74
www.eta.co.at
[Heating pipeline] function block
ETAtouch controller
5.11
[Heating pipeline] function block
Overview of heating pipeline
A heating pipeline is defined as a connection between
a heat producer and a consumer with an additional
pump and optional mixing valve.
Example: Boiler and consumer are in different and
widely separated buildings.
The heat is supplied to the connected consumers
(buffer, heating circuits, hot water tank, etc.) via the
heating pipeline with the heating pipeline pump.
Fig. 5-82: Heating pipeline with mixer
1
Operating condition and information.
A description of the operating conditions can be
found in the integrated Help menu by pressing the
button.
2
Producer for the heating pipeline.
Currently the heat producer provides a 77 °C flow
temperature in the pipeline.
3
Pipeline mixer
4
Pipeline pump
5
Heating pipeline consumers
Currently, the consumers are charged at a flow
temperature of 47 °C.
To protect the consumers, an antifreeze function
is available in the pipeline pump control system.
If the outside temperature drops below the set frost
protection limit (factory set at -20 °C), the remote pump
remains in operation until the outdoor temperature is at
least 2 °C higher than the set temperature [Frost pro-
tection].
Transmission line as heat transfer station
This function block can also be used to control a heat
transfer station in a local heating network. This
function block is then the heat producer for the
connected consumers such as heating circuits,
buffers, hot water tanks, etc.
Fig. 5-83: Transmission line as heat transfer station
1
Operating condition and information.
A description of the operating conditions can be
found in the integrated Help menu by pressing the
button.
2
Heat transfer station heat exchanger
3
Heating pipeline pump
4
Heat transfer station consumers.
Currently, the consumers are charged at a flow
temperature of 77 °C.
5
On/Off switch for the heat transfer station
= switched on
= switched off
If the heat transfer station is turned on (
), then
the connected consumers can be supplied with heat.
Once the heat is delivered to the consumer, a yellow
line appears beside the flow temperature and the
symbol of the consumer in the overview.
Summary of Contents for 13180LP-T
Page 1: ...2018 05 24 EN 0000000313 V 005 3 43 0 3308 93222 001 Pellet boiler 180 220 kW Operation ...
Page 29: ...ETAtouch controller Getting to know the control system 29 ...
Page 39: ...ETAtouch controller BufferFlex function block 39 ...
Page 47: ...ETAtouch controller Buffer function block 47 ...
Page 51: ...ETAtouch controller Hot water tank function block 51 ...
Page 55: ...ETAtouch controller Fresh water module function block 55 ...
Page 69: ...ETAtouch controller Solar function block 69 ...
Page 87: ......
Page 88: ...www eta co at www eta co at downloads DOWNLOAD ...