1. Setting via remote control

The 

DIP switch 1

 on the detector needs to be set as shown in the 

illustration.

G

B

000

2

9

M

A

N

ALK 08/2011

ESYLUX GmbH

Postfach 1834, 22908 Ahrensburg/Germany

Internet: www.esylux.com

e-mail: [email protected] 

Button

Customised setting

Entering programming mode
Blue LED

 lights up on the detector, indicating 

“blue mode”

 

(programming mode). The connected lighting turns on.
Whilst in programming mode, the detector’s movement sensor is disabled.

   

Channel selection
C1 = lighting 

(confirmed by 

blue and red LED

 flashing alternately)

C2 = HVAC

 (confirmed by 

blue and green LED

 flashing alternately)

Set switch-on light value using the eye button or a fixed light value

   

By pressing the 

“DIM”

 button once, the dimmer begins periodically and 

automatically adjusting the light intensity of the lighting gradually between 
max. and min. values.
When the desired ambient brightness level has been reached, press the 

“eye”

 button.

The light value will be stored as the new predetermined brightness value.

   

Preset switch-on values (100 lux - daytime operation)

Confirmed by 

blue and red LED

 on the detector flashing alternately.

Adjusting the time setting – first select channel C1 or C2.

   

Determining a time setting for channel “lighting-C1”:
(channel C1 must be selected first) 1 min. to 15 min.

Confirmed by 

blue and red LED

 on the detector flashing alternately.

   

Determining a time setting for channel “HVAC-C2”:
(channel C2 must be selected first) 5 min. to 15 min. or 
short pulse:

 once the detector has been triggered by movement, 

the channel and the 

green LED

 will be switched on for 5 seconds 

and then off for 5 seconds.
Confirmed by 

blue and green LED

 on the detector flashing alternately.

Setting fully and semiautomatic operation modes – first select channel C1 or C2.

Alternating between “fully automatic” and “semiautomatic” operation modes

Semiautomatic mode = press button, the 

blue LED

 will turn off for approx. 3 seconds.

Fully automatic mode = press button, the 

blue LED

 will flash for approx. 3 seconds.

Activating the orientation light (10 % of luminous efficiency)
So-called “night-light feature”: 

if the natural light in a room/hallway decreases 

and the lighting level falls below the light value set on the detector (e.g.: 
400 lux), the lighting is automatically dimmed to approx. 10 % of the 
max. luminous efficiency. When movement is sensed, the detector turns 
the lighting up to the preset light value. If the presence detector no longer 
detects movement, the lights will revert to approx. 10 % of their maximum 
luminous efficiency once the set time has elapsed.
If the ambient brightness is greater than the preset light value, the presence 
detector will automatically switch the orientation lighting off.
Confirmed by 

blue and red LED

 on the detector flashing alternately.

   

Activating the orientation light (10 % of luminous efficiency), 
but with fixed switch-on time of 1 min. to 60 min.

Lighting has been switched on, either automatically or by manually pressing 
a button. If the presence detector no longer detects movement, the lights will 
revert to approx. 10 % of their maximum luminous efficiency once the set 
time has elapsed. The selected orientation light switch-on time (e.g. 10 min.) 
will now begin. If the detector senses new movement within this period, the 
detector turns the lighting up to the preset light value. If, however, no new 
movement is sensed within this period, the orientation light is switched off 
automatically.
Confirmed by 

blue and red LED

 on the detector flashing alternately.

Deactivating the orientation light (10 % of luminous efficiency)

Confirmed by 

blue and red LED

 on the detector flashing alternately.

Switching LEDs on/off (red/green LED)

To switch LEDs off  = press button, the 

blue LED

 will turn off for approx. 3 seconds.

To switch LEDs on = press button, the 

blue LED

 will flash for approx. 3 seconds.

Reinstating factory settings

Confirmed by 

blue and red LED

 on the detector flashing alternately.

Exiting programming mode
Blue LED

 goes out; settings are now saved.

The detector will now operate automatically according to the preset values.

  NOTE: If the programming mode is not exited by pressing the button, the 

detector automatically exits the programming mode 10 minutes after the last 
button was pressed.

Additional functions via Mobil-PDi/plus remote control

Checking the range/detection using test mode

Connected lighting turns on – for clear inspection/pacing out of a detector’s 
field of detection. Real-time, load-free indication of movement given by 
2 flashes of the 

blue LED

.

  NOTE: Exit test mode by pressing the “TEST” or “RESET” button.

   

Temporary dimming to the desired light value (replaces button)

By pressing the 

“DIM”

 button once, the dimmer begins periodically and 

automatically adjusting the light intensity of the lighting gradually between 
max. and min. values. When the desired ambient brightness level has been 
reached, press the 

“eye”

 button.

This light value will be maintained for as long as persons are present in 
the room. Should these persons leave the detection range, the presence 
detector will revert to the previous setting mode after the default time setting 
has elapsed.

Switching channel “lighting-C1” or “HVAC-C2” on/off manually 
(replaces button) – first select the channel.

Interrupting the “TEST”, “light ON/OFF” functions

The detector switches back to the corresponding set operating mode.