeds 19 Installing Current Limiters DataTrack only 23 Installing Current Limiting Feed Connector on a J Box 24 Installing Current...

Page 4: ...on Manual Chapter 3 Troubleshooting 28 Loss of Power 28 Data Issues 29 Appendix A Parts and Accessories 31 Two circuit Accessories 31 DataTrack Mounting Accessories 42 Current Limiters 45 DataTrack Backbone Accessories 48 Appendix B Reconfiguring DMX Data Lines 61 ...

Page 5: ...p and 12 amp current limiting breakers located directly at the track Up to 22 pounds per foot 30 kilograms per meter of load capacity when properly supported Two year warranty White black powder coated and silver anodized finishes 4 ft 8 ft and 12 ft 1 21 m 2 43 m and 3 65 m sections that can be field cut to custom lengths as required Easy surface mounting using pre punched holes positioned every ...

Page 6: ...ndependent neutral for individual control and a common ground Maximum Feed 2 x 20A branch circuits Maximum Load 2 x 16A 2 x 1920W at 120V Maximum Load for EUTRAC systems 2 x 16A 2 x 4600W at 230V Supply Wiring 12 AWG 2 5 mm2 feed wires The DataTrack Backbone fixture adapter has a load capacity of 300W 120V supply or 600W 230V supply for EUTRAC systems Document Conventions This document uses the fo...

Page 7: ...Always disconnect electrical power before adding to or changing the configuration of the track Only install lighting track fixtures and fittings in DataTrack Per NEC article 410 151 A lighting track fittings shall not be equipped with general purpose receptacles Do not attempt to connect power tools extension cords appliances or similar devices to the track CAUTION For indoor use only Do not use i...

Page 8: ... When calling for support please try to have the following information available Product model Other components in your system luminaires connected control source etc Americas United Kingdom ETC Inc ETC Ltd Technical Services Department Technical Services Department 3031 Pleasant View Road 26 28 Victoria Industrial Estate Middleton WI 53562 Victoria Road 800 775 4382 USA toll free London W3 6UU En...

Page 9: ...k This is important to keep in mind when purchasing couplers ground left versus ground right ground inside versus ground outside All product references to ground orientation also refer to data bus orientation as illustrated below See Parts and Accessories on page 31 for a list of available DataTrack and DataTrack Backbone parts Figure 1 Coupler and track connections Planning the Installation Consi...

Page 10: ...ata connection of the coupler must mate with the data connection of the track This is important to keep in mind when choosing couplers ground left versus ground right ground inside versus ground outside CAUTION These figures show a continuous ground path within the track system If any of the couplers shown in these examples were replaced with an outside ground model the ground path would be broken...

Page 11: ...ave the ground connectors on the left side of the T instead of the right as shown they will not align with the connectors in the X couplers T coupler ground inside left Ground Feed Path L coupler ground inside L coupler ground inside L coupler ground inside L coupler ground inside X coupler T coupler ground inside right T coupler ground inside left T coupler ground inside right T coupler ground in...

Page 12: ...spended load capacity DataTrack Backbone When using track mounted fixtures on DataTrack Backbone the load capacity is the same as DataTrack Maximum load 22 lb 10 kg with fixtures mounted on 12 in 30 5 cm centers Maximum distance of 10 ft 3 m between structural mounting points for DataTrack Backbone Figure 6 DataTrack Backbone suspended load capacity for track fixtures Distance between structural m...

Page 13: ...center 2 ft 6 m 300 lb 136 kg 100 lb 45 kg 0 05 in 0 1 cm 3 ft 9 m 300 lb 136 kg 100 lb 45 kg 0 05 in 0 1 cm 4 ft 1 2 m 300 lb 136 kg 100 lb 45 kg 0 075 in 0 2 cm 5 ft 1 5 m 280 lb 127 kg 100 lb 45 kg 0 125 in 0 3 cm 6 ft 1 8 m 260 lb 118 kg 100 lb 45 kg 0 15 in 0 4 cm 7 ft 2 1 m 240 lb 109 kg 75 lb 34 kg 0 175 in 0 4 cm 8 ft 2 4 m 220 lb 100 kg 50 lb 23 kg 0 2 in 0 5 cm 9 ft 2 7 m 200 lb 91 kg 40...

Page 14: ...nsmission will become unreliable if DMX is not installed according to standard protocols CAUTION ETC recommends laying out the DMX data path for your track configuration BEFORE ordering all track and couplers to ensure that no loops stars or Y s are created that would disrupt data transmission Note The DMX data line is only for low voltage with an approximate value of 50V 2A maximum Note If L coup...

Page 15: ... zone or second DMX input required DMX TERM L coupler ground inside L coupler ground inside L coupler ground inside L coupler ground inside T coupler ground inside right T coupler ground inside left T coupler ground inside left T coupler ground inside right ...

Page 16: ...n as shown See Reconfiguring DMX Data Lines on page 61 for more information T2 D2 D1 D3 T3 T1 T coupler ground inside right T coupler ground inside right T coupler ground inside right T coupler ground inside right T coupler ground inside left L coupler ground inside L coupler ground inside T coupler ground inside left X coupler X coupler L coupler ground inside L coupler ground inside X coupler st...

Page 17: ...e of DataTrack The minimum distance that the bus bar can be cut back from the edge of the track profile is 0 08 in 2 mm The bus bar does not have to be moved out of the track profile Use a file to remove burrs after cutting and clean any metal shavings before installing WARNING RISK OF ELECTRIC SHOCK Cover the ends of DataTrack and DataTrack Backbone with end covers or protective caps CAUTION Befo...

Page 18: ...d load capacity when determining the number of attachment points to the structure Be sure to follow the installation instructions supplied with each component when installing the track system Surface Mounting DataTrack Only Determining the appropriate mounting hardware is the responsibility of the installing contractor Pre punched holes are positioned every 8 in 20 32 cm in the track for surface m...

Page 19: ...used by HVAC operation and other building systems could impact the function of the track system Threaded Rod Mounting DataTrack Backbone DataTrack Backbone provides a standard Unistrut profile on its top surface Use standard Unistrut hardware and threaded rod to mount DataTrack Backbone End of Track The end of the DataTrack must be enclosed with a DataTrack end cap If you are using DataTrack Backb...

Page 20: ...8 1 Prepare the end feeds both the power end feed and the DMX end feed For top feed a Remove the cover screw b Remove the cover c Remove the plug For end feed a Remove the cover screw b Remove the cover c Remove the plug d Install the wire guide to the end feed connector Figure 5 Prepare the end feed Note When installing end feeds be aware that DMX and power cannot be wired into the same end feed ...

Page 21: ...e to the terminals as illustrated and secure the screws Figure 6 Connect the power end feed L1 L1 L2 L2 N2 N2 N1 N1 a b d c Electrical connection for two 20A circuits at 120V AC Maximum load 1920W Fuses 2 x 16A Supply wire 12 AWG 2 5 mm2 recommended Data line maximum voltage 20V Data line maximum current 250mA 120 V 120 V L2 20A 2 1 N1 N2 20A L1 N1 N2 DATA DATA Electrical connection for two 20A ci...

Page 22: ...g and Installation Manual 3 Connect the DMX end feed a Install the wire retainer b Connect data line wires to screws as illustrated to track c Install the cover d Install the cover screw Figure 7 Connect the DMX end feed a Black Red Data line b c d ...

Page 23: ...n a surface mounted track Remove burrs Figure 8 Install the mid feed 2 Mount the mid feed canopy Figure 9 Mount the mid feed canopy Note Due to concerns about DMX performance ETC recommends that you use mid feeds to provide power to the track not DMX Drill hole on top of track where you want to put the adapter to pass through wires 0 59 in 15 mm 0 31 in 7 9 mm 0 55 in 14 mm Slide the canopy so tha...

Page 24: ...ount the track by referring to the instructions provided with the track Figure 10 Feed power lines and mount track 4 Before mounting press in the catch using a screwdriver and remove the cover Figure 11 Press in the catch and remove cover 5 Insert the mid feed into the track at the prepared position Figure 12 Mounting example Catch ...

Page 25: ...dividual circuits and the ground conductor as shown When wiring the track check that the ground conductor green and the neutral conductors white are connected as indicated in Figure 14 and Figure 15 Circuits 1 and 2 can be wired as required Figure 14 Wiring Figure 15 Dismantling and insulation strip lengths 5 pole mains lead Green Power supply line 3 8 in 9 mm 2 1 2 in 65 mm Wire size Minimum 16 A...

Page 26: ...k DataTrack Backbone System Planning and Installation Manual 8 When the wiring is complete a Place the hex head wrench in the cover b Reposition the cover c Click into place Figure 16 Secure the cover a b C click ...

Page 27: ...taTrack Backbone housing 1 Plate Mounting Hole 8 Cover Mounting Screws 2 Rectangular Hole 9 Cover 3 Track Feed Connector 2 10 Track Feed Connector 1 4 Round Knockout 11 Ground Tab 5 Line Terminal Hot 12 Line Terminal Hot 6 Overcurrent Device sold separately 13 Load Terminal 7 Load Terminal 14 Provided Lead Wires Overcurrent device sold separately 5 4 2 1 13 12 10 9 8 14 3 11 6 7 ...

Page 28: ...nter line of plate on ceiling to determine the mounting location of the feed connector 3 Make a hole in the ceiling for the electrical connector in a position that coincides with one of the round knockouts 4 Remove one round knockout where the power is to be passed through Do not remove any other knockouts 5 Push current limiting breakers into plate Breakers ordered separately 6 Attach electrical ...

Page 29: ... 1 terminal N1 of feed connector Clamp wire using screw See Figure 17 Figure 17 End feed wiring 3 Strip Hot 1 supply wire and connect to a 0 25 in 6 35 mm female quick disconnect not supplied Push onto the Line tap clamp on the overcurrent device 4 Connect load from overcurrent device to track feed connector terminal L1 using provided wire See Figure 17 5 Follow the same instructions for Neutral 2...

Page 30: ...ng 3 Measure and strip a new wire not provided and connect N1 terminal Feed Connector 1 to N1 terminal Feed Connector 2 4 Strip Hot 1 supply wire and connect to a 0 25 in 6 35 mm female quick disconnect not supplied Push onto the Line tap clamp on the overcurrent device 5 Connect load from overcurrent device to feed connector terminal L1 using provided wire 6 Measure and strip a new wire not provi...

Page 31: ... power supply connector to the ON position The overcurrent devices will automatically switch to OFF if current ratings are exceeded If overcurrent devices will not remain on Reduce the wattage on the track so the total wattage is less than the wattage specified on the overcurrent devices Turn the overcurrent devices to ON ...

Page 32: ...onfigurations other than straight runs Check all connections of track If connections check is good check components for proper ground inside outside If parts are incorrect change parts for the correct current flow Check live end feeds and couplers T L etc for proper ground path Lights flickering Check bulb for proper installation Turn switch off remove bulb inspect end for any oxidation clean off ...

Page 33: ... Loss of data on suspended track cable or pendant Check that the joined track sections have been joined by pendant clips Track sections must be joined by pendant clip Use 2 in 5 08 cm independent clips Use 4 in 10 16 cm clips where track meets Check for proper number of suspension points based on the load applied to the track see Suspended Load Capacity on page 8 If the number of suspension points...

Page 34: ...s Hand start one screw and then the other Finish securing screws with screwdriver Make sure wires are not interfering with cover Remove cover Tuck any loose wires out of the way when closing the cover Never interfere with wire connections No data through current limiter Check overcurrent device on limiter If tripped reset overcurrent device Check that end feeds are correct and able to transfer dat...

Page 35: ...e related DataTrack accessories Feeds power or data into the DataTrack system Mounts to the end of a linear section of DataTrack Top feed or end feed DataTrack Ground Color Model Number Right Black EDTREF GR White EDTREF GR 1 Silver EDTREF GR 5 Left Black EDTREF GL White EDTREF GL 1 Silver EDTREF GL5 Related Accessories DataTrack Backbone End Feed Housing Ground Color Model Number Both Black DTB E...

Page 36: ...tem Mounts anywhere inside the track Top feed only DataTrack Color Model Number Black EDTRMF White EDTRMF 1 Silver EDTRMF 5 Related Accessories DataTrack Backbone Mid Feed Housing Color Model Number Black DTB MF BLK White DTB MF WHT Silver DTB MF SLV Custom DTB MF CST 4 57 in 116 0 mm 1 36 in 34 5 mm 0 29 in 7 3 mm ...

Page 37: ...oupler Splices two pieces of DataTrack in line Supports power and or data feed Top feed only DataTrack Color Model Number Black EDTRIC White EDTRIC 1 Silver EDTRIC 5 4 72 in 120 0 mm 1 37 in 34 9 mm 1 40 in 35 6 mm 0 42 in 10 6 mm ...

Page 38: ...del Number Inside Black EDTRLC GI White EDTRLC GI 1 Silver EDTRLC GI 5 Outside Black EDTRLC GO White EDTRLC GO 1 Silver EDTRLC GO 5 Related Accessories DataTrack Backbone L coupler Housing Pull Box Color Model Number Yes Black DTB LF BLK White DTB LF WHT Silver DTB LF SLV Custom DTB LF CST No Black DTB L BLK White DTB L WHT Silver DTB L SLV Custom DTB L CST 3 02 in 76 8 mm 1 37 in 34 9 mm 1 66 in ...

Page 39: ...TC GIL White EDTRTC GIL 1 Silver EDTRTC GIL 5 Outside Right Black EDTRTC GOR White EDTRTC GOR 1 Silver EDTRTC GOR 5 Outside Left Black EDTRTC GOL White EDTRTC GOL 1 Silver EDTRTC GOL 5 Related Accessories DataTrack Backbone T coupler Housing Pull Box Color Model Number Yes Black DTB TF BLK White DTB TF WHT Silver DTB TF SLV Custom DTB TF CST No Black DTB T BLK White DTB T WHT Silver DTB T SLV Cust...

Page 40: ...terior corners field configurable DataTrack Color Model Number Black EDTRXC White EDTRXC 1 Silver EDTRXC 5 Related Accessories DataTrack Backbone X coupler Housing Pull Box Color Model Number Yes Black DTB XF BLK White DTB XF WHT Silver DTB XF SLV Custom DTB XF CST No Black DTB X BLK White DTB X WHT Silver DTB X SLV Custom DTB X CST 1 66 in 42 2 mm 1 37 in 34 9 mm 4 69 in 119 0 mm 1 66 in 42 2 mm ...

Page 41: ...power and or data feed Top feed only Can be used to connect DataTrack in a DataTrack Backbone installation but will not be supported within the DataTrack Backbone DataTrack Color Model Number Black EDTRFC White EDTRFC 1 Silver EDTRFC 5 2 81 in 71 3 mm 1 37 in 34 9 mm 3 28 in 83 3 mm 0 42 in 10 6 mm 1 40 in 35 6 mm ...

Page 42: ...s of DataTrack in line Requires 4 in 10 16 cm pendant clip to stabilize joint see Four inch Pendant Clip on page 42 DataTrack Color Model Number Black EDTRSC White EDTRSC 1 Silver EDTRSC 5 Related Accessories DataTrack Backbone Straight Locking Joint Color Model Number N A DTB LJ 2 64 in 67 0 mm 0 42 in 10 6 mm 1 42 in 36 1 mm ...

Page 43: ...ckbone end cap may also be used for cosmetic purposes see End Cap on page 57 DataTrack Color Model Number Black EDTREC White EDTREC 1 Silver EDTREC 5 Related Accessories DataTrack Backbone End Cap Color Model Number Black DTB EC BLK White DTB EC WHT Silver DTB EC SLV Custom DTB EC CST 0 53 in 13 5 mm 0 11 in 2 8 mm 0 49 in 12 3 mm 1 43 in 36 2 mm 1 26 in 32 0 mm ...

Page 44: ...ng surface created for feed wires from junction boxes Not for use with DataTrack Backbone DataTrack Color Model Number Black EDTRCC White EDTRCC 1 Silver EDTRCC 5 4 46 in 113 3 mm 0 37 in 9 5 mm 2 81 in 71 3 mm 1 39 in 35 3 mm 1 52 in 38 5 mm 4 46 in 113 3 mm 0 94 in 23 8 mm DataTrack Color Model Number Black EDTRMCC White EDTRMCC 1 Silver EDTRMCC 5 4 38 in 111 3 mm 4 61 in 117 0 mm 1 24 in 31 6 m...

Page 45: ... Terminates DMX data run One terminator required per data feed positioned at the end of the DMX data run Multiple data feeds and terminations may be required in a single DataTrack system DataTrack Color Model Number Black EDTRUA White EDTRUA 1 1 70 in 43 2 mm 0 65 in 16 5 mm 1 06 in 26 9 mm DataTrack Color Model Number Black EDTRDMXT White EDTRDMXT 1 Silver EDTRDMXT 5 1 39 in 35 2 mm 3 79 in 96 2 ...

Page 46: ...ck Backbone DataTrack Color Model Number Black EDTR2PC White EDTR2PC 1 Silver EDTR2PC 5 2 00 in 50 8 mm 1 40 in 35 6 mm 1 40 in 35 6 mm 0 73 in 18 5 mm Required for joints of pendant mounted tracks For pendant mounting with 1 16 in 1 6 mm aircraft cables threaded 3 8 in IPS or 5 8 in threaded rod Accessory kits with 48 in 1 22 m aircraft cables are available Not for use with DataTrack Backbone Dat...

Page 47: ...The diameter of the hole for running cable through the support feed canopy kit is 7 8 in 22 22 mm Not for use with DataTrack Backbone For attaching top of aircraft cable to building in support locations with no power and or data feed Pendant cable kit includes 4 ft length of 1 16 in 1 6 mm aircraft cable Canopy Cable gripper Coupler Not for use with DataTrack Backbone 5 00 in 127 0 mm DataTrack Co...

Page 48: ...n Manual T bar Mounting Clip For use with 15 16 in 23 81 mm T grid system Support independent of ceiling Kit from ETC includes mounting nut Not for use with DataTrack Backbone DataTrack Color Model Number White EDTRTB 0 75 in 19 1 mm 3 51 in 89 1 mm 1 35 in 34 3 mm ...

Page 49: ...or options Can be used in a DataTrack Backbone installation but will not be supported within the DataTrack Backbone Title 24 Compliant DataTrack Ground Color Model Number Right Black EDTREFCL GR White EDTREFCL GR 1 Silver EDTREFCL GR 5 Left Black EDTREFCL GL White EDTREFCL GL 1 Silver EDTREFCL GL 5 Right Title 24 compliant Black EDTREFCLT24 GR White EDTREFCLT24 GR 1 Silver EDTREFCLT24 GR 5 Left Ti...

Page 50: ...e 47 for options Can be used in a DataTrack Backbone installation but will not be supported within the DataTrack Backbone Title 24 Compliant DataTrack Color Model Number Black EDTRICCL White EDTRICCL 1 Silver EDTRICCL 5 Black Title 24 Compliant EDTRICCLT24 White Title 24 Compliant EDTRICCLT24 1 Silver Title 24 Compliant EDTRICCLT24 5 5 64 in 143 2 mm 1 37 in 34 9 mm 1 73 in 44 0 mm 5 64 in 143 2 m...

Page 51: ...t devices One per circuit DataTrack Amp Color Model Number 3A Black EDTRCL 3A White EDTRCL 3A 1 5A Black EDTRCL 5A White EDTRCL 5A 1 8A Black EDTRCL 8A White EDTRCL 8A 1 12A Black EDTRCL 12A White EDTRCL 12A 1 0 38 in 9 5 mm 1 56 in 39 7 mm 1 55 in 39 3 mm 0 78 in 19 8 mm ...

Page 52: ... 31 DataTrack Backbone Ground Color Model Number Both Black DTB EF BLK White DTB EF WHT Silver DTB EF SLV Custom DTB EF CST Related Accessories DataTrack End Feed Ground Color Model Number Right Black EDTREF GR White EDTREF GR 1 Silver EDTREF GR 5 Left Black EDTREF GL White EDTREF GL 1 Silver EDTREF GL5 3 in 76 2 mm 2 05 in 52 mm 3 28 in 83 4 mm 1 71 in 43 5 mm ...

Page 53: ...taTrack Backbone Color Model Number Black DTB MF BLK White DTB MF WHT Silver DTB MF SLV Custom DTB MF CST Related Accessories DataTrack Mid Feed Color Model Number Black EDTRMF White EDTRMF 1 Silver EDTRMF 5 11 81 in 5 34 in 135 7 mm 79 in 20 mm 4 66 in 118 4 mm 3 46 in 88 mm 1 65 in 42 mm ...

Page 54: ...or Model Number Black DTB L BLK White DTB L WHT Silver DTB L SLV Custom DTB L CST Related Accessories DataTrack L coupler Ground Color Model Number Inside Black EDTRLC GI White EDTRLC GI 1 Silver EDTRLC GI 5 Outside Black EDTRLC GO White EDTRLC GO 1 Silver EDTRLC GO 5 6 76 in 171 8 mm 3 46 in 88 mm 5 05 in 128 2 mm 1 71 in 43 5 mm 3 23 in 82 1 mm 79 in 20 mm ...

Page 55: ...ataTrack Backbone Color Model Number Black DTB LF BLK White DTB LF WHT Silver DTB LF SLV Custom DTB LF CST Related Accessories DataTrack L coupler Ground Color Model Number Inside Black EDTRLC GI White EDTRLC GI 1 Silver EDTRLC GI 5 Outside Black EDTRLC GO White EDTRLC GO 1 Silver EDTRLC GO 5 6 76 in 171 8 mm 3 46 in 88 mm 5 05 in 128 2 mm 5 46 in 138 8 mm 1 71 in 43 5 mm 79 in 20 mm ...

Page 56: ...ated Accessories DataTrack T coupler Ground Color Model Number Inside Right Black EDTRTC GIR White EDTRTC GIR 1 Silver EDTRTC GIR 5 Inside Left Black EDTRTC GIL White EDTRTC GIL 1 Silver EDTRTC GIL 5 Outside Right Black EDTRTC GOR White EDTRTC GOR 1 Silver EDTRTC GOR 5 Outside Left Black EDTRTC GOL White EDTRTC GOL 1 Silver EDTRTC GOL 5 3 46 in 88 mm 11 81 in 300 mm 5 05 in 128 2 mm 5 05 in 128 2 ...

Page 57: ...LV Custom DTB TF CST Related Accessories DataTrack T coupler Ground Color Model Number Inside Right Black EDTRTC GIR White EDTRTC GIR 1 Silver EDTRTC GIR 5 Inside Left Black EDTRTC GIL White EDTRTC GIL 1 Silver EDTRTC GIL 5 Outside Right Black EDTRTC GOR White EDTRTC GOR 1 Silver EDTRTC GOR 5 Outside Left Black EDTRTC GOL White EDTRTC GOL 1 Silver EDTRTC GOL 5 3 46 in 88 mm 11 81 in 300 mm 5 05 in...

Page 58: ... coupler on page 36 DataTrack Backbone Color Model Number Black DTB X BLK White DTB X WHT Silver DTB X SLV Custom DTB X CST Related Accessories DataTrack X coupler Color Model Number Black EDTRXC White EDTRXC 1 Silver EDTRXC 5 3 46 in 88 mm 11 81 in 300 mm 5 05 in 128 2 mm 5 05 in 128 2 mm 1 71 in 43 5 mm 79 in 20 mm ...

Page 59: ... allows space for a service loop DataTrack Backbone Color Model Number Black DTB XF BLK White DTB XF WHT Silver DTB XF SLV Custom DTB XF CST Related Accessories DataTrack X coupler Color Model Number Black EDTRXC White EDTRXC 1 Silver EDTRXC 5 3 46 in 88 mm 11 81 in 300 mm 5 05 in 128 2 mm 5 05 in 128 2 mm 2 20 in 55 8 mm 1 71 in 43 5 mm 79 in 20 mm ...

Page 60: ...the track is joined by an electrical straight coupler see Electrical Straight Coupler on page 38 DataTrack Backbone Color Model Number N A DTB LJ Related Accessories DataTrack Electrical Straight Coupler Color Model Number Black EDTRSC White EDTRSC 1 Silver EDTRSC 5 10 in 254 mm 2 05 in 52 mm 1 37 in 34 9 mm 1 71 in 43 5 mm 0 5 in 12 7 mm ...

Page 61: ...d cap DataTrack Backbone end cap does not replace DataTrack end cap see End Cap on page 39 DataTrack Backbone Color Model Number Black DTB EC BLK White DTB EC WHT Silver DTB EC SLV Custom DTB EC CST Related Accessories DataTrack End Cap Color Model Number Black EDTREC White EDTREC 1 Silver EDTREC 5 1 72 in 43 7 mm 3 33 in 84 5 mm 0 77 in 19 5 mm ...

Page 62: ...ut bolt to secure hanger to DataTrack Backbone Combination of steel and nylon washers provides both the secure mounting of the fixture yoke to the hanger and the ability to hand focus the fixture DataTrack Backbone Color Model Number Black DTB FH BLK White DTB FH WHT Silver DTB FH SLV Custom DTB FH CST 7 05 in 179 mm 2 18 in 55 4 mm 5 25 in 133 4 mm 1 81 in 46 mm 1 5 in 38 1 mm ...

Page 63: ...cure hanger to DataTrack Backbone 8 mm Allen wrench required for installation Combination of steel and nylon washers provides both the secure mounting of the fixture yoke to the hanger and the ability to hand focus the fixture DataTrack Backbone Color Model Number Black DTB FHEM BLK White DTB FHEM WHT Silver DTB FHEM SLV Custom DTB FHEM CST 6 55 in 166 3 mm 2 18 in 55 4 mm 5 25 in 133 4 mm 1 5 in ...

Page 64: ...or Emergency Lighting on page 59 Includes a blanking plug part number J1648 for fixtures that automatically terminate DMX to ensure that the DMX signal continues along the DataTrack data bus DataTrack Backbone Connector Color Model Number PowerCON connector Black DTB PTP BLK White DTB PTP WHT Silver DTB PTP SLV 1 72 in 43 6 mm 1 37 in 34 9 mm 1 2 in 30 5 mm 1 26 in 31 9 mm 1 37 in 34 9 mm 3 12 in ...

Page 65: ...applies to T couplers too 1 Using a Phillips head screwdriver remove the screws that secure the cover to the coupler 2 Using a flat blade screwdriver loosen the two screws securing the red and black data wires Figure 1 Original wire connection 3 Gently pull the wires from the connector and out from under the black bridge restraint Be careful not to remove the clear shielding 4 Repeat steps 2 and 3...

Page 66: ... locations 6 Insert the red and black wires into their new location Tighten the wire retaining screws Gently pull on the wires to verify that they are properly connected Figure 2 New wire connection 7 Repeat steps 5 and 6 for all remaining connections 8 Replace the coupler cover and secure in place New Wire Connection Data In Data Out ...

Page 67: ...Reconfiguring DMX Data Lines 63 ...

Page 68: ... 852 2799 1220 Paris FR 33 1 4243 3535 Web etcconnect com Support support etcconnect com Contact etcconnect com contactETC 2019 Electronic Theatre Controls Inc Trademark and patent info etcconnect com ip Product information and specifications subject to change ETC intends this document to be provided in its entirety 7066M2100 Rev D Released 2019 07 ...