AIR TO WATER HEAT PUMP SYSTEM

INSTALLATION AND SERVICE MANUAL

4

EN

1.0

IMPORTANT INSTALLATION POINTS

1.1

The unit, for use with the ESTIA air to water heat pump system, is a purpose

designed unvented water cylinder.

1.2

The water cylinder

MUST

be fitted with a Pressure Relief Valve that complies

with your local Plumbing and Building Regulations.

FAILURE TO PROVIDE

ADEQUATE PRESSURE RELIEF WILL INVALIDATE ANY GUARANTEE

AND LEAD TO A DANGEROUS INSTALLATION

.

1.3

Where the inlet pressure exceeds 0.6 MPa (6 bar) a Pressure Reducing Valve

(set at max. 0.5 MPa (5 bar)) should be fitted to the inlet supply to the water

cylinder

.

This

MUST NOT

be fitted between the Pressure Relief Valve and the water

cylinder.

1.4

A Check (non-return) Valve should be fitted to the inlet supply to the water cylinder.

This

MUST NOT

be fitted between the Pressure Relief Valve and the water cylinder.

1.5

This appliance is not intended for use by persons (including children) with

reduced physical, sensory or mental capabilities, or lack of experience or

knowledge, unless they have been given supervision or instruction concerning

use of the appliance by a person responsible for their safety. Children should be

supervised to ensure that they do not play with the appliance.

2.0

INSTALLATION – GENERAL REQUIREMENTS

2.1

National Wiring Regulations may contain restrictions concerning the installation

of these units in certain areas, eg. Bathrooms.

2.2

The unit

MUST

be installed vertically.

2.3

The unit must be positioned on a level surface.

2.4

Enough space should be left around the unit for pipe connections and for access

to controls and any safety valves fitted. Refer to Diagram 1 and the Dimensions

Table to determine a suitable position for the water cylinder.

2.5

NOTE:

Ensure the floor can support the full weight of the unit (see

TECHNICAL

SPECIFICATIONS

).

2.6

DO NOT

install where the unit may freeze.

2.7

The mains water supply to the property will be supplying both the hot and cold

water requirements simultaneously. It is recommended that the maximum water

demand is assessed and the water supply checked to ensure this demand can

be satisfactorily met.

NOTE:

a high mains water pressure will not always guarantee high flow rates.

We suggest the minimum supply requirements should be 0.1 MPa (1.0 bar)

pressure and 20 litres per minute flowrate. However, at these values outlet flow

rates may be poor if several outlets are used simultaneously. The higher the

available pressure and flow rate the better the system performance.

2.8

LIMITATIONS:

The water cylinder should not be used in association with any of the following:
• Situations where maintenance is likely to be neglected or safety devices

tampered with.

Summary of Contents for HWS-1501CSHM3-E

Page 1: ...SYSTEM INSTALLATIONS UND WARTUNGSANLEITUNG 26 DE SYST M TEPELN HO ERPADLA VZDUCH VODA SERVISN A MONT N MANU L 38 CZ CR LEVEG V Z H SZIVATTY RENDSZER FELSZEREL SI S SZERVIZEL SI K ZIK N 60 HU 72 GR LUF...

Page 2: ...AL REGULATIONS PLEASE LEAVE THIS MANUAL WITH THE UNIT FOR FUTURE REFERENCE TECHNICAL SPECIFICATIONS Rated pressure 1 0 MPa 10 bar Test pressure hydraulic 1 5 MPa 15 bar Minimum recommended supply pres...

Page 3: ...shcaft m b H Petersgasse 45 A 8010 Graz Austria Hungary Magyar AIRCOND Klimaanlagen Handelsgesellshcaft m b H Petersgasse 45 A 8010 Graz Austria Greece Carrier Hellas Aircondilioning S A 4g Andersen s...

Page 4: ...nce 2 0 INSTALLATION GENERAL REQUIREMENTS 2 1 National Wiring Regulations may contain restrictions concerning the installation of these units in certain areas eg Bathrooms 2 2 The unit MUST be install...

Page 5: ...ontinuously downward direction in a frost free environment 3 2 The water connections on the unit accept direct connection of 22mm outside diameter pipe nuts and olives are supplied for this purpose Th...

Page 6: ...t on the front of the cover ISOLATE THE ELECTRICAL SUPPLY BEFORE REMOVING THE COVER 4 3 The cylinder heater MUST be earthed 4 4 All electrical wiring should be carried out by a competent electrician a...

Page 7: ...inder for long periods without draw off will become de oxygenated and potentially corrode the vessel material If the installation is to be left unused following installation and commissioning the wate...

Page 8: ...remove the thermal cut out sensing bulb from its pocket on the cylinder heater by pulling outwards Be careful not to kink the capillary tube 6 6 Remove the element tail insulating shroud by pulling it...

Page 9: ...released 8 0 USER INSTRUCTIONS 8 1 The water storage temperature at the Air to Water Heat Pump System Water Cylinder is set at the control panel of the Hydro Unit This can be set to give temperatures...

Page 10: ...correct parts are ordered 9 2 DO NOT replace with parts not recommended by the manufacturer as this will invalidate your guarantee and may render the installation dangerous 9 3 Description Part No Cy...

Page 11: ...sor 1 Cylinder heater thermal cut out has operated 2 Faulty water cylinder temperature sensor 1 Water storage temperature on Heat Pump Controller is set too high 2 Faulty water cylinder temperature se...

Page 12: ...ervice within a period of 7 days If this is not the case it must either be drained or regularly flushed as required in the section Commissioning Warning 11 7 The unit is NOT guaranteed against damage...

Page 13: ...or the distributor In case of installation of a new product it may be possible to have the distributor pick up old WEEE directly The producer importer and distributor are responsible for collection a...

Page 14: ...129 NOTES...

Page 15: ...130 NOTES...