3 Installation
page 21
ELC X-Series-V1.5-06.18-GB
subject to technical alterations
3.2.13
X805 and X806: Control cables
Fig. 16 on page 24 shows the interconnection of X805 and X806. Comments on the wiring are
given in the following tables.
X806:
Connector pin assignment:
Connection torque:
min. 0.22 Nm
max. 0.25 Nm
Pin assignment X806:
Designation
Number Description
technical
Interconnection
OUT
X806.1
Continuous contact, connected
to X805.1
max. 1A, 24V DC
Safety Relay IN
X806.2
Control signal input safety relay
+24V DC
Control signal (+24V DC ± 10%
/ 35mA) for the safety relay in
reference to X806.7 (GND)
Init Signal IN
X806.3
Input initialisation signal for
safety sh24Vext.
24V DC ± 10% external supply
in reference to X806.7 (GND)
Shield
X806.4
Continuous contact, connected
to X805.4, usable for shield of
the control cable
max. 1A, 24V
24V_OUT
X806.5
Output 24V DC,
connected to X805.5
24V DC ± 10%,
max. 1.8A
24V_USV*
X806.6
Short-time buffer voltage after
emergency shutdown/switch-
off
Capacitance 47mF +/-20% 24V
+/-10%
24V_GND
X806.7
Common (GND)
GND
* 24V_USV available for certain ELC-types only
1
7