3. Connection and Installation
we suggest changing the bigger one, such as 12V/5A. Except the power
consumption reserved, there are 2A current for the lock. For the common electrical
lock (the standby current is 300mA, the max current is 500mA), the max connected
lock is 4.
4) To protect the access control system against the self-induced electromotive force
generated by an electronic lock at the instant of switching off/on, it is necessary to
connect a diode in parallel (please use the FR107 delivered with the system) with
the electronic lock to release the self-induced electromotive force.
1. Wet mode: External power supply for NO Lock
2. Wet mode: External power supply for NC Lock
21