In a building, distribution lines must be installed horizontally or vertically.
They should be protected in casing pipes (like plastic or iron water pipes, to be
selected according to the technical requirements of indoor distribution). Metal
hoses are applicable to ceiling wiring, but must be secure and good-looking.
Shielding measures and shielding connection: If the electromagnetic
interference in the wring environment is found strong in the survey before
construction, it is necessary to consider shielding protection for data cables
when designing a construction scheme. Overall shielding protection is required
if there is a large radioactive interference source or wiring has to be parallel
with a large-current power supply on the construction site. Generally, shielding
measures include: Keeping a maximum distance from any interference source,
and using metal wiring troughs or galvanized metal water pipes to ensure
reliable grounding of the connection between the shielding layers of data
cables and the metal troughs or pipes. Note that a shielding enclosure can have
a shielding effect only when it is grounded reliably.
Ground wire connection method: Reliable large-diameter ground wires in
compliance with applicable national standards are needed on the wiring site,
and should be connected in a tree form to avoid DC loop. These ground wires
must be kept far away from lightning fields. No lightning conductor can serve
as a ground wire, and ensure there is no lightning current through any ground
wire when there is lightning. Metal wiring troughs and pipes must be
connected continuously and reliably, and linked to ground wires through
large-diameter wires. The impedance of this section of wire cannot exceed
2ohm. The shielding layer also must be connected reliably, and grounded at
one end to guarantee uniform current direction. The ground wire of the
shielding layer must be connected through a larger wire (not smaller than
2.5mm
2
).
28
Installation Guide for inBIO
4
60 Series Control Panel
Summary of Contents for inBIO460 Series
Page 1: ...Security at Fingertips www esslsecurity com...
Page 2: ......
Page 16: ...3 Connection and Installation inBIO260 terminal connection diagram 13...
Page 17: ...inBIO460 terminal connection diagram 14 Installation Guide for inBIO460 Series Control Panel...
Page 27: ...24 Installation Guide for inBIO460 Series Control Panel...
Page 37: ...between 485 and 485 34 Installation Guide for inBIO460 Series Control Panel...