4. System Networking
4. System Networking
4.1 System Wiring and Wires Requirements
1. RS485 communication wires are made of internationally accepted shielded
twisted pairs, which provide effective protection and shield of interference.
2. The power supply is 12V DC converted from 220V.
3. The Wiegand readers use 6-core communication shielded wires (RVVP 6×0.5mm)
(usually there are 6, 8, and 10-core types available for users to select) to reduce
interference during transmission.
4. As an electronic lock has a big current, it generates strong interference signal
during an action. To reduce the effect of an electronic lock during an action on other
elements, 4-core wires (RVV 4×0.75mm
2
, two for a power supply and two for door
sensor) are recommended.
5. For EXT485 communication, we suggest to use 4-conducotor wire (RVVP
4*0.5mm)
6. Other control cables (like exit buttons) are all made of 2-core wires (RVV
2×0.5mm
2
).
7. Notes for wiring:
Signal wires (like network cables and RS-485 wires) can neither run in parallel
with nor share one casing pipe with large-power electric wires (like electronic
lock wires and power cables). If parallel wiring is unavoidable for
environmental reasons, the distance must be over 50cm.
Try to avoid using any wire with a connector during wiring. When a connector
is indispensable, it must be crimped or welded. No mechanical force can be
applied to the joint or branch of conductors.
27
Summary of Contents for inBIO460 Series
Page 1: ...Security at Fingertips www esslsecurity com...
Page 2: ......
Page 16: ...3 Connection and Installation inBIO260 terminal connection diagram 13...
Page 17: ...inBIO460 terminal connection diagram 14 Installation Guide for inBIO460 Series Control Panel...
Page 27: ...24 Installation Guide for inBIO460 Series Control Panel...
Page 37: ...between 485 and 485 34 Installation Guide for inBIO460 Series Control Panel...